COMAP-VISA DEFINITIONS ::= BEGIN
|
|
--******************************************************************--
|
IMPORTS
|
OBJECT-GROUP, NOTIFICATION-GROUP
|
FROM SNMPv2-CONF
|
Gauge32, Integer32, OBJECT-TYPE, MODULE-IDENTITY, NOTIFICATION-TYPE, enterprises
|
FROM SNMPv2-SMI
|
DisplayString
|
FROM SNMPv2-TC;
|
|
visa MODULE-IDENTITY
|
LAST-UPDATED "202104211009Z"
|
ORGANIZATION "ComAp a.s."
|
CONTACT-INFO "ComAp"
|
DESCRIPTION "VISA"
|
REVISION "202104211009Z"
|
DESCRIPTION "None"
|
::= {enterprises 28634 17}
|
|
--******************************************************************--
|
|
notifications OBJECT IDENTIFIER ::= { visa 0 }
|
groupRdFix OBJECT IDENTIFIER ::= { visa 1 }
|
groupRdCfg OBJECT IDENTIFIER ::= { visa 2 }
|
groupWrFix OBJECT IDENTIFIER ::= { visa 3 }
|
groupWrCfg OBJECT IDENTIFIER ::= { visa 4 }
|
groupW OBJECT IDENTIFIER ::= { visa 5 }
|
notificationData OBJECT IDENTIFIER ::= { visa 6 }
|
conformanceGroups OBJECT IDENTIFIER ::= { visa 10}
|
|
--******************************************************************--
|
|
|
--******************************************************************--
|
|
conformanceGroupRdCfg OBJECT-GROUP
|
OBJECTS { vGeneratorVoltageL1N, vGeneratorVoltageL2N, vGeneratorVoltageL3N, vMainsVoltageL1N, vMainsVoltageL2N,
|
vMainsVoltageL3N, vLoadAL1, vLoadAL2, vLoadAL3, vLoadKW,
|
vLoadKVAr, vLoadPowerFactor, vGensetKWh, vRunningHours, vNumStarts,
|
vGeneratorFrequency, vMainsFrequency, vBatteryVoltage, vBinaryInputs, vBinaryOutputs,
|
vLoadCharacteristic, vLoadKWL1, vLoadKWL2, vLoadKWL3, vLoadKVArL1,
|
vLoadKVArL2, vLoadKVArL3, vLoadKVAL1, vLoadKVAL2, vLoadKVAL3,
|
vLoadPowerFactorL1, vLoadPowerFactorL2, vLoadPowerFactorL3, vGensetKVArh, vLoadKVA,
|
vLoadCharacteristicL1, vLoadCharacteristicL2, vLoadCharacteristicL3, vTotalFuelConsumption, vNotUsed,
|
vNotUsed, vFuelLevel, vBatteryCharg, vGeneratorVoltageL1L2, vGeneratorVoltageL2L3,
|
vGeneratorVoltageL3L1, vMainsVoltageL1L2, vMainsVoltageL2L3, vMainsVoltageL3L1, vControlerMode,
|
vCUTemperature, vMaintenance1, vMaintenance2, vMaintenance3, vDPlus,
|
vMainsKWh, vMainsKVArh, vNumEStops, vShutdowns, vDate,
|
vTime }
|
STATUS current
|
DESCRIPTION "Objects for reading only"
|
::= { conformanceGroups 1 }
|
|
vGeneratorVoltageL1N OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 8192 }
|
|
vGeneratorVoltageL2N OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 8193 }
|
|
vGeneratorVoltageL3N OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 8194 }
|
|
vMainsVoltageL1N OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 8195 }
|
|
vMainsVoltageL2N OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 8196 }
|
|
vMainsVoltageL3N OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 8197 }
|
|
vLoadAL1 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='A'"
|
::= { groupRdCfg 8198 }
|
|
vLoadAL2 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='A'"
|
::= { groupRdCfg 8199 }
|
|
vLoadAL3 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='A'"
|
::= { groupRdCfg 8200 }
|
|
vLoadKW OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kW'"
|
::= { groupRdCfg 8202 }
|
|
vLoadKVAr OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVAr'"
|
::= { groupRdCfg 8203 }
|
|
vLoadPowerFactor OBJECT-TYPE
|
SYNTAX Integer32(-128..127)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=2, UNIT=''"
|
::= { groupRdCfg 8204 }
|
|
vGensetKWh OBJECT-TYPE
|
SYNTAX Integer32
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kWh'"
|
::= { groupRdCfg 8205 }
|
|
vRunningHours OBJECT-TYPE
|
SYNTAX Integer32
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=1, UNIT='h'"
|
::= { groupRdCfg 8206 }
|
|
vNumStarts OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT=''"
|
::= { groupRdCfg 8207 }
|
|
vGeneratorFrequency OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=1, UNIT='Hz'"
|
::= { groupRdCfg 8210 }
|
|
vMainsFrequency OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=1, UNIT='Hz'"
|
::= { groupRdCfg 8211 }
|
|
vBatteryVoltage OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=1, UNIT='V'"
|
::= { groupRdCfg 8213 }
|
|
vBinaryInputs OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "BINARY, BITS=8"
|
::= { groupRdCfg 8235 }
|
|
vBinaryOutputs OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "BINARY, BITS=8"
|
::= { groupRdCfg 8239 }
|
|
vLoadCharacteristic OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "String"
|
::= { groupRdCfg 8395 }
|
|
vLoadKWL1 OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kW'"
|
::= { groupRdCfg 8524 }
|
|
vLoadKWL2 OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kW'"
|
::= { groupRdCfg 8525 }
|
|
vLoadKWL3 OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kW'"
|
::= { groupRdCfg 8526 }
|
|
vLoadKVArL1 OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVAr'"
|
::= { groupRdCfg 8527 }
|
|
vLoadKVArL2 OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVAr'"
|
::= { groupRdCfg 8528 }
|
|
vLoadKVArL3 OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVAr'"
|
::= { groupRdCfg 8529 }
|
|
vLoadKVAL1 OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVA'"
|
::= { groupRdCfg 8530 }
|
|
vLoadKVAL2 OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVA'"
|
::= { groupRdCfg 8531 }
|
|
vLoadKVAL3 OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVA'"
|
::= { groupRdCfg 8532 }
|
|
vLoadPowerFactorL1 OBJECT-TYPE
|
SYNTAX Integer32(-128..127)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=2, UNIT=''"
|
::= { groupRdCfg 8533 }
|
|
vLoadPowerFactorL2 OBJECT-TYPE
|
SYNTAX Integer32(-128..127)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=2, UNIT=''"
|
::= { groupRdCfg 8534 }
|
|
vLoadPowerFactorL3 OBJECT-TYPE
|
SYNTAX Integer32(-128..127)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=2, UNIT=''"
|
::= { groupRdCfg 8535 }
|
|
vGensetKVArh OBJECT-TYPE
|
SYNTAX Integer32
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVArh'"
|
::= { groupRdCfg 8539 }
|
|
vLoadKVA OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVA'"
|
::= { groupRdCfg 8565 }
|
|
vLoadCharacteristicL1 OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "String"
|
::= { groupRdCfg 8626 }
|
|
vLoadCharacteristicL2 OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "String"
|
::= { groupRdCfg 8627 }
|
|
vLoadCharacteristicL3 OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "String"
|
::= { groupRdCfg 8628 }
|
|
vTotalFuelConsumption OBJECT-TYPE
|
SYNTAX Gauge32
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='L'"
|
::= { groupRdCfg 9040 }
|
|
vNotUsed OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT=''"
|
::= { groupRdCfg 9151 }
|
|
vNotUsed OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT=''"
|
::= { groupRdCfg 9152 }
|
|
vFuelLevel OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='Percent'"
|
::= { groupRdCfg 9153 }
|
|
vBatteryCharg OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='Ohm'"
|
::= { groupRdCfg 9154 }
|
|
vGeneratorVoltageL1L2 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 9628 }
|
|
vGeneratorVoltageL2L3 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 9629 }
|
|
vGeneratorVoltageL3L1 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 9630 }
|
|
vMainsVoltageL1L2 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 9631 }
|
|
vMainsVoltageL2L3 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 9632 }
|
|
vMainsVoltageL3L1 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='V'"
|
::= { groupRdCfg 9633 }
|
|
vControlerMode OBJECT-TYPE
|
SYNTAX Integer32(0..255)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "LIST, 0-OFF, 1-MAN, 2-AUTO, 3-TEST"
|
::= { groupRdCfg 9887 }
|
|
vCUTemperature OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=1, UNIT='DegreeC'"
|
::= { groupRdCfg 10124 }
|
|
vMaintenance1 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='h'"
|
::= { groupRdCfg 10528 }
|
|
vMaintenance2 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='h'"
|
::= { groupRdCfg 10529 }
|
|
vMaintenance3 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='h'"
|
::= { groupRdCfg 10530 }
|
|
vDPlus OBJECT-TYPE
|
SYNTAX Integer32(-32768..32767)
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=1, UNIT='V'"
|
::= { groupRdCfg 10603 }
|
|
vMainsKWh OBJECT-TYPE
|
SYNTAX Integer32
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kWh'"
|
::= { groupRdCfg 11025 }
|
|
vMainsKVArh OBJECT-TYPE
|
SYNTAX Integer32
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='kVArh'"
|
::= { groupRdCfg 11026 }
|
|
vNumEStops OBJECT-TYPE
|
SYNTAX Gauge32
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT=''"
|
::= { groupRdCfg 11195 }
|
|
vShutdowns OBJECT-TYPE
|
SYNTAX Gauge32
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT=''"
|
::= { groupRdCfg 11196 }
|
|
vDate OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "Date"
|
::= { groupRdCfg 24553 }
|
|
vTime OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS read-only
|
STATUS current
|
DESCRIPTION "Time"
|
::= { groupRdCfg 24554 }
|
|
|
|
|
--******************************************************************--
|
|
conformanceGroupWrFix OBJECT-GROUP
|
OBJECTS { pfActionArgument }
|
STATUS current
|
DESCRIPTION "Objects for read/write"
|
::= { conformanceGroups 2 }
|
|
pfActionArgument OBJECT-TYPE
|
SYNTAX Gauge32
|
MAX-ACCESS read-write
|
STATUS current
|
DESCRIPTION "Command argument"
|
::= { groupWrFix 24550 }
|
|
|
--******************************************************************--
|
|
conformanceGroupWrCfg OBJECT-GROUP
|
OBJECTS { pControllerMode, pGenSetName, pMaintenanceTimer1, pMaintenanceTimer2, pMaintenanceTimer3 }
|
STATUS current
|
DESCRIPTION "Objects for read/write"
|
::= { conformanceGroups 3 }
|
|
pControllerMode OBJECT-TYPE
|
SYNTAX Integer32(0..255)
|
MAX-ACCESS read-write
|
STATUS current
|
DESCRIPTION "LIST, 0-OFF, 1-MAN, 2-AUTO, 3-TEST"
|
::= { groupWrCfg 8315 }
|
|
pGenSetName OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS read-write
|
STATUS current
|
DESCRIPTION "String"
|
::= { groupWrCfg 8637 }
|
|
pMaintenanceTimer1 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-write
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='h'"
|
::= { groupWrCfg 10528 }
|
|
pMaintenanceTimer2 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-write
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='h'"
|
::= { groupWrCfg 10529 }
|
|
pMaintenanceTimer3 OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-write
|
STATUS current
|
DESCRIPTION "DEC=0, UNIT='h'"
|
::= { groupWrCfg 10530 }
|
|
|
|
|
--******************************************************************--
|
|
conformanceGroupW OBJECT-GROUP
|
OBJECTS { pfPassword, pfActionCommand }
|
STATUS current
|
DESCRIPTION "Objects for writing only"
|
::= { conformanceGroups 4 }
|
|
pfPassword OBJECT-TYPE
|
SYNTAX Integer32(0..9999)
|
MAX-ACCESS read-write
|
STATUS current
|
DESCRIPTION "User password"
|
::= { groupW 24524 }
|
|
pfActionCommand OBJECT-TYPE
|
SYNTAX Integer32(0..65535)
|
MAX-ACCESS read-write
|
STATUS current
|
DESCRIPTION "Command"
|
::= { groupW 24551 }
|
|
|
--******************************************************************--
|
|
conformanceGroupNotifData OBJECT-GROUP
|
OBJECTS { tControllerName, tSerNum, tTrapText }
|
STATUS current
|
DESCRIPTION "Objects for trap bindings, not accessible"
|
::= { conformanceGroups 5 }
|
|
tControllerName OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS accessible-for-notify
|
STATUS current
|
DESCRIPTION "Name of the controller."
|
::= { notificationData 1 }
|
|
tSerNum OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS accessible-for-notify
|
STATUS current
|
DESCRIPTION "Serial number of the controller."
|
::= { notificationData 2 }
|
|
tTrapText OBJECT-TYPE
|
SYNTAX DisplayString
|
MAX-ACCESS accessible-for-notify
|
STATUS current
|
DESCRIPTION "Trap reason description."
|
::= { notificationData 3 }
|
|
|
--******************************************************************--
|
|
conformanceGroupNotifications NOTIFICATION-GROUP
|
NOTIFICATIONS { tRemoteStartCHR2FStopL1Activated, tRemoteStartCHR2FStopL1Disappeared, tRemoteStartCHR2FStopL1AlarmReset, tRemoteStartCHR2FStopL2Activated, tRemoteStartCHR2FStopL2Disappeared,
|
tRemoteStartCHR2FStopL2AlarmReset, tRemoteStartCHR2FStopSFActivated, tRemoteStartCHR2FStopSFDisappeared, tRemoteStartCHR2FStopSFAlarmReset, tRemTESTOnLoadL1Activated,
|
tRemTESTOnLoadL1Disappeared, tRemTESTOnLoadL1AlarmReset, tRemTESTOnLoadL2Activated, tRemTESTOnLoadL2Disappeared, tRemTESTOnLoadL2AlarmReset,
|
tRemTESTOnLoadSFActivated, tRemTESTOnLoadSFDisappeared, tRemTESTOnLoadSFAlarmReset, tFuelLeakL1Activated, tFuelLeakL1Disappeared,
|
tFuelLeakL1AlarmReset, tFuelLeakL2Activated, tFuelLeakL2Disappeared, tFuelLeakL2AlarmReset, tFuelLeakSFActivated,
|
tFuelLeakSFDisappeared, tFuelLeakSFAlarmReset, tLowOilLevelL1Activated, tLowOilLevelL1Disappeared, tLowOilLevelL1AlarmReset,
|
tLowOilLevelL2Activated, tLowOilLevelL2Disappeared, tLowOilLevelL2AlarmReset, tLowOilLevelSFActivated, tLowOilLevelSFDisappeared,
|
tLowOilLevelSFAlarmReset, tLowCoolantLevelL1Activated, tLowCoolantLevelL1Disappeared, tLowCoolantLevelL1AlarmReset, tLowCoolantLevelL2Activated,
|
tLowCoolantLevelL2Disappeared, tLowCoolantLevelL2AlarmReset, tLowCoolantLevelSFActivated, tLowCoolantLevelSFDisappeared, tLowCoolantLevelSFAlarmReset,
|
tEmergencyStopL1Activated1, tEmergencyStopL1Disappeared1, tEmergencyStopL1AlarmReset1, tEmergencyStopL2Activated1, tEmergencyStopL2Disappeared1,
|
tEmergencyStopL2AlarmReset1, tEmergencyStopSFActivated1, tEmergencyStopSFDisappeared1, tEmergencyStopSFAlarmReset1, tFuelLevelL1Activated,
|
tFuelLevelL1Disappeared, tFuelLevelL1AlarmReset, tFuelLevelL2Activated, tFuelLevelL2Disappeared, tFuelLevelL2AlarmReset,
|
tFuelLevelSFActivated, tFuelLevelSFDisappeared, tFuelLevelSFAlarmReset, tBatteryChargL1Activated, tBatteryChargL1Disappeared,
|
tBatteryChargL1AlarmReset, tBatteryChargL2Activated, tBatteryChargL2Disappeared, tBatteryChargL2AlarmReset, tBatteryChargSFActivated,
|
tBatteryChargSFDisappeared, tBatteryChargSFAlarmReset, tEngineSpeedL1Activated, tEngineSpeedL1Disappeared, tEngineSpeedL1AlarmReset,
|
tEngineSpeedL2Activated, tEngineSpeedL2Disappeared, tEngineSpeedL2AlarmReset, tEngineSpeedSFActivated, tEngineSpeedSFDisappeared,
|
tEngineSpeedSFAlarmReset, tFuelRateL1Activated, tFuelRateL1Disappeared, tFuelRateL1AlarmReset, tFuelRateL2Activated,
|
tFuelRateL2Disappeared, tFuelRateL2AlarmReset, tFuelRateSFActivated, tFuelRateSFDisappeared, tFuelRateSFAlarmReset,
|
tCoolantTempL1Activated, tCoolantTempL1Disappeared, tCoolantTempL1AlarmReset, tCoolantTempL2Activated, tCoolantTempL2Disappeared,
|
tCoolantTempL2AlarmReset, tCoolantTempSFActivated, tCoolantTempSFDisappeared, tCoolantTempSFAlarmReset, tOilPressL1Activated,
|
tOilPressL1Disappeared, tOilPressL1AlarmReset, tOilPressL2Activated, tOilPressL2Disappeared, tOilPressL2AlarmReset,
|
tOilPressSFActivated, tOilPressSFDisappeared, tOilPressSFAlarmReset, tAlCHR2FHistCHR2Emsg1L1Activated, tAlCHR2FHistCHR2Emsg1L1Disappeared,
|
tAlCHR2FHistCHR2Emsg1L1AlarmReset, tAlCHR2FHistCHR2Emsg1L2Activated, tAlCHR2FHistCHR2Emsg1L2Disappeared, tAlCHR2FHistCHR2Emsg1L2AlarmReset, tAlCHR2FHistCHR2Emsg1SFActivated,
|
tAlCHR2FHistCHR2Emsg1SFDisappeared, tAlCHR2FHistCHR2Emsg1SFAlarmReset, tAlCHR2FHistCHR2Emsg2L1Activated, tAlCHR2FHistCHR2Emsg2L1Disappeared, tAlCHR2FHistCHR2Emsg2L1AlarmReset,
|
tAlCHR2FHistCHR2Emsg2L2Activated, tAlCHR2FHistCHR2Emsg2L2Disappeared, tAlCHR2FHistCHR2Emsg2L2AlarmReset, tAlCHR2FHistCHR2Emsg2SFActivated, tAlCHR2FHistCHR2Emsg2SFDisappeared,
|
tAlCHR2FHistCHR2Emsg2SFAlarmReset, tAlCHR2FHistCHR2Emsg3L1Activated, tAlCHR2FHistCHR2Emsg3L1Disappeared, tAlCHR2FHistCHR2Emsg3L1AlarmReset, tAlCHR2FHistCHR2Emsg3L2Activated,
|
tAlCHR2FHistCHR2Emsg3L2Disappeared, tAlCHR2FHistCHR2Emsg3L2AlarmReset, tAlCHR2FHistCHR2Emsg3SFActivated, tAlCHR2FHistCHR2Emsg3SFDisappeared, tAlCHR2FHistCHR2Emsg3SFAlarmReset,
|
tAlCHR2FHistCHR2Emsg4L1Activated, tAlCHR2FHistCHR2Emsg4L1Disappeared, tAlCHR2FHistCHR2Emsg4L1AlarmReset, tAlCHR2FHistCHR2Emsg4L2Activated, tAlCHR2FHistCHR2Emsg4L2Disappeared,
|
tAlCHR2FHistCHR2Emsg4L2AlarmReset, tAlCHR2FHistCHR2Emsg4SFActivated, tAlCHR2FHistCHR2Emsg4SFDisappeared, tAlCHR2FHistCHR2Emsg4SFAlarmReset, tAlCHR2FHistCHR2Emsg5L1Activated,
|
tAlCHR2FHistCHR2Emsg5L1Disappeared, tAlCHR2FHistCHR2Emsg5L1AlarmReset, tAlCHR2FHistCHR2Emsg5L2Activated, tAlCHR2FHistCHR2Emsg5L2Disappeared, tAlCHR2FHistCHR2Emsg5L2AlarmReset,
|
tAlCHR2FHistCHR2Emsg5SFActivated, tAlCHR2FHistCHR2Emsg5SFDisappeared, tAlCHR2FHistCHR2Emsg5SFAlarmReset, tAlCHR2FHistCHR2Emsg6L1Activated, tAlCHR2FHistCHR2Emsg6L1Disappeared,
|
tAlCHR2FHistCHR2Emsg6L1AlarmReset, tAlCHR2FHistCHR2Emsg6L2Activated, tAlCHR2FHistCHR2Emsg6L2Disappeared, tAlCHR2FHistCHR2Emsg6L2AlarmReset, tAlCHR2FHistCHR2Emsg6SFActivated,
|
tAlCHR2FHistCHR2Emsg6SFDisappeared, tAlCHR2FHistCHR2Emsg6SFAlarmReset, tAlCHR2FHistCHR2Emsg7L1Activated, tAlCHR2FHistCHR2Emsg7L1Disappeared, tAlCHR2FHistCHR2Emsg7L1AlarmReset,
|
tAlCHR2FHistCHR2Emsg7L2Activated, tAlCHR2FHistCHR2Emsg7L2Disappeared, tAlCHR2FHistCHR2Emsg7L2AlarmReset, tAlCHR2FHistCHR2Emsg7SFActivated, tAlCHR2FHistCHR2Emsg7SFDisappeared,
|
tAlCHR2FHistCHR2Emsg7SFAlarmReset, tAlCHR2FHistCHR2Emsg8L1Activated, tAlCHR2FHistCHR2Emsg8L1Disappeared, tAlCHR2FHistCHR2Emsg8L1AlarmReset, tAlCHR2FHistCHR2Emsg8L2Activated,
|
tAlCHR2FHistCHR2Emsg8L2Disappeared, tAlCHR2FHistCHR2Emsg8L2AlarmReset, tAlCHR2FHistCHR2Emsg8SFActivated, tAlCHR2FHistCHR2Emsg8SFDisappeared, tAlCHR2FHistCHR2Emsg8SFAlarmReset,
|
tAlCHR2FHistCHR2Emsg9L1Activated, tAlCHR2FHistCHR2Emsg9L1Disappeared, tAlCHR2FHistCHR2Emsg9L1AlarmReset, tAlCHR2FHistCHR2Emsg9L2Activated, tAlCHR2FHistCHR2Emsg9L2Disappeared,
|
tAlCHR2FHistCHR2Emsg9L2AlarmReset, tAlCHR2FHistCHR2Emsg9SFActivated, tAlCHR2FHistCHR2Emsg9SFDisappeared, tAlCHR2FHistCHR2Emsg9SFAlarmReset, tAlCHR2FHistCHR2Emsg10L1Activated,
|
tAlCHR2FHistCHR2Emsg10L1Disappeared, tAlCHR2FHistCHR2Emsg10L1AlarmReset, tAlCHR2FHistCHR2Emsg10L2Activated, tAlCHR2FHistCHR2Emsg10L2Disappeared, tAlCHR2FHistCHR2Emsg10L2AlarmReset,
|
tAlCHR2FHistCHR2Emsg10SFActivated, tAlCHR2FHistCHR2Emsg10SFDisappeared, tAlCHR2FHistCHR2Emsg10SFAlarmReset, tAlCHR2FHistCHR2Emsg11L1Activated, tAlCHR2FHistCHR2Emsg11L1Disappeared,
|
tAlCHR2FHistCHR2Emsg11L1AlarmReset, tAlCHR2FHistCHR2Emsg11L2Activated, tAlCHR2FHistCHR2Emsg11L2Disappeared, tAlCHR2FHistCHR2Emsg11L2AlarmReset, tAlCHR2FHistCHR2Emsg11SFActivated,
|
tAlCHR2FHistCHR2Emsg11SFDisappeared, tAlCHR2FHistCHR2Emsg11SFAlarmReset, tAlCHR2FHistCHR2Emsg12L1Activated, tAlCHR2FHistCHR2Emsg12L1Disappeared, tAlCHR2FHistCHR2Emsg12L1AlarmReset,
|
tAlCHR2FHistCHR2Emsg12L2Activated, tAlCHR2FHistCHR2Emsg12L2Disappeared, tAlCHR2FHistCHR2Emsg12L2AlarmReset, tAlCHR2FHistCHR2Emsg12SFActivated, tAlCHR2FHistCHR2Emsg12SFDisappeared,
|
tAlCHR2FHistCHR2Emsg12SFAlarmReset, tAlCHR2FHistCHR2Emsg13L1Activated, tAlCHR2FHistCHR2Emsg13L1Disappeared, tAlCHR2FHistCHR2Emsg13L1AlarmReset, tAlCHR2FHistCHR2Emsg13L2Activated,
|
tAlCHR2FHistCHR2Emsg13L2Disappeared, tAlCHR2FHistCHR2Emsg13L2AlarmReset, tAlCHR2FHistCHR2Emsg13SFActivated, tAlCHR2FHistCHR2Emsg13SFDisappeared, tAlCHR2FHistCHR2Emsg13SFAlarmReset,
|
tAlCHR2FHistCHR2Emsg14L1Activated, tAlCHR2FHistCHR2Emsg14L1Disappeared, tAlCHR2FHistCHR2Emsg14L1AlarmReset, tAlCHR2FHistCHR2Emsg14L2Activated, tAlCHR2FHistCHR2Emsg14L2Disappeared,
|
tAlCHR2FHistCHR2Emsg14L2AlarmReset, tAlCHR2FHistCHR2Emsg14SFActivated, tAlCHR2FHistCHR2Emsg14SFDisappeared, tAlCHR2FHistCHR2Emsg14SFAlarmReset, tAlCHR2FHistCHR2Emsg15L1Activated,
|
tAlCHR2FHistCHR2Emsg15L1Disappeared, tAlCHR2FHistCHR2Emsg15L1AlarmReset, tAlCHR2FHistCHR2Emsg15L2Activated, tAlCHR2FHistCHR2Emsg15L2Disappeared, tAlCHR2FHistCHR2Emsg15L2AlarmReset,
|
tAlCHR2FHistCHR2Emsg15SFActivated, tAlCHR2FHistCHR2Emsg15SFDisappeared, tAlCHR2FHistCHR2Emsg15SFAlarmReset, tAlCHR2FHistCHR2Emsg16L1Activated, tAlCHR2FHistCHR2Emsg16L1Disappeared,
|
tAlCHR2FHistCHR2Emsg16L1AlarmReset, tAlCHR2FHistCHR2Emsg16L2Activated, tAlCHR2FHistCHR2Emsg16L2Disappeared, tAlCHR2FHistCHR2Emsg16L2AlarmReset, tAlCHR2FHistCHR2Emsg16SFActivated,
|
tAlCHR2FHistCHR2Emsg16SFDisappeared, tAlCHR2FHistCHR2Emsg16SFAlarmReset, tBatteryChargerL1Activated, tBatteryChargerL1Disappeared, tBatteryChargerL1AlarmReset,
|
tBatteryChargerL2Activated, tBatteryChargerL2Disappeared, tBatteryChargerL2AlarmReset, tBatteryChargerSFActivated, tBatteryChargerSFDisappeared,
|
tBatteryChargerSFAlarmReset, tForceProtCHR2E2L1Activated, tForceProtCHR2E2L1Disappeared, tForceProtCHR2E2L1AlarmReset, tForceProtCHR2E2L2Activated,
|
tForceProtCHR2E2L2Disappeared, tForceProtCHR2E2L2AlarmReset, tForceProtCHR2E2SFActivated, tForceProtCHR2E2SFDisappeared, tForceProtCHR2E2SFAlarmReset,
|
tModuleBroSlotABrcFalseModuleL1Activated, tModuleBroSlotABrcFalseModuleL1Disappeared, tModuleBroSlotABrcFalseModuleL1AlarmReset, tModuleBroSlotABrcFalseModuleL2Activated, tModuleBroSlotABrcFalseModuleL2Disappeared,
|
tModuleBroSlotABrcFalseModuleL2AlarmReset, tModuleBroSlotABrcFalseModuleSFActivated, tModuleBroSlotABrcFalseModuleSFDisappeared, tModuleBroSlotABrcFalseModuleSFAlarmReset, tModuleBroSlotBBrcFalseModuleL1Activated,
|
tModuleBroSlotBBrcFalseModuleL1Disappeared, tModuleBroSlotBBrcFalseModuleL1AlarmReset, tModuleBroSlotBBrcFalseModuleL2Activated, tModuleBroSlotBBrcFalseModuleL2Disappeared, tModuleBroSlotBBrcFalseModuleL2AlarmReset,
|
tModuleBroSlotBBrcFalseModuleSFActivated, tModuleBroSlotBBrcFalseModuleSFDisappeared, tModuleBroSlotBBrcFalseModuleSFAlarmReset, tModuleBroSlotABrcUnknownModuleL1Activated, tModuleBroSlotABrcUnknownModuleL1Disappeared,
|
tModuleBroSlotABrcUnknownModuleL1AlarmReset, tModuleBroSlotABrcUnknownModuleL2Activated, tModuleBroSlotABrcUnknownModuleL2Disappeared, tModuleBroSlotABrcUnknownModuleL2AlarmReset, tModuleBroSlotABrcUnknownModuleSFActivated,
|
tModuleBroSlotABrcUnknownModuleSFDisappeared, tModuleBroSlotABrcUnknownModuleSFAlarmReset, tModuleBroSlotBBrcUnknownModuleL1Activated, tModuleBroSlotBBrcUnknownModuleL1Disappeared, tModuleBroSlotBBrcUnknownModuleL1AlarmReset,
|
tModuleBroSlotBBrcUnknownModuleL2Activated, tModuleBroSlotBBrcUnknownModuleL2Disappeared, tModuleBroSlotBBrcUnknownModuleL2AlarmReset, tModuleBroSlotBBrcUnknownModuleSFActivated, tModuleBroSlotBBrcUnknownModuleSFDisappeared,
|
tModuleBroSlotBBrcUnknownModuleSFAlarmReset, tModuleBroSlotABrcUnattendedL1Activated, tModuleBroSlotABrcUnattendedL1Disappeared, tModuleBroSlotABrcUnattendedL1AlarmReset, tModuleBroSlotABrcUnattendedL2Activated,
|
tModuleBroSlotABrcUnattendedL2Disappeared, tModuleBroSlotABrcUnattendedL2AlarmReset, tModuleBroSlotABrcUnattendedSFActivated, tModuleBroSlotABrcUnattendedSFDisappeared, tModuleBroSlotABrcUnattendedSFAlarmReset,
|
tModuleBroSlotBBrcUnattendedL1Activated, tModuleBroSlotBBrcUnattendedL1Disappeared, tModuleBroSlotBBrcUnattendedL1AlarmReset, tModuleBroSlotBBrcUnattendedL2Activated, tModuleBroSlotBBrcUnattendedL2Disappeared,
|
tModuleBroSlotBBrcUnattendedL2AlarmReset, tModuleBroSlotBBrcUnattendedSFActivated, tModuleBroSlotBBrcUnattendedSFDisappeared, tModuleBroSlotBBrcUnattendedSFAlarmReset, tModuleBroSlotABrcCommCHR2EOutageL1Activated,
|
tModuleBroSlotABrcCommCHR2EOutageL1Disappeared, tModuleBroSlotABrcCommCHR2EOutageL1AlarmReset, tModuleBroSlotABrcCommCHR2EOutageL2Activated, tModuleBroSlotABrcCommCHR2EOutageL2Disappeared, tModuleBroSlotABrcCommCHR2EOutageL2AlarmReset,
|
tModuleBroSlotABrcCommCHR2EOutageSFActivated, tModuleBroSlotABrcCommCHR2EOutageSFDisappeared, tModuleBroSlotABrcCommCHR2EOutageSFAlarmReset, tModuleBroSlotBBrcCommCHR2EOutageL1Activated, tModuleBroSlotBBrcCommCHR2EOutageL1Disappeared,
|
tModuleBroSlotBBrcCommCHR2EOutageL1AlarmReset, tModuleBroSlotBBrcCommCHR2EOutageL2Activated, tModuleBroSlotBBrcCommCHR2EOutageL2Disappeared, tModuleBroSlotBBrcCommCHR2EOutageL2AlarmReset, tModuleBroSlotBBrcCommCHR2EOutageSFActivated,
|
tModuleBroSlotBBrcCommCHR2EOutageSFDisappeared, tModuleBroSlotBBrcCommCHR2EOutageSFAlarmReset, tModuleBroSlotABrcUnexpectedL1Activated, tModuleBroSlotABrcUnexpectedL1Disappeared, tModuleBroSlotABrcUnexpectedL1AlarmReset,
|
tModuleBroSlotABrcUnexpectedL2Activated, tModuleBroSlotABrcUnexpectedL2Disappeared, tModuleBroSlotABrcUnexpectedL2AlarmReset, tModuleBroSlotABrcUnexpectedSFActivated, tModuleBroSlotABrcUnexpectedSFDisappeared,
|
tModuleBroSlotABrcUnexpectedSFAlarmReset, tModuleBroSlotBBrcUnexpectedL1Activated, tModuleBroSlotBBrcUnexpectedL1Disappeared, tModuleBroSlotBBrcUnexpectedL1AlarmReset, tModuleBroSlotBBrcUnexpectedL2Activated,
|
tModuleBroSlotBBrcUnexpectedL2Disappeared, tModuleBroSlotBBrcUnexpectedL2AlarmReset, tModuleBroSlotBBrcUnexpectedSFActivated, tModuleBroSlotBBrcUnexpectedSFDisappeared, tModuleBroSlotBBrcUnexpectedSFAlarmReset,
|
tEMBroABrcAMessageLostL1Activated, tEMBroABrcAMessageLostL1Disappeared, tEMBroABrcAMessageLostL1AlarmReset, tEMBroABrcAMessageLostL2Activated, tEMBroABrcAMessageLostL2Disappeared,
|
tEMBroABrcAMessageLostL2AlarmReset, tEMBroABrcAMessageLostSFActivated, tEMBroABrcAMessageLostSFDisappeared, tEMBroABrcAMessageLostSFAlarmReset, tEMBroBBrcAMessageLostL1Activated,
|
tEMBroBBrcAMessageLostL1Disappeared, tEMBroBBrcAMessageLostL1AlarmReset, tEMBroBBrcAMessageLostL2Activated, tEMBroBBrcAMessageLostL2Disappeared, tEMBroBBrcAMessageLostL2AlarmReset,
|
tEMBroBBrcAMessageLostSFActivated, tEMBroBBrcAMessageLostSFDisappeared, tEMBroBBrcAMessageLostSFAlarmReset, tEMBroABrcConfigurationMistakeL1Activated, tEMBroABrcConfigurationMistakeL1Disappeared,
|
tEMBroABrcConfigurationMistakeL1AlarmReset, tEMBroABrcConfigurationMistakeL2Activated, tEMBroABrcConfigurationMistakeL2Disappeared, tEMBroABrcConfigurationMistakeL2AlarmReset, tEMBroABrcConfigurationMistakeSFActivated,
|
tEMBroABrcConfigurationMistakeSFDisappeared, tEMBroABrcConfigurationMistakeSFAlarmReset, tEMBroBBrcConfigurationMistakeL1Activated, tEMBroBBrcConfigurationMistakeL1Disappeared, tEMBroBBrcConfigurationMistakeL1AlarmReset,
|
tEMBroBBrcConfigurationMistakeL2Activated, tEMBroBBrcConfigurationMistakeL2Disappeared, tEMBroBBrcConfigurationMistakeL2AlarmReset, tEMBroBBrcConfigurationMistakeSFActivated, tEMBroBBrcConfigurationMistakeSFDisappeared,
|
tEMBroBBrcConfigurationMistakeSFAlarmReset, tEMBroABrcInsufficientL1Activated, tEMBroABrcInsufficientL1Disappeared, tEMBroABrcInsufficientL1AlarmReset, tEMBroABrcInsufficientL2Activated,
|
tEMBroABrcInsufficientL2Disappeared, tEMBroABrcInsufficientL2AlarmReset, tEMBroABrcInsufficientSFActivated, tEMBroABrcInsufficientSFDisappeared, tEMBroABrcInsufficientSFAlarmReset,
|
tEMBroBBrcInsufficientL1Activated, tEMBroBBrcInsufficientL1Disappeared, tEMBroBBrcInsufficientL1AlarmReset, tEMBroBBrcInsufficientL2Activated, tEMBroBBrcInsufficientL2Disappeared,
|
tEMBroBBrcInsufficientL2AlarmReset, tEMBroBBrcInsufficientSFActivated, tEMBroBBrcInsufficientSFDisappeared, tEMBroBBrcInsufficientSFAlarmReset, tEMBroABrcMissingOrDamagedL1Activated,
|
tEMBroABrcMissingOrDamagedL1Disappeared, tEMBroABrcMissingOrDamagedL1AlarmReset, tEMBroABrcMissingOrDamagedL2Activated, tEMBroABrcMissingOrDamagedL2Disappeared, tEMBroABrcMissingOrDamagedL2AlarmReset,
|
tEMBroABrcMissingOrDamagedSFActivated, tEMBroABrcMissingOrDamagedSFDisappeared, tEMBroABrcMissingOrDamagedSFAlarmReset, tEMBroBBrcMissingOrDamagedL1Activated, tEMBroBBrcMissingOrDamagedL1Disappeared,
|
tEMBroBBrcMissingOrDamagedL1AlarmReset, tEMBroBBrcMissingOrDamagedL2Activated, tEMBroBBrcMissingOrDamagedL2Disappeared, tEMBroBBrcMissingOrDamagedL2AlarmReset, tEMBroBBrcMissingOrDamagedSFActivated,
|
tEMBroBBrcMissingOrDamagedSFDisappeared, tEMBroBBrcMissingOrDamagedSFAlarmReset, tEventEMail1FailL1Activated, tEventEMail1FailL1Disappeared, tEventEMail1FailL1AlarmReset,
|
tEventEMail1FailL2Activated, tEventEMail1FailL2Disappeared, tEventEMail1FailL2AlarmReset, tEventEMail1FailSFActivated, tEventEMail1FailSFDisappeared,
|
tEventEMail1FailSFAlarmReset, tEventEMail2FailL1Activated, tEventEMail2FailL1Disappeared, tEventEMail2FailL1AlarmReset, tEventEMail2FailL2Activated,
|
tEventEMail2FailL2Disappeared, tEventEMail2FailL2AlarmReset, tEventEMail2FailSFActivated, tEventEMail2FailSFDisappeared, tEventEMail2FailSFAlarmReset,
|
tEventEMail3FailL1Activated, tEventEMail3FailL1Disappeared, tEventEMail3FailL1AlarmReset, tEventEMail3FailL2Activated, tEventEMail3FailL2Disappeared,
|
tEventEMail3FailL2AlarmReset, tEventEMail3FailSFActivated, tEventEMail3FailSFDisappeared, tEventEMail3FailSFAlarmReset, tEventEMail4FailL1Activated,
|
tEventEMail4FailL1Disappeared, tEventEMail4FailL1AlarmReset, tEventEMail4FailL2Activated, tEventEMail4FailL2Disappeared, tEventEMail4FailL2AlarmReset,
|
tEventEMail4FailSFActivated, tEventEMail4FailSFDisappeared, tEventEMail4FailSFAlarmReset, tEventSMS1FailL1Activated, tEventSMS1FailL1Disappeared,
|
tEventSMS1FailL1AlarmReset, tEventSMS1FailL2Activated, tEventSMS1FailL2Disappeared, tEventSMS1FailL2AlarmReset, tEventSMS1FailSFActivated,
|
tEventSMS1FailSFDisappeared, tEventSMS1FailSFAlarmReset, tEventSMS2FailL1Activated, tEventSMS2FailL1Disappeared, tEventSMS2FailL1AlarmReset,
|
tEventSMS2FailL2Activated, tEventSMS2FailL2Disappeared, tEventSMS2FailL2AlarmReset, tEventSMS2FailSFActivated, tEventSMS2FailSFDisappeared,
|
tEventSMS2FailSFAlarmReset, tEventSMS3FailL1Activated, tEventSMS3FailL1Disappeared, tEventSMS3FailL1AlarmReset, tEventSMS3FailL2Activated,
|
tEventSMS3FailL2Disappeared, tEventSMS3FailL2AlarmReset, tEventSMS3FailSFActivated, tEventSMS3FailSFDisappeared, tEventSMS3FailSFAlarmReset,
|
tEventSMS4FailL1Activated, tEventSMS4FailL1Disappeared, tEventSMS4FailL1AlarmReset, tEventSMS4FailL2Activated, tEventSMS4FailL2Disappeared,
|
tEventSMS4FailL2AlarmReset, tEventSMS4FailSFActivated, tEventSMS4FailSFDisappeared, tEventSMS4FailSFAlarmReset, tAlarmEMail1FailL1Activated,
|
tAlarmEMail1FailL1Disappeared, tAlarmEMail1FailL1AlarmReset, tAlarmEMail1FailL2Activated, tAlarmEMail1FailL2Disappeared, tAlarmEMail1FailL2AlarmReset,
|
tAlarmEMail1FailSFActivated, tAlarmEMail1FailSFDisappeared, tAlarmEMail1FailSFAlarmReset, tAlarmEMail2FailL1Activated, tAlarmEMail2FailL1Disappeared,
|
tAlarmEMail2FailL1AlarmReset, tAlarmEMail2FailL2Activated, tAlarmEMail2FailL2Disappeared, tAlarmEMail2FailL2AlarmReset, tAlarmEMail2FailSFActivated,
|
tAlarmEMail2FailSFDisappeared, tAlarmEMail2FailSFAlarmReset, tAlarmEMail3FailL1Activated, tAlarmEMail3FailL1Disappeared, tAlarmEMail3FailL1AlarmReset,
|
tAlarmEMail3FailL2Activated, tAlarmEMail3FailL2Disappeared, tAlarmEMail3FailL2AlarmReset, tAlarmEMail3FailSFActivated, tAlarmEMail3FailSFDisappeared,
|
tAlarmEMail3FailSFAlarmReset, tAlarmEMail4FailL1Activated, tAlarmEMail4FailL1Disappeared, tAlarmEMail4FailL1AlarmReset, tAlarmEMail4FailL2Activated,
|
tAlarmEMail4FailL2Disappeared, tAlarmEMail4FailL2AlarmReset, tAlarmEMail4FailSFActivated, tAlarmEMail4FailSFDisappeared, tAlarmEMail4FailSFAlarmReset,
|
tAlarmSMS1FailL1Activated, tAlarmSMS1FailL1Disappeared, tAlarmSMS1FailL1AlarmReset, tAlarmSMS1FailL2Activated, tAlarmSMS1FailL2Disappeared,
|
tAlarmSMS1FailL2AlarmReset, tAlarmSMS1FailSFActivated, tAlarmSMS1FailSFDisappeared, tAlarmSMS1FailSFAlarmReset, tAlarmSMS2FailL1Activated,
|
tAlarmSMS2FailL1Disappeared, tAlarmSMS2FailL1AlarmReset, tAlarmSMS2FailL2Activated, tAlarmSMS2FailL2Disappeared, tAlarmSMS2FailL2AlarmReset,
|
tAlarmSMS2FailSFActivated, tAlarmSMS2FailSFDisappeared, tAlarmSMS2FailSFAlarmReset, tAlarmSMS3FailL1Activated, tAlarmSMS3FailL1Disappeared,
|
tAlarmSMS3FailL1AlarmReset, tAlarmSMS3FailL2Activated, tAlarmSMS3FailL2Disappeared, tAlarmSMS3FailL2AlarmReset, tAlarmSMS3FailSFActivated,
|
tAlarmSMS3FailSFDisappeared, tAlarmSMS3FailSFAlarmReset, tAlarmSMS4FailL1Activated, tAlarmSMS4FailL1Disappeared, tAlarmSMS4FailL1AlarmReset,
|
tAlarmSMS4FailL2Activated, tAlarmSMS4FailL2Disappeared, tAlarmSMS4FailL2AlarmReset, tAlarmSMS4FailSFActivated, tAlarmSMS4FailSFDisappeared,
|
tAlarmSMS4FailSFAlarmReset, tSNMPTRAP1FailL1Activated, tSNMPTRAP1FailL1Disappeared, tSNMPTRAP1FailL1AlarmReset, tSNMPTRAP1FailL2Activated,
|
tSNMPTRAP1FailL2Disappeared, tSNMPTRAP1FailL2AlarmReset, tSNMPTRAP1FailSFActivated, tSNMPTRAP1FailSFDisappeared, tSNMPTRAP1FailSFAlarmReset,
|
tSNMPTRAP2FailL1Activated, tSNMPTRAP2FailL1Disappeared, tSNMPTRAP2FailL1AlarmReset, tSNMPTRAP2FailL2Activated, tSNMPTRAP2FailL2Disappeared,
|
tSNMPTRAP2FailL2AlarmReset, tSNMPTRAP2FailSFActivated, tSNMPTRAP2FailSFDisappeared, tSNMPTRAP2FailSFAlarmReset, tECUYellowLampL1Activated,
|
tECUYellowLampL1Disappeared, tECUYellowLampL1AlarmReset, tECUYellowLampL2Activated, tECUYellowLampL2Disappeared, tECUYellowLampL2AlarmReset,
|
tECUYellowLampSFActivated, tECUYellowLampSFDisappeared, tECUYellowLampSFAlarmReset, tECURedLampL1Activated, tECURedLampL1Disappeared,
|
tECURedLampL1AlarmReset, tECURedLampL2Activated, tECURedLampL2Disappeared, tECURedLampL2AlarmReset, tECURedLampSFActivated,
|
tECURedLampSFDisappeared, tECURedLampSFAlarmReset, tECUWaitToStartL1Activated, tECUWaitToStartL1Disappeared, tECUWaitToStartL1AlarmReset,
|
tECUWaitToStartL2Activated, tECUWaitToStartL2Disappeared, tECUWaitToStartL2AlarmReset, tECUWaitToStartSFActivated, tECUWaitToStartSFDisappeared,
|
tECUWaitToStartSFAlarmReset, tECUStateDash3L1Activated, tECUStateDash3L1Disappeared, tECUStateDash3L1AlarmReset, tECUStateDash3L2Activated,
|
tECUStateDash3L2Disappeared, tECUStateDash3L2AlarmReset, tECUStateDash3SFActivated, tECUStateDash3SFDisappeared, tECUStateDash3SFAlarmReset,
|
tECUStateDash4L1Activated, tECUStateDash4L1Disappeared, tECUStateDash4L1AlarmReset, tECUStateDash4L2Activated, tECUStateDash4L2Disappeared,
|
tECUStateDash4L2AlarmReset, tECUStateDash4SFActivated, tECUStateDash4SFDisappeared, tECUStateDash4SFAlarmReset, tECUStateDash5L1Activated,
|
tECUStateDash5L1Disappeared, tECUStateDash5L1AlarmReset, tECUStateDash5L2Activated, tECUStateDash5L2Disappeared, tECUStateDash5L2AlarmReset,
|
tECUStateDash5SFActivated, tECUStateDash5SFDisappeared, tECUStateDash5SFAlarmReset, tECUStateDash6L1Activated, tECUStateDash6L1Disappeared,
|
tECUStateDash6L1AlarmReset, tECUStateDash6L2Activated, tECUStateDash6L2Disappeared, tECUStateDash6L2AlarmReset, tECUStateDash6SFActivated,
|
tECUStateDash6SFDisappeared, tECUStateDash6SFAlarmReset, tECUStateDash7L1Activated, tECUStateDash7L1Disappeared, tECUStateDash7L1AlarmReset,
|
tECUStateDash7L2Activated, tECUStateDash7L2Disappeared, tECUStateDash7L2AlarmReset, tECUStateDash7SFActivated, tECUStateDash7SFDisappeared,
|
tECUStateDash7SFAlarmReset, tAfterTreatmentL1Activated, tAfterTreatmentL1Disappeared, tAfterTreatmentL1AlarmReset, tAfterTreatmentL2Activated,
|
tAfterTreatmentL2Disappeared, tAfterTreatmentL2AlarmReset, tAfterTreatmentSFActivated, tAfterTreatmentSFDisappeared, tAfterTreatmentSFAlarmReset,
|
tEmergencyStopL1Activated2, tEmergencyStopL1Disappeared2, tEmergencyStopL1AlarmReset2, tEmergencyStopL2Activated2, tEmergencyStopL2Disappeared2,
|
tEmergencyStopL2AlarmReset2, tEmergencyStopSFActivated2, tEmergencyStopSFDisappeared2, tEmergencyStopSFAlarmReset2, tRPML1Activated,
|
tRPML1Disappeared, tRPML1AlarmReset, tRPML2Activated, tRPML2Disappeared, tRPML2AlarmReset,
|
tRPMSFActivated, tRPMSFDisappeared, tRPMSFAlarmReset, tWrnChargingAlternatorFailL1Activated, tWrnChargingAlternatorFailL1Disappeared,
|
tWrnChargingAlternatorFailL1AlarmReset, tWrnChargingAlternatorFailL2Activated, tWrnChargingAlternatorFailL2Disappeared, tWrnChargingAlternatorFailL2AlarmReset, tWrnChargingAlternatorFailSFActivated,
|
tWrnChargingAlternatorFailSFDisappeared, tWrnChargingAlternatorFailSFAlarmReset, tWrnStopFailL1Activated, tWrnStopFailL1Disappeared, tWrnStopFailL1AlarmReset,
|
tWrnStopFailL2Activated, tWrnStopFailL2Disappeared, tWrnStopFailL2AlarmReset, tWrnStopFailSFActivated, tWrnStopFailSFDisappeared,
|
tWrnStopFailSFAlarmReset, tSdOverspeedL1Activated, tSdOverspeedL1Disappeared, tSdOverspeedL1AlarmReset, tSdOverspeedL2Activated,
|
tSdOverspeedL2Disappeared, tSdOverspeedL2AlarmReset, tSdOverspeedSFActivated, tSdOverspeedSFDisappeared, tSdOverspeedSFAlarmReset,
|
tSdUnderspeedL1Activated, tSdUnderspeedL1Disappeared, tSdUnderspeedL1AlarmReset, tSdUnderspeedL2Activated, tSdUnderspeedL2Disappeared,
|
tSdUnderspeedL2AlarmReset, tSdUnderspeedSFActivated, tSdUnderspeedSFDisappeared, tSdUnderspeedSFAlarmReset, tSdRPMMeasurementFailL1Activated,
|
tSdRPMMeasurementFailL1Disappeared, tSdRPMMeasurementFailL1AlarmReset, tSdRPMMeasurementFailL2Activated, tSdRPMMeasurementFailL2Disappeared, tSdRPMMeasurementFailL2AlarmReset,
|
tSdRPMMeasurementFailSFActivated, tSdRPMMeasurementFailSFDisappeared, tSdRPMMeasurementFailSFAlarmReset, tSdBatteryFlatL1Activated, tSdBatteryFlatL1Disappeared,
|
tSdBatteryFlatL1AlarmReset, tSdBatteryFlatL2Activated, tSdBatteryFlatL2Disappeared, tSdBatteryFlatL2AlarmReset, tSdBatteryFlatSFActivated,
|
tSdBatteryFlatSFDisappeared, tSdBatteryFlatSFAlarmReset, tWrnMaintenance1L1Activated, tWrnMaintenance1L1Disappeared, tWrnMaintenance1L1AlarmReset,
|
tWrnMaintenance1L2Activated, tWrnMaintenance1L2Disappeared, tWrnMaintenance1L2AlarmReset, tWrnMaintenance1SFActivated, tWrnMaintenance1SFDisappeared,
|
tWrnMaintenance1SFAlarmReset, tWrnMaintenance2L1Activated, tWrnMaintenance2L1Disappeared, tWrnMaintenance2L1AlarmReset, tWrnMaintenance2L2Activated,
|
tWrnMaintenance2L2Disappeared, tWrnMaintenance2L2AlarmReset, tWrnMaintenance2SFActivated, tWrnMaintenance2SFDisappeared, tWrnMaintenance2SFAlarmReset,
|
tWrnMaintenance3L1Activated, tWrnMaintenance3L1Disappeared, tWrnMaintenance3L1AlarmReset, tWrnMaintenance3L2Activated, tWrnMaintenance3L2Disappeared,
|
tWrnMaintenance3L2AlarmReset, tWrnMaintenance3SFActivated, tWrnMaintenance3SFDisappeared, tWrnMaintenance3SFAlarmReset, tSdStartFailL1Activated,
|
tSdStartFailL1Disappeared, tSdStartFailL1AlarmReset, tSdStartFailL2Activated, tSdStartFailL2Disappeared, tSdStartFailL2AlarmReset,
|
tSdStartFailSFActivated, tSdStartFailSFDisappeared, tSdStartFailSFAlarmReset, tWrnMCBFailL1Activated, tWrnMCBFailL1Disappeared,
|
tWrnMCBFailL1AlarmReset, tWrnMCBFailL2Activated, tWrnMCBFailL2Disappeared, tWrnMCBFailL2AlarmReset, tWrnMCBFailSFActivated,
|
tWrnMCBFailSFDisappeared, tWrnMCBFailSFAlarmReset, tSdGCBFailL1Activated, tSdGCBFailL1Disappeared, tSdGCBFailL1AlarmReset,
|
tSdGCBFailL2Activated, tSdGCBFailL2Disappeared, tSdGCBFailL2AlarmReset, tSdGCBFailSFActivated, tSdGCBFailSFDisappeared,
|
tSdGCBFailSFAlarmReset, tGeneratorVoltageL1NL1Activated, tGeneratorVoltageL1NL1Disappeared, tGeneratorVoltageL1NL1AlarmReset, tGeneratorVoltageL1NL2Activated,
|
tGeneratorVoltageL1NL2Disappeared, tGeneratorVoltageL1NL2AlarmReset, tGeneratorVoltageL1NSFActivated, tGeneratorVoltageL1NSFDisappeared, tGeneratorVoltageL1NSFAlarmReset,
|
tGeneratorVoltageL2NL1Activated, tGeneratorVoltageL2NL1Disappeared, tGeneratorVoltageL2NL1AlarmReset, tGeneratorVoltageL2NL2Activated, tGeneratorVoltageL2NL2Disappeared,
|
tGeneratorVoltageL2NL2AlarmReset, tGeneratorVoltageL2NSFActivated, tGeneratorVoltageL2NSFDisappeared, tGeneratorVoltageL2NSFAlarmReset, tGeneratorVoltageL3NL1Activated,
|
tGeneratorVoltageL3NL1Disappeared, tGeneratorVoltageL3NL1AlarmReset, tGeneratorVoltageL3NL2Activated, tGeneratorVoltageL3NL2Disappeared, tGeneratorVoltageL3NL2AlarmReset,
|
tGeneratorVoltageL3NSFActivated, tGeneratorVoltageL3NSFDisappeared, tGeneratorVoltageL3NSFAlarmReset, tGeneratorVoltageL1L2L1Activated, tGeneratorVoltageL1L2L1Disappeared,
|
tGeneratorVoltageL1L2L1AlarmReset, tGeneratorVoltageL1L2L2Activated, tGeneratorVoltageL1L2L2Disappeared, tGeneratorVoltageL1L2L2AlarmReset, tGeneratorVoltageL1L2SFActivated,
|
tGeneratorVoltageL1L2SFDisappeared, tGeneratorVoltageL1L2SFAlarmReset, tGeneratorVoltageL2L3L1Activated, tGeneratorVoltageL2L3L1Disappeared, tGeneratorVoltageL2L3L1AlarmReset,
|
tGeneratorVoltageL2L3L2Activated, tGeneratorVoltageL2L3L2Disappeared, tGeneratorVoltageL2L3L2AlarmReset, tGeneratorVoltageL2L3SFActivated, tGeneratorVoltageL2L3SFDisappeared,
|
tGeneratorVoltageL2L3SFAlarmReset, tGeneratorVoltageL3L1L1Activated, tGeneratorVoltageL3L1L1Disappeared, tGeneratorVoltageL3L1L1AlarmReset, tGeneratorVoltageL3L1L2Activated,
|
tGeneratorVoltageL3L1L2Disappeared, tGeneratorVoltageL3L1L2AlarmReset, tGeneratorVoltageL3L1SFActivated, tGeneratorVoltageL3L1SFDisappeared, tGeneratorVoltageL3L1SFAlarmReset,
|
tBOCGenVoltageUnbalancePhPhL1Activated, tBOCGenVoltageUnbalancePhPhL1Disappeared, tBOCGenVoltageUnbalancePhPhL1AlarmReset, tBOCGenVoltageUnbalancePhPhL2Activated, tBOCGenVoltageUnbalancePhPhL2Disappeared,
|
tBOCGenVoltageUnbalancePhPhL2AlarmReset, tBOCGenVoltageUnbalancePhPhSFActivated, tBOCGenVoltageUnbalancePhPhSFDisappeared, tBOCGenVoltageUnbalancePhPhSFAlarmReset, tBOCGenVoltageUnbalancePhNL1Activated,
|
tBOCGenVoltageUnbalancePhNL1Disappeared, tBOCGenVoltageUnbalancePhNL1AlarmReset, tBOCGenVoltageUnbalancePhNL2Activated, tBOCGenVoltageUnbalancePhNL2Disappeared, tBOCGenVoltageUnbalancePhNL2AlarmReset,
|
tBOCGenVoltageUnbalancePhNSFActivated, tBOCGenVoltageUnbalancePhNSFDisappeared, tBOCGenVoltageUnbalancePhNSFAlarmReset, tGeneratorFrequencyL1Activated, tGeneratorFrequencyL1Disappeared,
|
tGeneratorFrequencyL1AlarmReset, tGeneratorFrequencyL2Activated, tGeneratorFrequencyL2Disappeared, tGeneratorFrequencyL2AlarmReset, tGeneratorFrequencySFActivated,
|
tGeneratorFrequencySFDisappeared, tGeneratorFrequencySFAlarmReset, tMainsVoltageL1NL1Activated, tMainsVoltageL1NL1Disappeared, tMainsVoltageL1NL1AlarmReset,
|
tMainsVoltageL1NL2Activated, tMainsVoltageL1NL2Disappeared, tMainsVoltageL1NL2AlarmReset, tMainsVoltageL1NSFActivated, tMainsVoltageL1NSFDisappeared,
|
tMainsVoltageL1NSFAlarmReset, tMainsVoltageL2NL1Activated, tMainsVoltageL2NL1Disappeared, tMainsVoltageL2NL1AlarmReset, tMainsVoltageL2NL2Activated,
|
tMainsVoltageL2NL2Disappeared, tMainsVoltageL2NL2AlarmReset, tMainsVoltageL2NSFActivated, tMainsVoltageL2NSFDisappeared, tMainsVoltageL2NSFAlarmReset,
|
tMainsVoltageL3NL1Activated, tMainsVoltageL3NL1Disappeared, tMainsVoltageL3NL1AlarmReset, tMainsVoltageL3NL2Activated, tMainsVoltageL3NL2Disappeared,
|
tMainsVoltageL3NL2AlarmReset, tMainsVoltageL3NSFActivated, tMainsVoltageL3NSFDisappeared, tMainsVoltageL3NSFAlarmReset, tMainsVoltageL1L2L1Activated,
|
tMainsVoltageL1L2L1Disappeared, tMainsVoltageL1L2L1AlarmReset, tMainsVoltageL1L2L2Activated, tMainsVoltageL1L2L2Disappeared, tMainsVoltageL1L2L2AlarmReset,
|
tMainsVoltageL1L2SFActivated, tMainsVoltageL1L2SFDisappeared, tMainsVoltageL1L2SFAlarmReset, tMainsVoltageL2L3L1Activated, tMainsVoltageL2L3L1Disappeared,
|
tMainsVoltageL2L3L1AlarmReset, tMainsVoltageL2L3L2Activated, tMainsVoltageL2L3L2Disappeared, tMainsVoltageL2L3L2AlarmReset, tMainsVoltageL2L3SFActivated,
|
tMainsVoltageL2L3SFDisappeared, tMainsVoltageL2L3SFAlarmReset, tMainsVoltageL3L1L1Activated, tMainsVoltageL3L1L1Disappeared, tMainsVoltageL3L1L1AlarmReset,
|
tMainsVoltageL3L1L2Activated, tMainsVoltageL3L1L2Disappeared, tMainsVoltageL3L1L2AlarmReset, tMainsVoltageL3L1SFActivated, tMainsVoltageL3L1SFDisappeared,
|
tMainsVoltageL3L1SFAlarmReset, tMainsFrequencyL1Activated, tMainsFrequencyL1Disappeared, tMainsFrequencyL1AlarmReset, tMainsFrequencyL2Activated,
|
tMainsFrequencyL2Disappeared, tMainsFrequencyL2AlarmReset, tMainsFrequencySFActivated, tMainsFrequencySFDisappeared, tMainsFrequencySFAlarmReset,
|
tMainsL1GtVL1Activated, tMainsL1GtVL1Disappeared, tMainsL1GtVL1AlarmReset, tMainsL1GtVL2Activated, tMainsL1GtVL2Disappeared,
|
tMainsL1GtVL2AlarmReset, tMainsL1GtVSFActivated, tMainsL1GtVSFDisappeared, tMainsL1GtVSFAlarmReset, tMainsL1LtVL1Activated,
|
tMainsL1LtVL1Disappeared, tMainsL1LtVL1AlarmReset, tMainsL1LtVL2Activated, tMainsL1LtVL2Disappeared, tMainsL1LtVL2AlarmReset,
|
tMainsL1LtVSFActivated, tMainsL1LtVSFDisappeared, tMainsL1LtVSFAlarmReset, tMainsL2GtVL1Activated, tMainsL2GtVL1Disappeared,
|
tMainsL2GtVL1AlarmReset, tMainsL2GtVL2Activated, tMainsL2GtVL2Disappeared, tMainsL2GtVL2AlarmReset, tMainsL2GtVSFActivated,
|
tMainsL2GtVSFDisappeared, tMainsL2GtVSFAlarmReset, tMainsL2LtVL1Activated, tMainsL2LtVL1Disappeared, tMainsL2LtVL1AlarmReset,
|
tMainsL2LtVL2Activated, tMainsL2LtVL2Disappeared, tMainsL2LtVL2AlarmReset, tMainsL2LtVSFActivated, tMainsL2LtVSFDisappeared,
|
tMainsL2LtVSFAlarmReset, tMainsL3GtVL1Activated, tMainsL3GtVL1Disappeared, tMainsL3GtVL1AlarmReset, tMainsL3GtVL2Activated,
|
tMainsL3GtVL2Disappeared, tMainsL3GtVL2AlarmReset, tMainsL3GtVSFActivated, tMainsL3GtVSFDisappeared, tMainsL3GtVSFAlarmReset,
|
tMainsL3LtVL1Activated, tMainsL3LtVL1Disappeared, tMainsL3LtVL1AlarmReset, tMainsL3LtVL2Activated, tMainsL3LtVL2Disappeared,
|
tMainsL3LtVL2AlarmReset, tMainsL3LtVSFActivated, tMainsL3LtVSFDisappeared, tMainsL3LtVSFAlarmReset, tMainsL12GtVL1Activated,
|
tMainsL12GtVL1Disappeared, tMainsL12GtVL1AlarmReset, tMainsL12GtVL2Activated, tMainsL12GtVL2Disappeared, tMainsL12GtVL2AlarmReset,
|
tMainsL12GtVSFActivated, tMainsL12GtVSFDisappeared, tMainsL12GtVSFAlarmReset, tMainsL12LtVL1Activated, tMainsL12LtVL1Disappeared,
|
tMainsL12LtVL1AlarmReset, tMainsL12LtVL2Activated, tMainsL12LtVL2Disappeared, tMainsL12LtVL2AlarmReset, tMainsL12LtVSFActivated,
|
tMainsL12LtVSFDisappeared, tMainsL12LtVSFAlarmReset, tMainsL23GtVL1Activated, tMainsL23GtVL1Disappeared, tMainsL23GtVL1AlarmReset,
|
tMainsL23GtVL2Activated, tMainsL23GtVL2Disappeared, tMainsL23GtVL2AlarmReset, tMainsL23GtVSFActivated, tMainsL23GtVSFDisappeared,
|
tMainsL23GtVSFAlarmReset, tMainsL23LtVL1Activated, tMainsL23LtVL1Disappeared, tMainsL23LtVL1AlarmReset, tMainsL23LtVL2Activated,
|
tMainsL23LtVL2Disappeared, tMainsL23LtVL2AlarmReset, tMainsL23LtVSFActivated, tMainsL23LtVSFDisappeared, tMainsL23LtVSFAlarmReset,
|
tMainsL31GtVL1Activated, tMainsL31GtVL1Disappeared, tMainsL31GtVL1AlarmReset, tMainsL31GtVL2Activated, tMainsL31GtVL2Disappeared,
|
tMainsL31GtVL2AlarmReset, tMainsL31GtVSFActivated, tMainsL31GtVSFDisappeared, tMainsL31GtVSFAlarmReset, tMainsL31LtVL1Activated,
|
tMainsL31LtVL1Disappeared, tMainsL31LtVL1AlarmReset, tMainsL31LtVL2Activated, tMainsL31LtVL2Disappeared, tMainsL31LtVL2AlarmReset,
|
tMainsL31LtVSFActivated, tMainsL31LtVSFDisappeared, tMainsL31LtVSFAlarmReset, tMainsVoltageUnbalancePhPhL1Activated, tMainsVoltageUnbalancePhPhL1Disappeared,
|
tMainsVoltageUnbalancePhPhL1AlarmReset, tMainsVoltageUnbalancePhPhL2Activated, tMainsVoltageUnbalancePhPhL2Disappeared, tMainsVoltageUnbalancePhPhL2AlarmReset, tMainsVoltageUnbalancePhPhSFActivated,
|
tMainsVoltageUnbalancePhPhSFDisappeared, tMainsVoltageUnbalancePhPhSFAlarmReset, tMainsVoltageUnbalancePhNL1Activated, tMainsVoltageUnbalancePhNL1Disappeared, tMainsVoltageUnbalancePhNL1AlarmReset,
|
tMainsVoltageUnbalancePhNL2Activated, tMainsVoltageUnbalancePhNL2Disappeared, tMainsVoltageUnbalancePhNL2AlarmReset, tMainsVoltageUnbalancePhNSFActivated, tMainsVoltageUnbalancePhNSFDisappeared,
|
tMainsVoltageUnbalancePhNSFAlarmReset, tMainsGtFrequencyL1Activated, tMainsGtFrequencyL1Disappeared, tMainsGtFrequencyL1AlarmReset, tMainsGtFrequencyL2Activated,
|
tMainsGtFrequencyL2Disappeared, tMainsGtFrequencyL2AlarmReset, tMainsGtFrequencySFActivated, tMainsGtFrequencySFDisappeared, tMainsGtFrequencySFAlarmReset,
|
tMainsLtFrequencyL1Activated, tMainsLtFrequencyL1Disappeared, tMainsLtFrequencyL1AlarmReset, tMainsLtFrequencyL2Activated, tMainsLtFrequencyL2Disappeared,
|
tMainsLtFrequencyL2AlarmReset, tMainsLtFrequencySFActivated, tMainsLtFrequencySFDisappeared, tMainsLtFrequencySFAlarmReset, tGeneratorCCWRotationL1Activated,
|
tGeneratorCCWRotationL1Disappeared, tGeneratorCCWRotationL1AlarmReset, tGeneratorCCWRotationL2Activated, tGeneratorCCWRotationL2Disappeared, tGeneratorCCWRotationL2AlarmReset,
|
tGeneratorCCWRotationSFActivated, tGeneratorCCWRotationSFDisappeared, tGeneratorCCWRotationSFAlarmReset, tMainsCCWRotationL1Activated, tMainsCCWRotationL1Disappeared,
|
tMainsCCWRotationL1AlarmReset, tMainsCCWRotationL2Activated, tMainsCCWRotationL2Disappeared, tMainsCCWRotationL2AlarmReset, tMainsCCWRotationSFActivated,
|
tMainsCCWRotationSFDisappeared, tMainsCCWRotationSFAlarmReset, tSdEarthFaultCurrentL1Activated, tSdEarthFaultCurrentL1Disappeared, tSdEarthFaultCurrentL1AlarmReset,
|
tSdEarthFaultCurrentL2Activated, tSdEarthFaultCurrentL2Disappeared, tSdEarthFaultCurrentL2AlarmReset, tSdEarthFaultCurrentSFActivated, tSdEarthFaultCurrentSFDisappeared,
|
tSdEarthFaultCurrentSFAlarmReset, tBOCOvercurrentIDMTL1Activated, tBOCOvercurrentIDMTL1Disappeared, tBOCOvercurrentIDMTL1AlarmReset, tBOCOvercurrentIDMTL2Activated,
|
tBOCOvercurrentIDMTL2Disappeared, tBOCOvercurrentIDMTL2AlarmReset, tBOCOvercurrentIDMTSFActivated, tBOCOvercurrentIDMTSFDisappeared, tBOCOvercurrentIDMTSFAlarmReset,
|
tGenGtIeBroIDMTBrcL1Activated, tGenGtIeBroIDMTBrcL1Disappeared, tGenGtIeBroIDMTBrcL1AlarmReset, tGenGtIeBroIDMTBrcL2Activated, tGenGtIeBroIDMTBrcL2Disappeared,
|
tGenGtIeBroIDMTBrcL2AlarmReset, tGenGtIeBroIDMTBrcSFActivated, tGenGtIeBroIDMTBrcSFDisappeared, tGenGtIeBroIDMTBrcSFAlarmReset, tTransferringFuelL1Activated,
|
tTransferringFuelL1Disappeared, tTransferringFuelL1AlarmReset, tTransferringFuelL2Activated, tTransferringFuelL2Disappeared, tTransferringFuelL2AlarmReset,
|
tTransferringFuelSFActivated, tTransferringFuelSFDisappeared, tTransferringFuelSFAlarmReset, tFuelTransferFailedL1Activated, tFuelTransferFailedL1Disappeared,
|
tFuelTransferFailedL1AlarmReset, tFuelTransferFailedL2Activated, tFuelTransferFailedL2Disappeared, tFuelTransferFailedL2AlarmReset, tFuelTransferFailedSFActivated,
|
tFuelTransferFailedSFDisappeared, tFuelTransferFailedSFAlarmReset, tWrnBatteryUndervoltageL1Activated, tWrnBatteryUndervoltageL1Disappeared, tWrnBatteryUndervoltageL1AlarmReset,
|
tWrnBatteryUndervoltageL2Activated, tWrnBatteryUndervoltageL2Disappeared, tWrnBatteryUndervoltageL2AlarmReset, tWrnBatteryUndervoltageSFActivated, tWrnBatteryUndervoltageSFDisappeared,
|
tWrnBatteryUndervoltageSFAlarmReset, tWrnBatteryOvervoltageL1Activated, tWrnBatteryOvervoltageL1Disappeared, tWrnBatteryOvervoltageL1AlarmReset, tWrnBatteryOvervoltageL2Activated,
|
tWrnBatteryOvervoltageL2Disappeared, tWrnBatteryOvervoltageL2AlarmReset, tWrnBatteryOvervoltageSFActivated, tWrnBatteryOvervoltageSFDisappeared, tWrnBatteryOvervoltageSFAlarmReset,
|
tBatteryVoltageL1Activated, tBatteryVoltageL1Disappeared, tBatteryVoltageL1AlarmReset, tBatteryVoltageL2Activated, tBatteryVoltageL2Disappeared,
|
tBatteryVoltageL2AlarmReset, tBatteryVoltageSFActivated, tBatteryVoltageSFDisappeared, tBatteryVoltageSFAlarmReset, tWrnCoolantTemperatureLowL1Activated,
|
tWrnCoolantTemperatureLowL1Disappeared, tWrnCoolantTemperatureLowL1AlarmReset, tWrnCoolantTemperatureLowL2Activated, tWrnCoolantTemperatureLowL2Disappeared, tWrnCoolantTemperatureLowL2AlarmReset,
|
tWrnCoolantTemperatureLowSFActivated, tWrnCoolantTemperatureLowSFDisappeared, tWrnCoolantTemperatureLowSFAlarmReset, tBatteryChargeFailL1Activated, tBatteryChargeFailL1Disappeared,
|
tBatteryChargeFailL1AlarmReset, tBatteryChargeFailL2Activated, tBatteryChargeFailL2Disappeared, tBatteryChargeFailL2AlarmReset, tBatteryChargeFailSFActivated,
|
tBatteryChargeFailSFDisappeared, tBatteryChargeFailSFAlarmReset, tWrnOverrideAllSdL1Activated, tWrnOverrideAllSdL1Disappeared, tWrnOverrideAllSdL1AlarmReset,
|
tWrnOverrideAllSdL2Activated, tWrnOverrideAllSdL2Disappeared, tWrnOverrideAllSdL2AlarmReset, tWrnOverrideAllSdSFActivated, tWrnOverrideAllSdSFDisappeared,
|
tWrnOverrideAllSdSFAlarmReset, tWrnRentalTimer1L1Activated, tWrnRentalTimer1L1Disappeared, tWrnRentalTimer1L1AlarmReset, tWrnRentalTimer1L2Activated,
|
tWrnRentalTimer1L2Disappeared, tWrnRentalTimer1L2AlarmReset, tWrnRentalTimer1SFActivated, tWrnRentalTimer1SFDisappeared, tWrnRentalTimer1SFAlarmReset,
|
tWrnRentalTimer2L1Activated, tWrnRentalTimer2L1Disappeared, tWrnRentalTimer2L1AlarmReset, tWrnRentalTimer2L2Activated, tWrnRentalTimer2L2Disappeared,
|
tWrnRentalTimer2L2AlarmReset, tWrnRentalTimer2SFActivated, tWrnRentalTimer2SFDisappeared, tWrnRentalTimer2SFAlarmReset, tRentalTimer1ElapsedL1Activated,
|
tRentalTimer1ElapsedL1Disappeared, tRentalTimer1ElapsedL1AlarmReset, tRentalTimer1ElapsedL2Activated, tRentalTimer1ElapsedL2Disappeared, tRentalTimer1ElapsedL2AlarmReset,
|
tRentalTimer1ElapsedSFActivated, tRentalTimer1ElapsedSFDisappeared, tRentalTimer1ElapsedSFAlarmReset, tRentalTimer2ElapsedL1Activated, tRentalTimer2ElapsedL1Disappeared,
|
tRentalTimer2ElapsedL1AlarmReset, tRentalTimer2ElapsedL2Activated, tRentalTimer2ElapsedL2Disappeared, tRentalTimer2ElapsedL2AlarmReset, tRentalTimer2ElapsedSFActivated,
|
tRentalTimer2ElapsedSFDisappeared, tRentalTimer2ElapsedSFAlarmReset, tBOCRentalTimer1ExceededL1Activated, tBOCRentalTimer1ExceededL1Disappeared, tBOCRentalTimer1ExceededL1AlarmReset,
|
tBOCRentalTimer1ExceededL2Activated, tBOCRentalTimer1ExceededL2Disappeared, tBOCRentalTimer1ExceededL2AlarmReset, tBOCRentalTimer1ExceededSFActivated, tBOCRentalTimer1ExceededSFDisappeared,
|
tBOCRentalTimer1ExceededSFAlarmReset, tBOCRentalTimer2ExceededL1Activated, tBOCRentalTimer2ExceededL1Disappeared, tBOCRentalTimer2ExceededL1AlarmReset, tBOCRentalTimer2ExceededL2Activated,
|
tBOCRentalTimer2ExceededL2Disappeared, tBOCRentalTimer2ExceededL2AlarmReset, tBOCRentalTimer2ExceededSFActivated, tBOCRentalTimer2ExceededSFDisappeared, tBOCRentalTimer2ExceededSFAlarmReset,
|
tRentalTimerBlockStartL1Activated, tRentalTimerBlockStartL1Disappeared, tRentalTimerBlockStartL1AlarmReset, tRentalTimerBlockStartL2Activated, tRentalTimerBlockStartL2Disappeared,
|
tRentalTimerBlockStartL2AlarmReset, tRentalTimerBlockStartSFActivated, tRentalTimerBlockStartSFDisappeared, tRentalTimerBlockStartSFAlarmReset, tManualRestoreL1Activated,
|
tManualRestoreL1Disappeared, tManualRestoreL1AlarmReset, tManualRestoreL2Activated, tManualRestoreL2Disappeared, tManualRestoreL2AlarmReset,
|
tManualRestoreSFActivated, tManualRestoreSFDisappeared, tManualRestoreSFAlarmReset, tWrnMainsVoltageDetectedL1Activated, tWrnMainsVoltageDetectedL1Disappeared,
|
tWrnMainsVoltageDetectedL1AlarmReset, tWrnMainsVoltageDetectedL2Activated, tWrnMainsVoltageDetectedL2Disappeared, tWrnMainsVoltageDetectedL2AlarmReset, tWrnMainsVoltageDetectedSFActivated,
|
tWrnMainsVoltageDetectedSFDisappeared, tWrnMainsVoltageDetectedSFAlarmReset, tWrnFuelTheftL1Activated, tWrnFuelTheftL1Disappeared, tWrnFuelTheftL1AlarmReset,
|
tWrnFuelTheftL2Activated, tWrnFuelTheftL2Disappeared, tWrnFuelTheftL2AlarmReset, tWrnFuelTheftSFActivated, tWrnFuelTheftSFDisappeared,
|
tWrnFuelTheftSFAlarmReset, tModuleCHR3ASlot1L1Activated, tModuleCHR3ASlot1L1Disappeared, tModuleCHR3ASlot1L1AlarmReset, tModuleCHR3ASlot1L2Activated,
|
tModuleCHR3ASlot1L2Disappeared, tModuleCHR3ASlot1L2AlarmReset, tModuleCHR3ASlot1SFActivated, tModuleCHR3ASlot1SFDisappeared, tModuleCHR3ASlot1SFAlarmReset,
|
tModuleCHR3ASlot2L1Activated, tModuleCHR3ASlot2L1Disappeared, tModuleCHR3ASlot2L1AlarmReset, tModuleCHR3ASlot2L2Activated, tModuleCHR3ASlot2L2Disappeared,
|
tModuleCHR3ASlot2L2AlarmReset, tModuleCHR3ASlot2SFActivated, tModuleCHR3ASlot2SFDisappeared, tModuleCHR3ASlot2SFAlarmReset, tECUL1Activated,
|
tECUL1Disappeared, tECUL1AlarmReset, tECUL2Activated, tECUL2Disappeared, tECUL2AlarmReset,
|
tECUSFActivated, tECUSFDisappeared, tECUSFAlarmReset, tECUDiagBlockedL1Activated, tECUDiagBlockedL1Disappeared,
|
tECUDiagBlockedL1AlarmReset, tECUDiagBlockedL2Activated, tECUDiagBlockedL2Disappeared, tECUDiagBlockedL2AlarmReset, tECUDiagBlockedSFActivated,
|
tECUDiagBlockedSFDisappeared, tECUDiagBlockedSFAlarmReset, tWrongConfigL1Activated, tWrongConfigL1Disappeared, tWrongConfigL1AlarmReset,
|
tWrongConfigL2Activated, tWrongConfigL2Disappeared, tWrongConfigL2AlarmReset, tWrongConfigSFActivated, tWrongConfigSFDisappeared,
|
tWrongConfigSFAlarmReset, tRTCBatteryFlatL1Activated, tRTCBatteryFlatL1Disappeared, tRTCBatteryFlatL1AlarmReset, tRTCBatteryFlatL2Activated,
|
tRTCBatteryFlatL2Disappeared, tRTCBatteryFlatL2AlarmReset, tRTCBatteryFlatSFActivated, tRTCBatteryFlatSFDisappeared, tRTCBatteryFlatSFAlarmReset,
|
tECUCommunicationFailL1Activated, tECUCommunicationFailL1Disappeared, tECUCommunicationFailL1AlarmReset, tECUCommunicationFailL2Activated, tECUCommunicationFailL2Disappeared,
|
tECUCommunicationFailL2AlarmReset, tECUCommunicationFailSFActivated, tECUCommunicationFailSFDisappeared, tECUCommunicationFailSFAlarmReset, tGeneratorL1GtVoltageL1Activated,
|
tGeneratorL1GtVoltageL1Disappeared, tGeneratorL1GtVoltageL1AlarmReset, tGeneratorL1GtVoltageL2Activated, tGeneratorL1GtVoltageL2Disappeared, tGeneratorL1GtVoltageL2AlarmReset,
|
tGeneratorL1GtVoltageSFActivated, tGeneratorL1GtVoltageSFDisappeared, tGeneratorL1GtVoltageSFAlarmReset, tGeneratorL2GtVoltageL1Activated, tGeneratorL2GtVoltageL1Disappeared,
|
tGeneratorL2GtVoltageL1AlarmReset, tGeneratorL2GtVoltageL2Activated, tGeneratorL2GtVoltageL2Disappeared, tGeneratorL2GtVoltageL2AlarmReset, tGeneratorL2GtVoltageSFActivated,
|
tGeneratorL2GtVoltageSFDisappeared, tGeneratorL2GtVoltageSFAlarmReset, tGeneratorL3GtVoltageL1Activated, tGeneratorL3GtVoltageL1Disappeared, tGeneratorL3GtVoltageL1AlarmReset,
|
tGeneratorL3GtVoltageL2Activated, tGeneratorL3GtVoltageL2Disappeared, tGeneratorL3GtVoltageL2AlarmReset, tGeneratorL3GtVoltageSFActivated, tGeneratorL3GtVoltageSFDisappeared,
|
tGeneratorL3GtVoltageSFAlarmReset, tGeneratorL1L2GtVoltageL1Activated, tGeneratorL1L2GtVoltageL1Disappeared, tGeneratorL1L2GtVoltageL1AlarmReset, tGeneratorL1L2GtVoltageL2Activated,
|
tGeneratorL1L2GtVoltageL2Disappeared, tGeneratorL1L2GtVoltageL2AlarmReset, tGeneratorL1L2GtVoltageSFActivated, tGeneratorL1L2GtVoltageSFDisappeared, tGeneratorL1L2GtVoltageSFAlarmReset,
|
tGeneratorL2L3GtVoltageL1Activated, tGeneratorL2L3GtVoltageL1Disappeared, tGeneratorL2L3GtVoltageL1AlarmReset, tGeneratorL2L3GtVoltageL2Activated, tGeneratorL2L3GtVoltageL2Disappeared,
|
tGeneratorL2L3GtVoltageL2AlarmReset, tGeneratorL2L3GtVoltageSFActivated, tGeneratorL2L3GtVoltageSFDisappeared, tGeneratorL2L3GtVoltageSFAlarmReset, tGeneratorL3L1GtVoltageL1Activated,
|
tGeneratorL3L1GtVoltageL1Disappeared, tGeneratorL3L1GtVoltageL1AlarmReset, tGeneratorL3L1GtVoltageL2Activated, tGeneratorL3L1GtVoltageL2Disappeared, tGeneratorL3L1GtVoltageL2AlarmReset,
|
tGeneratorL3L1GtVoltageSFActivated, tGeneratorL3L1GtVoltageSFDisappeared, tGeneratorL3L1GtVoltageSFAlarmReset, tGeneratorL1LtVoltageL1Activated, tGeneratorL1LtVoltageL1Disappeared,
|
tGeneratorL1LtVoltageL1AlarmReset, tGeneratorL1LtVoltageL2Activated, tGeneratorL1LtVoltageL2Disappeared, tGeneratorL1LtVoltageL2AlarmReset, tGeneratorL1LtVoltageSFActivated,
|
tGeneratorL1LtVoltageSFDisappeared, tGeneratorL1LtVoltageSFAlarmReset, tGeneratorL2LtVoltageL1Activated, tGeneratorL2LtVoltageL1Disappeared, tGeneratorL2LtVoltageL1AlarmReset,
|
tGeneratorL2LtVoltageL2Activated, tGeneratorL2LtVoltageL2Disappeared, tGeneratorL2LtVoltageL2AlarmReset, tGeneratorL2LtVoltageSFActivated, tGeneratorL2LtVoltageSFDisappeared,
|
tGeneratorL2LtVoltageSFAlarmReset, tGeneratorL3LtVoltageL1Activated, tGeneratorL3LtVoltageL1Disappeared, tGeneratorL3LtVoltageL1AlarmReset, tGeneratorL3LtVoltageL2Activated,
|
tGeneratorL3LtVoltageL2Disappeared, tGeneratorL3LtVoltageL2AlarmReset, tGeneratorL3LtVoltageSFActivated, tGeneratorL3LtVoltageSFDisappeared, tGeneratorL3LtVoltageSFAlarmReset,
|
tGeneratorL1L2LtVoltageL1Activated, tGeneratorL1L2LtVoltageL1Disappeared, tGeneratorL1L2LtVoltageL1AlarmReset, tGeneratorL1L2LtVoltageL2Activated, tGeneratorL1L2LtVoltageL2Disappeared,
|
tGeneratorL1L2LtVoltageL2AlarmReset, tGeneratorL1L2LtVoltageSFActivated, tGeneratorL1L2LtVoltageSFDisappeared, tGeneratorL1L2LtVoltageSFAlarmReset, tGeneratorL2L3LtVoltageL1Activated,
|
tGeneratorL2L3LtVoltageL1Disappeared, tGeneratorL2L3LtVoltageL1AlarmReset, tGeneratorL2L3LtVoltageL2Activated, tGeneratorL2L3LtVoltageL2Disappeared, tGeneratorL2L3LtVoltageL2AlarmReset,
|
tGeneratorL2L3LtVoltageSFActivated, tGeneratorL2L3LtVoltageSFDisappeared, tGeneratorL2L3LtVoltageSFAlarmReset, tGeneratorL3L1LtVoltageL1Activated, tGeneratorL3L1LtVoltageL1Disappeared,
|
tGeneratorL3L1LtVoltageL1AlarmReset, tGeneratorL3L1LtVoltageL2Activated, tGeneratorL3L1LtVoltageL2Disappeared, tGeneratorL3L1LtVoltageL2AlarmReset, tGeneratorL3L1LtVoltageSFActivated,
|
tGeneratorL3L1LtVoltageSFDisappeared, tGeneratorL3L1LtVoltageSFAlarmReset, tGeneratorGtFrequencyL1Activated, tGeneratorGtFrequencyL1Disappeared, tGeneratorGtFrequencyL1AlarmReset,
|
tGeneratorGtFrequencyL2Activated, tGeneratorGtFrequencyL2Disappeared, tGeneratorGtFrequencyL2AlarmReset, tGeneratorGtFrequencySFActivated, tGeneratorGtFrequencySFDisappeared,
|
tGeneratorGtFrequencySFAlarmReset, tGeneratorLtFrequencyL1Activated, tGeneratorLtFrequencyL1Disappeared, tGeneratorLtFrequencyL1AlarmReset, tGeneratorLtFrequencyL2Activated,
|
tGeneratorLtFrequencyL2Disappeared, tGeneratorLtFrequencyL2AlarmReset, tGeneratorLtFrequencySFActivated, tGeneratorLtFrequencySFDisappeared, tGeneratorLtFrequencySFAlarmReset,
|
tCurrentUnbalanceL1Activated, tCurrentUnbalanceL1Disappeared, tCurrentUnbalanceL1AlarmReset, tCurrentUnbalanceL2Activated, tCurrentUnbalanceL2Disappeared,
|
tCurrentUnbalanceL2AlarmReset, tCurrentUnbalanceSFActivated, tCurrentUnbalanceSFDisappeared, tCurrentUnbalanceSFAlarmReset, tOverloadL1Activated,
|
tOverloadL1Disappeared, tOverloadL1AlarmReset, tOverloadL2Activated, tOverloadL2Disappeared, tOverloadL2AlarmReset,
|
tOverloadSFActivated, tOverloadSFDisappeared, tOverloadSFAlarmReset, tShortCircuitL1Activated, tShortCircuitL1Disappeared,
|
tShortCircuitL1AlarmReset, tShortCircuitL2Activated, tShortCircuitL2Disappeared, tShortCircuitL2AlarmReset, tShortCircuitSFActivated,
|
tShortCircuitSFDisappeared, tShortCircuitSFAlarmReset, tFence1AlarmL1Activated1, tFence1AlarmL1Disappeared1, tFence1AlarmL1AlarmReset1,
|
tFence1AlarmL2Activated1, tFence1AlarmL2Disappeared1, tFence1AlarmL2AlarmReset1, tFence1AlarmSFActivated1, tFence1AlarmSFDisappeared1,
|
tFence1AlarmSFAlarmReset1, tFence1AlarmL1Activated2, tFence1AlarmL1Disappeared2, tFence1AlarmL1AlarmReset2, tFence1AlarmL2Activated2,
|
tFence1AlarmL2Disappeared2, tFence1AlarmL2AlarmReset2, tFence1AlarmSFActivated2, tFence1AlarmSFDisappeared2, tFence1AlarmSFAlarmReset2,
|
tFence2AlarmL1Activated1, tFence2AlarmL1Disappeared1, tFence2AlarmL1AlarmReset1, tFence2AlarmL2Activated1, tFence2AlarmL2Disappeared1,
|
tFence2AlarmL2AlarmReset1, tFence2AlarmSFActivated1, tFence2AlarmSFDisappeared1, tFence2AlarmSFAlarmReset1, tFence2AlarmL1Activated2,
|
tFence2AlarmL1Disappeared2, tFence2AlarmL1AlarmReset2, tFence2AlarmL2Activated2, tFence2AlarmL2Disappeared2, tFence2AlarmL2AlarmReset2,
|
tFence2AlarmSFActivated2, tFence2AlarmSFDisappeared2, tFence2AlarmSFAlarmReset2, tInjectorCylHash1Activated1, tInjectorCylHash2Activated1,
|
tInjectorCylHash3Activated1, tInjectorCylHash4Activated1, tInjectorCylHash5Activated1, tInjectorCylHash6Activated1, t8VSensPwrSuppActivated,
|
tThrottlePosActivated, tAccelPedalPosActivated, tPercentLoadActivated, tFuelDelPressActivated, tWaterInFuelIndActivated,
|
tEngineOilLevelActivated, tEngOilPressActivated, tCrankcasePressActivated1, tBoostPressActivated, tIntakeTempActivated,
|
tAirInletPressActivated, tAirFiltDifPresActivated, tBarometricPresActivated, tCoolantPressActivated, tEngCoolTempActivated,
|
tCoolantLevelActivated, tCrankcasePressActivated2, tFuelRailPressActivated, tBattPotentialActivated, tBatteryVoltageActivated,
|
tAirInletTempActivated, tFuelTempActivated, tEngOilTempActivated, tFuelRateActivated, tRatedEngSpeedActivated,
|
tEngineSpeedActivated, tTimingCalibrActivated1, tJ1939DatalinkActivated, tIncorrectFWActivated, tVINActivated,
|
tTotalEngHoursActivated, tDataLinkCommActivated, tCheckSysParamsActivated, tECMFaultActivated, tTimingCalibrActivated2,
|
t5VSensPwrSuppActivated, tCheckPrgParamsActivated, tTurboOutltPresActivated, tAtmospherPressActivated, tActionAlrtLampActivated,
|
tEngOverspdLampActivated, tEnCoolTempLampActivated, tLubOilPresLampActivated, tEnShutdownLampActivated, tEngWarningLampActivated,
|
tEngSpeedSens2Activated, tCrankTermRelayActivated, tEngDesOpSpeedActivated, t5VSupplyFailActivated, tPrehActuatorActivated,
|
tEMSProgFailureActivated, tEEPROMChecksumActivated, tCalibrMemFailActivated, tCrankSensorActivated, tTimingSensorActivated,
|
tJ1939CANBusActivated, tInjectorCylHash1Activated2, tInjectorCylHash2Activated2, tInjectorCylHash3Activated2, tInjectorCylHash4Activated2,
|
tInjectorCylHash5Activated2, tInjectorCylHash6Activated2, tEngStartRelayActivated, tECM8DCSupplyActivated, tOverrdCtrlModeActivated,
|
tSecSpeedSensActivated, tServiceToolActivated, tRequestedSpeedActivated, tAuxEngSdSwitchActivated, tEngDerateSwtchActivated,
|
tCritOverrideEnActivated, tEngSdApproachActivated, tEngineSdActivated, tCheckCfgParamsActivated, tDiagnosticLampActivated,
|
tECUMainRelayActivated, tAnlgThrottlSigActivated, tInjectorCylHash1Disappeared1, tInjectorCylHash2Disappeared1, tInjectorCylHash3Disappeared1,
|
tInjectorCylHash4Disappeared1, tInjectorCylHash5Disappeared1, tInjectorCylHash6Disappeared1, t8VSensPwrSuppDisappeared, tThrottlePosDisappeared,
|
tAccelPedalPosDisappeared, tPercentLoadDisappeared, tFuelDelPressDisappeared, tWaterInFuelIndDisappeared, tEngineOilLevelDisappeared,
|
tEngOilPressDisappeared, tCrankcasePressDisappeared1, tBoostPressDisappeared, tIntakeTempDisappeared, tAirInletPressDisappeared,
|
tAirFiltDifPresDisappeared, tBarometricPresDisappeared, tCoolantPressDisappeared, tEngCoolTempDisappeared, tCoolantLevelDisappeared,
|
tCrankcasePressDisappeared2, tFuelRailPressDisappeared, tBattPotentialDisappeared, tBatteryVoltageDisappeared, tAirInletTempDisappeared,
|
tFuelTempDisappeared, tEngOilTempDisappeared, tFuelRateDisappeared, tRatedEngSpeedDisappeared, tEngineSpeedDisappeared,
|
tTimingCalibrDisappeared1, tJ1939DatalinkDisappeared, tIncorrectFWDisappeared, tVINDisappeared, tTotalEngHoursDisappeared,
|
tDataLinkCommDisappeared, tCheckSysParamsDisappeared, tECMFaultDisappeared, tTimingCalibrDisappeared2, t5VSensPwrSuppDisappeared,
|
tCheckPrgParamsDisappeared, tTurboOutltPresDisappeared, tAtmospherPressDisappeared, tActionAlrtLampDisappeared, tEngOverspdLampDisappeared,
|
tEnCoolTempLampDisappeared, tLubOilPresLampDisappeared, tEnShutdownLampDisappeared, tEngWarningLampDisappeared, tEngSpeedSens2Disappeared,
|
tCrankTermRelayDisappeared, tEngDesOpSpeedDisappeared, t5VSupplyFailDisappeared, tPrehActuatorDisappeared, tEMSProgFailureDisappeared,
|
tEEPROMChecksumDisappeared, tCalibrMemFailDisappeared, tCrankSensorDisappeared, tTimingSensorDisappeared, tJ1939CANBusDisappeared,
|
tInjectorCylHash1Disappeared2, tInjectorCylHash2Disappeared2, tInjectorCylHash3Disappeared2, tInjectorCylHash4Disappeared2, tInjectorCylHash5Disappeared2,
|
tInjectorCylHash6Disappeared2, tEngStartRelayDisappeared, tECM8DCSupplyDisappeared, tOverrdCtrlModeDisappeared, tSecSpeedSensDisappeared,
|
tServiceToolDisappeared, tRequestedSpeedDisappeared, tAuxEngSdSwitchDisappeared, tEngDerateSwtchDisappeared, tCritOverrideEnDisappeared,
|
tEngSdApproachDisappeared, tEngineSdDisappeared, tCheckCfgParamsDisappeared, tDiagnosticLampDisappeared, tECUMainRelayDisappeared,
|
tAnlgThrottlSigDisappeared, tInjectorCylHash1AlarmReset1, tInjectorCylHash2AlarmReset1, tInjectorCylHash3AlarmReset1, tInjectorCylHash4AlarmReset1,
|
tInjectorCylHash5AlarmReset1, tInjectorCylHash6AlarmReset1, t8VSensPwrSuppAlarmReset, tThrottlePosAlarmReset, tAccelPedalPosAlarmReset,
|
tPercentLoadAlarmReset, tFuelDelPressAlarmReset, tWaterInFuelIndAlarmReset, tEngineOilLevelAlarmReset, tEngOilPressAlarmReset,
|
tCrankcasePressAlarmReset1, tBoostPressAlarmReset, tIntakeTempAlarmReset, tAirInletPressAlarmReset, tAirFiltDifPresAlarmReset,
|
tBarometricPresAlarmReset, tCoolantPressAlarmReset, tEngCoolTempAlarmReset, tCoolantLevelAlarmReset, tCrankcasePressAlarmReset2,
|
tFuelRailPressAlarmReset, tBattPotentialAlarmReset, tBatteryVoltageAlarmReset, tAirInletTempAlarmReset, tFuelTempAlarmReset,
|
tEngOilTempAlarmReset, tFuelRateAlarmReset, tRatedEngSpeedAlarmReset, tEngineSpeedAlarmReset, tTimingCalibrAlarmReset1,
|
tJ1939DatalinkAlarmReset, tIncorrectFWAlarmReset, tVINAlarmReset, tTotalEngHoursAlarmReset, tDataLinkCommAlarmReset,
|
tCheckSysParamsAlarmReset, tECMFaultAlarmReset, tTimingCalibrAlarmReset2, t5VSensPwrSuppAlarmReset, tCheckPrgParamsAlarmReset,
|
tTurboOutltPresAlarmReset, tAtmospherPressAlarmReset, tActionAlrtLampAlarmReset, tEngOverspdLampAlarmReset, tEnCoolTempLampAlarmReset,
|
tLubOilPresLampAlarmReset, tEnShutdownLampAlarmReset, tEngWarningLampAlarmReset, tEngSpeedSens2AlarmReset, tCrankTermRelayAlarmReset,
|
tEngDesOpSpeedAlarmReset, t5VSupplyFailAlarmReset, tPrehActuatorAlarmReset, tEMSProgFailureAlarmReset, tEEPROMChecksumAlarmReset,
|
tCalibrMemFailAlarmReset, tCrankSensorAlarmReset, tTimingSensorAlarmReset, tJ1939CANBusAlarmReset, tInjectorCylHash1AlarmReset2,
|
tInjectorCylHash2AlarmReset2, tInjectorCylHash3AlarmReset2, tInjectorCylHash4AlarmReset2, tInjectorCylHash5AlarmReset2, tInjectorCylHash6AlarmReset2,
|
tEngStartRelayAlarmReset, tECM8DCSupplyAlarmReset, tOverrdCtrlModeAlarmReset, tSecSpeedSensAlarmReset, tServiceToolAlarmReset,
|
tRequestedSpeedAlarmReset, tAuxEngSdSwitchAlarmReset, tEngDerateSwtchAlarmReset, tCritOverrideEnAlarmReset, tEngSdApproachAlarmReset,
|
tEngineSdAlarmReset, tCheckCfgParamsAlarmReset, tDiagnosticLampAlarmReset, tECUMainRelayAlarmReset, tAnlgThrottlSigAlarmReset,
|
tECUCommunicationFail, tBO1, tBO2, tBO3, tBO4,
|
tModuleBroSlotABrcFalseModule, tModuleBroSlotBBrcFalseModule, tModuleBroSlotABrcUnknownModule, tModuleBroSlotBBrcUnknownModule, tModuleBroSlotABrcUnattended,
|
tModuleBroSlotBBrcUnattended, tModuleBroSlotABrcCommCHR2EOutage, tModuleBroSlotBBrcCommCHR2EOutage, tModuleBroSlotABrcUnexpected, tModuleBroSlotBBrcUnexpected,
|
tEMBroABrcAMessageLost, tEMBroBBrcAMessageLost, tEMBroABrcConfigurationMistake, tEMBroBBrcConfigurationMistake, tEMBroABrcInsufficient,
|
tEMBroBBrcInsufficient, tEMBroABrcMissingOrDamaged, tEMBroBBrcMissingOrDamaged, tForceHistCHR2E1, tForceHistCHR2E2,
|
thistPLC3, thistPLC4, tFaultReset, tEventEMail1OK, tEventEMail2OK,
|
tEventEMail3OK, tEventEMail4OK, tEventSMS1OK, tEventSMS2OK, tEventSMS3OK,
|
tEventSMS4OK, tAlarmEMail1OK, tAlarmEMail2OK, tAlarmEMail3OK, tAlarmEMail4OK,
|
tAlarmSMS1OK, tAlarmSMS2OK, tAlarmSMS3OK, tAlarmSMS4OK, tSNMPTRAP1OK,
|
tSNMPTRAP2OK, tEventEMail1Fail, tEventEMail2Fail, tEventEMail3Fail, tEventEMail4Fail,
|
tEventSMS1Fail, tEventSMS2Fail, tEventSMS3Fail, tEventSMS4Fail, tAlarmEMail1Fail,
|
tAlarmEMail2Fail, tAlarmEMail3Fail, tAlarmEMail4Fail, tAlarmSMS1Fail, tAlarmSMS2Fail,
|
tAlarmSMS3Fail, tAlarmSMS4Fail, tSNMPTRAP1Fail, tSNMPTRAP2Fail, tSwitchedOn,
|
tWatchdog, tSystem, tSystemLog, tWrongConfig, tSetpointChange,
|
tPasswordSet, tPasswordChng, tAccessCodeSet, tAccessCodeChng, tAdminAction,
|
tTerminal, tExtDisplay, tBinaryUnstable, tForceValue, tTimeModeChange,
|
tGroupsLinked, tGroupsUnlinked, tPreAlarmStamp, tProgrammingRequest, tProgrammingFinished,
|
tProgrammingResult, tUnknownECUDiag, tAlCHR2FHistCHR2Emsg1, tAlCHR2FHistCHR2Emsg2, tAlCHR2FHistCHR2Emsg3,
|
tAlCHR2FHistCHR2Emsg4, tAlCHR2FHistCHR2Emsg5, tAlCHR2FHistCHR2Emsg6, tAlCHR2FHistCHR2Emsg7, tAlCHR2FHistCHR2Emsg8,
|
tAlCHR2FHistCHR2Emsg9, tAlCHR2FHistCHR2Emsg10, tAlCHR2FHistCHR2Emsg11, tAlCHR2FHistCHR2Emsg12, tAlCHR2FHistCHR2Emsg13,
|
tAlCHR2FHistCHR2Emsg14, tAlCHR2FHistCHR2Emsg15, tAlCHR2FHistCHR2Emsg16, tTimeStamp, tEmergencyStop,
|
tGeneratorL1GtVoltage, tGeneratorL2GtVoltage, tGeneratorL3GtVoltage, tGeneratorL1LtVoltage, tGeneratorL2LtVoltage,
|
tGeneratorL3LtVoltage, tGeneratorL1L2GtVoltage, tGeneratorL2L3GtVoltage, tGeneratorL3L1GtVoltage, tGeneratorL1L2LtVoltage,
|
tGeneratorL2L3LtVoltage, tGeneratorL3L1LtVoltage, tGeneratorVoltageUnbalance, tCurrentUnbalance, tGeneratorGtFrequency,
|
tGeneratorLtFrequency, tMainsL1GtVoltage, tMainsL2GtVoltage, tMainsL3GtVoltage, tMainsL1LtVoltage,
|
tMainsL2LtVoltage, tMainsL3LtVoltage, tMainsL1L2GtVoltage, tMainsL2L3GtVoltage, tMainsL3L1GtVoltage,
|
tMainsL1L2LtVoltage, tMainsL2L3LtVoltage, tMainsL3L1LtVoltage, tMainsVoltageUnbalance, tMainsGtFrequency,
|
tMainsLtFrequency, tOverload, tSdGCBFail, tWrnMCBFail, tSdOverspeed,
|
tSdUnderspeed, tSdIOMFail, tSdRPMMeasurementFail, tSdBatteryFlat, tSdStartFail,
|
tWrnMaintenance1, tWrnMaintenance2, tWrnMaintenance3, tShortCircuit, tBOCOvercurrentIDMT,
|
tSdEarthFaultCurrent, tEarthAmpsIDMT, tWrnRA15Fail, tWrnCoolantTemperatureLow, tBatteryChargeFail,
|
tWrnOverrideAllSd, tTimerON, tTimerOFF, tres1, tres2,
|
tECUFault, tWrnECUCommunicationFail, tDPFRegenInhib, tRegenerNeeded, tRegenerNeededCHR21,
|
tHESTLamp, tECURedLamp, tECUYellowLamp, tECUWaitToStart, tWrnMainsVoltageDetected,
|
tGeneratorCCWRotation, tMainsCCWRotation, tMainsFail, tMainsReturned, tLoadOnMains,
|
tLoadOnGenset, tAltConf1Active, tAltConf2Active, tWrnRentalTimer1, tWrnRentalTimer2,
|
tRentalTimer1Elapsed, tRentalTimer2Elapsed, tBOCRentalTimer1Exceeded, tBOCRentalTimer2Exceeded, tGenPeakStart,
|
tPMSStart, tRemoteStart, tAMFStart, tManualStart, tTestStart,
|
tGenSetStop, tManualStop, tAMFStop, tRemoteStop, tGenPeakStop,
|
tPMSStop, tTESTModeON, tTESTModeOFF, tGCBOpened, tGCBClosed,
|
tMCBOpened, tMCBOpenExt, tMCBClosed, tSyncStarted, tRevSyncStarted,
|
tReady, tIdleRun, tRunning, tWarming, tSoftLoad,
|
tLoaded, tSoftUnload, tCooling, tEmergMAN, tNotReady,
|
tWrnChargingAlternatorFail, tWrnStopFail, tTestOnLoad, tFence1Alarm, tFence2Alarm,
|
tWrnFuelTheft, tProtectionsDisabled, tProtectionsEnabled }
|
STATUS current
|
DESCRIPTION "Notifications"
|
::= { conformanceGroups 6 }
|
|
tRemoteStartCHR2FStopL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Remote Start/Stop - alarm activated"
|
::= { notifications 8388608 }
|
|
tRemoteStartCHR2FStopL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Remote Start/Stop - alarm disappeared"
|
::= { notifications 8388609 }
|
|
tRemoteStartCHR2FStopL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Remote Start/Stop - alarm reset"
|
::= { notifications 8388610 }
|
|
tRemoteStartCHR2FStopL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Remote Start/Stop - alarm activated"
|
::= { notifications 142606336 }
|
|
tRemoteStartCHR2FStopL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Remote Start/Stop - alarm disappeared"
|
::= { notifications 142606337 }
|
|
tRemoteStartCHR2FStopL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Remote Start/Stop - alarm reset"
|
::= { notifications 142606338 }
|
|
tRemoteStartCHR2FStopSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Remote Start/Stop - alarm activated"
|
::= { notifications 276824064 }
|
|
tRemoteStartCHR2FStopSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Remote Start/Stop - alarm disappeared"
|
::= { notifications 276824065 }
|
|
tRemoteStartCHR2FStopSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Remote Start/Stop - alarm reset"
|
::= { notifications 276824066 }
|
|
tRemTESTOnLoadL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rem TEST On Load - alarm activated"
|
::= { notifications 8388612 }
|
|
tRemTESTOnLoadL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rem TEST On Load - alarm disappeared"
|
::= { notifications 8388613 }
|
|
tRemTESTOnLoadL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rem TEST On Load - alarm reset"
|
::= { notifications 8388614 }
|
|
tRemTESTOnLoadL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rem TEST On Load - alarm activated"
|
::= { notifications 142606340 }
|
|
tRemTESTOnLoadL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rem TEST On Load - alarm disappeared"
|
::= { notifications 142606341 }
|
|
tRemTESTOnLoadL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rem TEST On Load - alarm reset"
|
::= { notifications 142606342 }
|
|
tRemTESTOnLoadSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rem TEST On Load - alarm activated"
|
::= { notifications 276824068 }
|
|
tRemTESTOnLoadSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rem TEST On Load - alarm disappeared"
|
::= { notifications 276824069 }
|
|
tRemTESTOnLoadSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rem TEST On Load - alarm reset"
|
::= { notifications 276824070 }
|
|
tFuelLeakL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Leak - alarm activated"
|
::= { notifications 8388616 }
|
|
tFuelLeakL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Leak - alarm disappeared"
|
::= { notifications 8388617 }
|
|
tFuelLeakL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Leak - alarm reset"
|
::= { notifications 8388618 }
|
|
tFuelLeakL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Leak - alarm activated"
|
::= { notifications 142606344 }
|
|
tFuelLeakL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Leak - alarm disappeared"
|
::= { notifications 142606345 }
|
|
tFuelLeakL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Leak - alarm reset"
|
::= { notifications 142606346 }
|
|
tFuelLeakSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Leak - alarm activated"
|
::= { notifications 276824072 }
|
|
tFuelLeakSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Leak - alarm disappeared"
|
::= { notifications 276824073 }
|
|
tFuelLeakSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Leak - alarm reset"
|
::= { notifications 276824074 }
|
|
tLowOilLevelL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Low Oil Level - alarm activated"
|
::= { notifications 8388628 }
|
|
tLowOilLevelL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Low Oil Level - alarm disappeared"
|
::= { notifications 8388629 }
|
|
tLowOilLevelL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Low Oil Level - alarm reset"
|
::= { notifications 8388630 }
|
|
tLowOilLevelL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Low Oil Level - alarm activated"
|
::= { notifications 142606356 }
|
|
tLowOilLevelL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Low Oil Level - alarm disappeared"
|
::= { notifications 142606357 }
|
|
tLowOilLevelL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Low Oil Level - alarm reset"
|
::= { notifications 142606358 }
|
|
tLowOilLevelSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Low Oil Level - alarm activated"
|
::= { notifications 276824084 }
|
|
tLowOilLevelSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Low Oil Level - alarm disappeared"
|
::= { notifications 276824085 }
|
|
tLowOilLevelSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Low Oil Level - alarm reset"
|
::= { notifications 276824086 }
|
|
tLowCoolantLevelL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Low Coolant Level - alarm activated"
|
::= { notifications 8388632 }
|
|
tLowCoolantLevelL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Low Coolant Level - alarm disappeared"
|
::= { notifications 8388633 }
|
|
tLowCoolantLevelL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Low Coolant Level - alarm reset"
|
::= { notifications 8388634 }
|
|
tLowCoolantLevelL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Low Coolant Level - alarm activated"
|
::= { notifications 142606360 }
|
|
tLowCoolantLevelL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Low Coolant Level - alarm disappeared"
|
::= { notifications 142606361 }
|
|
tLowCoolantLevelL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Low Coolant Level - alarm reset"
|
::= { notifications 142606362 }
|
|
tLowCoolantLevelSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Low Coolant Level - alarm activated"
|
::= { notifications 276824088 }
|
|
tLowCoolantLevelSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Low Coolant Level - alarm disappeared"
|
::= { notifications 276824089 }
|
|
tLowCoolantLevelSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Low Coolant Level - alarm reset"
|
::= { notifications 276824090 }
|
|
tEmergencyStopL1Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Emergency Stop - alarm activated"
|
::= { notifications 8388636 }
|
|
tEmergencyStopL1Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Emergency Stop - alarm disappeared"
|
::= { notifications 8388637 }
|
|
tEmergencyStopL1AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Emergency Stop - alarm reset"
|
::= { notifications 8388638 }
|
|
tEmergencyStopL2Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Emergency Stop - alarm activated"
|
::= { notifications 142606364 }
|
|
tEmergencyStopL2Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Emergency Stop - alarm disappeared"
|
::= { notifications 142606365 }
|
|
tEmergencyStopL2AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Emergency Stop - alarm reset"
|
::= { notifications 142606366 }
|
|
tEmergencyStopSFActivated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Emergency Stop - alarm activated"
|
::= { notifications 276824092 }
|
|
tEmergencyStopSFDisappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Emergency Stop - alarm disappeared"
|
::= { notifications 276824093 }
|
|
tEmergencyStopSFAlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Emergency Stop - alarm reset"
|
::= { notifications 276824094 }
|
|
tFuelLevelL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Level - alarm activated"
|
::= { notifications 16777224 }
|
|
tFuelLevelL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Level - alarm disappeared"
|
::= { notifications 16777225 }
|
|
tFuelLevelL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Level - alarm reset"
|
::= { notifications 16777226 }
|
|
tFuelLevelL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Level - alarm activated"
|
::= { notifications 150994952 }
|
|
tFuelLevelL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Level - alarm disappeared"
|
::= { notifications 150994953 }
|
|
tFuelLevelL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Level - alarm reset"
|
::= { notifications 150994954 }
|
|
tFuelLevelSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Level - alarm activated"
|
::= { notifications 285212680 }
|
|
tFuelLevelSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Level - alarm disappeared"
|
::= { notifications 285212681 }
|
|
tFuelLevelSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Level - alarm reset"
|
::= { notifications 285212682 }
|
|
tBatteryChargL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BatteryCharg - alarm activated"
|
::= { notifications 16777228 }
|
|
tBatteryChargL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BatteryCharg - alarm disappeared"
|
::= { notifications 16777229 }
|
|
tBatteryChargL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BatteryCharg - alarm reset"
|
::= { notifications 16777230 }
|
|
tBatteryChargL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BatteryCharg - alarm activated"
|
::= { notifications 150994956 }
|
|
tBatteryChargL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BatteryCharg - alarm disappeared"
|
::= { notifications 150994957 }
|
|
tBatteryChargL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BatteryCharg - alarm reset"
|
::= { notifications 150994958 }
|
|
tBatteryChargSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BatteryCharg - alarm activated"
|
::= { notifications 285212684 }
|
|
tBatteryChargSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BatteryCharg - alarm disappeared"
|
::= { notifications 285212685 }
|
|
tBatteryChargSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BatteryCharg - alarm reset"
|
::= { notifications 285212686 }
|
|
tEngineSpeedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Engine Speed - alarm activated"
|
::= { notifications 16777488 }
|
|
tEngineSpeedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Engine Speed - alarm disappeared"
|
::= { notifications 16777489 }
|
|
tEngineSpeedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Engine Speed - alarm reset"
|
::= { notifications 16777490 }
|
|
tEngineSpeedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Engine Speed - alarm activated"
|
::= { notifications 150995216 }
|
|
tEngineSpeedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Engine Speed - alarm disappeared"
|
::= { notifications 150995217 }
|
|
tEngineSpeedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Engine Speed - alarm reset"
|
::= { notifications 150995218 }
|
|
tEngineSpeedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Engine Speed - alarm activated"
|
::= { notifications 285212944 }
|
|
tEngineSpeedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Engine Speed - alarm disappeared"
|
::= { notifications 285212945 }
|
|
tEngineSpeedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Engine Speed - alarm reset"
|
::= { notifications 285212946 }
|
|
tFuelRateL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Rate - alarm activated"
|
::= { notifications 16777492 }
|
|
tFuelRateL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Rate - alarm disappeared"
|
::= { notifications 16777493 }
|
|
tFuelRateL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Rate - alarm reset"
|
::= { notifications 16777494 }
|
|
tFuelRateL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Rate - alarm activated"
|
::= { notifications 150995220 }
|
|
tFuelRateL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Rate - alarm disappeared"
|
::= { notifications 150995221 }
|
|
tFuelRateL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Rate - alarm reset"
|
::= { notifications 150995222 }
|
|
tFuelRateSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Rate - alarm activated"
|
::= { notifications 285212948 }
|
|
tFuelRateSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Rate - alarm disappeared"
|
::= { notifications 285212949 }
|
|
tFuelRateSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Rate - alarm reset"
|
::= { notifications 285212950 }
|
|
tCoolantTempL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - CoolantTemp - alarm activated"
|
::= { notifications 16777496 }
|
|
tCoolantTempL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - CoolantTemp - alarm disappeared"
|
::= { notifications 16777497 }
|
|
tCoolantTempL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - CoolantTemp - alarm reset"
|
::= { notifications 16777498 }
|
|
tCoolantTempL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - CoolantTemp - alarm activated"
|
::= { notifications 150995224 }
|
|
tCoolantTempL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - CoolantTemp - alarm disappeared"
|
::= { notifications 150995225 }
|
|
tCoolantTempL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - CoolantTemp - alarm reset"
|
::= { notifications 150995226 }
|
|
tCoolantTempSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - CoolantTemp - alarm activated"
|
::= { notifications 285212952 }
|
|
tCoolantTempSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - CoolantTemp - alarm disappeared"
|
::= { notifications 285212953 }
|
|
tCoolantTempSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - CoolantTemp - alarm reset"
|
::= { notifications 285212954 }
|
|
tOilPressL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Oil Press - alarm activated"
|
::= { notifications 16777504 }
|
|
tOilPressL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Oil Press - alarm disappeared"
|
::= { notifications 16777505 }
|
|
tOilPressL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Oil Press - alarm reset"
|
::= { notifications 16777506 }
|
|
tOilPressL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Oil Press - alarm activated"
|
::= { notifications 150995232 }
|
|
tOilPressL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Oil Press - alarm disappeared"
|
::= { notifications 150995233 }
|
|
tOilPressL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Oil Press - alarm reset"
|
::= { notifications 150995234 }
|
|
tOilPressSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Oil Press - alarm activated"
|
::= { notifications 285212960 }
|
|
tOilPressSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Oil Press - alarm disappeared"
|
::= { notifications 285212961 }
|
|
tOilPressSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Oil Press - alarm reset"
|
::= { notifications 285212962 }
|
|
tAlCHR2FHistCHR2Emsg1L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 1 - alarm activated"
|
::= { notifications 41943040 }
|
|
tAlCHR2FHistCHR2Emsg1L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 1 - alarm disappeared"
|
::= { notifications 41943041 }
|
|
tAlCHR2FHistCHR2Emsg1L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 1 - alarm reset"
|
::= { notifications 41943042 }
|
|
tAlCHR2FHistCHR2Emsg1L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 1 - alarm activated"
|
::= { notifications 176160768 }
|
|
tAlCHR2FHistCHR2Emsg1L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 1 - alarm disappeared"
|
::= { notifications 176160769 }
|
|
tAlCHR2FHistCHR2Emsg1L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 1 - alarm reset"
|
::= { notifications 176160770 }
|
|
tAlCHR2FHistCHR2Emsg1SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 1 - alarm activated"
|
::= { notifications 310378496 }
|
|
tAlCHR2FHistCHR2Emsg1SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 1 - alarm disappeared"
|
::= { notifications 310378497 }
|
|
tAlCHR2FHistCHR2Emsg1SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 1 - alarm reset"
|
::= { notifications 310378498 }
|
|
tAlCHR2FHistCHR2Emsg2L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 2 - alarm activated"
|
::= { notifications 41943044 }
|
|
tAlCHR2FHistCHR2Emsg2L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 2 - alarm disappeared"
|
::= { notifications 41943045 }
|
|
tAlCHR2FHistCHR2Emsg2L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 2 - alarm reset"
|
::= { notifications 41943046 }
|
|
tAlCHR2FHistCHR2Emsg2L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 2 - alarm activated"
|
::= { notifications 176160772 }
|
|
tAlCHR2FHistCHR2Emsg2L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 2 - alarm disappeared"
|
::= { notifications 176160773 }
|
|
tAlCHR2FHistCHR2Emsg2L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 2 - alarm reset"
|
::= { notifications 176160774 }
|
|
tAlCHR2FHistCHR2Emsg2SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 2 - alarm activated"
|
::= { notifications 310378500 }
|
|
tAlCHR2FHistCHR2Emsg2SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 2 - alarm disappeared"
|
::= { notifications 310378501 }
|
|
tAlCHR2FHistCHR2Emsg2SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 2 - alarm reset"
|
::= { notifications 310378502 }
|
|
tAlCHR2FHistCHR2Emsg3L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 3 - alarm activated"
|
::= { notifications 41943048 }
|
|
tAlCHR2FHistCHR2Emsg3L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 3 - alarm disappeared"
|
::= { notifications 41943049 }
|
|
tAlCHR2FHistCHR2Emsg3L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 3 - alarm reset"
|
::= { notifications 41943050 }
|
|
tAlCHR2FHistCHR2Emsg3L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 3 - alarm activated"
|
::= { notifications 176160776 }
|
|
tAlCHR2FHistCHR2Emsg3L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 3 - alarm disappeared"
|
::= { notifications 176160777 }
|
|
tAlCHR2FHistCHR2Emsg3L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 3 - alarm reset"
|
::= { notifications 176160778 }
|
|
tAlCHR2FHistCHR2Emsg3SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 3 - alarm activated"
|
::= { notifications 310378504 }
|
|
tAlCHR2FHistCHR2Emsg3SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 3 - alarm disappeared"
|
::= { notifications 310378505 }
|
|
tAlCHR2FHistCHR2Emsg3SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 3 - alarm reset"
|
::= { notifications 310378506 }
|
|
tAlCHR2FHistCHR2Emsg4L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 4 - alarm activated"
|
::= { notifications 41943052 }
|
|
tAlCHR2FHistCHR2Emsg4L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 4 - alarm disappeared"
|
::= { notifications 41943053 }
|
|
tAlCHR2FHistCHR2Emsg4L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 4 - alarm reset"
|
::= { notifications 41943054 }
|
|
tAlCHR2FHistCHR2Emsg4L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 4 - alarm activated"
|
::= { notifications 176160780 }
|
|
tAlCHR2FHistCHR2Emsg4L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 4 - alarm disappeared"
|
::= { notifications 176160781 }
|
|
tAlCHR2FHistCHR2Emsg4L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 4 - alarm reset"
|
::= { notifications 176160782 }
|
|
tAlCHR2FHistCHR2Emsg4SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 4 - alarm activated"
|
::= { notifications 310378508 }
|
|
tAlCHR2FHistCHR2Emsg4SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 4 - alarm disappeared"
|
::= { notifications 310378509 }
|
|
tAlCHR2FHistCHR2Emsg4SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 4 - alarm reset"
|
::= { notifications 310378510 }
|
|
tAlCHR2FHistCHR2Emsg5L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 5 - alarm activated"
|
::= { notifications 41943056 }
|
|
tAlCHR2FHistCHR2Emsg5L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 5 - alarm disappeared"
|
::= { notifications 41943057 }
|
|
tAlCHR2FHistCHR2Emsg5L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 5 - alarm reset"
|
::= { notifications 41943058 }
|
|
tAlCHR2FHistCHR2Emsg5L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 5 - alarm activated"
|
::= { notifications 176160784 }
|
|
tAlCHR2FHistCHR2Emsg5L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 5 - alarm disappeared"
|
::= { notifications 176160785 }
|
|
tAlCHR2FHistCHR2Emsg5L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 5 - alarm reset"
|
::= { notifications 176160786 }
|
|
tAlCHR2FHistCHR2Emsg5SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 5 - alarm activated"
|
::= { notifications 310378512 }
|
|
tAlCHR2FHistCHR2Emsg5SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 5 - alarm disappeared"
|
::= { notifications 310378513 }
|
|
tAlCHR2FHistCHR2Emsg5SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 5 - alarm reset"
|
::= { notifications 310378514 }
|
|
tAlCHR2FHistCHR2Emsg6L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 6 - alarm activated"
|
::= { notifications 41943060 }
|
|
tAlCHR2FHistCHR2Emsg6L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 6 - alarm disappeared"
|
::= { notifications 41943061 }
|
|
tAlCHR2FHistCHR2Emsg6L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 6 - alarm reset"
|
::= { notifications 41943062 }
|
|
tAlCHR2FHistCHR2Emsg6L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 6 - alarm activated"
|
::= { notifications 176160788 }
|
|
tAlCHR2FHistCHR2Emsg6L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 6 - alarm disappeared"
|
::= { notifications 176160789 }
|
|
tAlCHR2FHistCHR2Emsg6L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 6 - alarm reset"
|
::= { notifications 176160790 }
|
|
tAlCHR2FHistCHR2Emsg6SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 6 - alarm activated"
|
::= { notifications 310378516 }
|
|
tAlCHR2FHistCHR2Emsg6SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 6 - alarm disappeared"
|
::= { notifications 310378517 }
|
|
tAlCHR2FHistCHR2Emsg6SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 6 - alarm reset"
|
::= { notifications 310378518 }
|
|
tAlCHR2FHistCHR2Emsg7L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 7 - alarm activated"
|
::= { notifications 41943064 }
|
|
tAlCHR2FHistCHR2Emsg7L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 7 - alarm disappeared"
|
::= { notifications 41943065 }
|
|
tAlCHR2FHistCHR2Emsg7L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 7 - alarm reset"
|
::= { notifications 41943066 }
|
|
tAlCHR2FHistCHR2Emsg7L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 7 - alarm activated"
|
::= { notifications 176160792 }
|
|
tAlCHR2FHistCHR2Emsg7L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 7 - alarm disappeared"
|
::= { notifications 176160793 }
|
|
tAlCHR2FHistCHR2Emsg7L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 7 - alarm reset"
|
::= { notifications 176160794 }
|
|
tAlCHR2FHistCHR2Emsg7SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 7 - alarm activated"
|
::= { notifications 310378520 }
|
|
tAlCHR2FHistCHR2Emsg7SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 7 - alarm disappeared"
|
::= { notifications 310378521 }
|
|
tAlCHR2FHistCHR2Emsg7SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 7 - alarm reset"
|
::= { notifications 310378522 }
|
|
tAlCHR2FHistCHR2Emsg8L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 8 - alarm activated"
|
::= { notifications 41943068 }
|
|
tAlCHR2FHistCHR2Emsg8L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 8 - alarm disappeared"
|
::= { notifications 41943069 }
|
|
tAlCHR2FHistCHR2Emsg8L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 8 - alarm reset"
|
::= { notifications 41943070 }
|
|
tAlCHR2FHistCHR2Emsg8L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 8 - alarm activated"
|
::= { notifications 176160796 }
|
|
tAlCHR2FHistCHR2Emsg8L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 8 - alarm disappeared"
|
::= { notifications 176160797 }
|
|
tAlCHR2FHistCHR2Emsg8L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 8 - alarm reset"
|
::= { notifications 176160798 }
|
|
tAlCHR2FHistCHR2Emsg8SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 8 - alarm activated"
|
::= { notifications 310378524 }
|
|
tAlCHR2FHistCHR2Emsg8SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 8 - alarm disappeared"
|
::= { notifications 310378525 }
|
|
tAlCHR2FHistCHR2Emsg8SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 8 - alarm reset"
|
::= { notifications 310378526 }
|
|
tAlCHR2FHistCHR2Emsg9L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 9 - alarm activated"
|
::= { notifications 41943072 }
|
|
tAlCHR2FHistCHR2Emsg9L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 9 - alarm disappeared"
|
::= { notifications 41943073 }
|
|
tAlCHR2FHistCHR2Emsg9L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 9 - alarm reset"
|
::= { notifications 41943074 }
|
|
tAlCHR2FHistCHR2Emsg9L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 9 - alarm activated"
|
::= { notifications 176160800 }
|
|
tAlCHR2FHistCHR2Emsg9L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 9 - alarm disappeared"
|
::= { notifications 176160801 }
|
|
tAlCHR2FHistCHR2Emsg9L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 9 - alarm reset"
|
::= { notifications 176160802 }
|
|
tAlCHR2FHistCHR2Emsg9SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 9 - alarm activated"
|
::= { notifications 310378528 }
|
|
tAlCHR2FHistCHR2Emsg9SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 9 - alarm disappeared"
|
::= { notifications 310378529 }
|
|
tAlCHR2FHistCHR2Emsg9SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 9 - alarm reset"
|
::= { notifications 310378530 }
|
|
tAlCHR2FHistCHR2Emsg10L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 10 - alarm activated"
|
::= { notifications 41943076 }
|
|
tAlCHR2FHistCHR2Emsg10L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 10 - alarm disappeared"
|
::= { notifications 41943077 }
|
|
tAlCHR2FHistCHR2Emsg10L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 10 - alarm reset"
|
::= { notifications 41943078 }
|
|
tAlCHR2FHistCHR2Emsg10L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 10 - alarm activated"
|
::= { notifications 176160804 }
|
|
tAlCHR2FHistCHR2Emsg10L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 10 - alarm disappeared"
|
::= { notifications 176160805 }
|
|
tAlCHR2FHistCHR2Emsg10L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 10 - alarm reset"
|
::= { notifications 176160806 }
|
|
tAlCHR2FHistCHR2Emsg10SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 10 - alarm activated"
|
::= { notifications 310378532 }
|
|
tAlCHR2FHistCHR2Emsg10SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 10 - alarm disappeared"
|
::= { notifications 310378533 }
|
|
tAlCHR2FHistCHR2Emsg10SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 10 - alarm reset"
|
::= { notifications 310378534 }
|
|
tAlCHR2FHistCHR2Emsg11L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 11 - alarm activated"
|
::= { notifications 41943080 }
|
|
tAlCHR2FHistCHR2Emsg11L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 11 - alarm disappeared"
|
::= { notifications 41943081 }
|
|
tAlCHR2FHistCHR2Emsg11L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 11 - alarm reset"
|
::= { notifications 41943082 }
|
|
tAlCHR2FHistCHR2Emsg11L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 11 - alarm activated"
|
::= { notifications 176160808 }
|
|
tAlCHR2FHistCHR2Emsg11L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 11 - alarm disappeared"
|
::= { notifications 176160809 }
|
|
tAlCHR2FHistCHR2Emsg11L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 11 - alarm reset"
|
::= { notifications 176160810 }
|
|
tAlCHR2FHistCHR2Emsg11SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 11 - alarm activated"
|
::= { notifications 310378536 }
|
|
tAlCHR2FHistCHR2Emsg11SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 11 - alarm disappeared"
|
::= { notifications 310378537 }
|
|
tAlCHR2FHistCHR2Emsg11SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 11 - alarm reset"
|
::= { notifications 310378538 }
|
|
tAlCHR2FHistCHR2Emsg12L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 12 - alarm activated"
|
::= { notifications 41943084 }
|
|
tAlCHR2FHistCHR2Emsg12L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 12 - alarm disappeared"
|
::= { notifications 41943085 }
|
|
tAlCHR2FHistCHR2Emsg12L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 12 - alarm reset"
|
::= { notifications 41943086 }
|
|
tAlCHR2FHistCHR2Emsg12L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 12 - alarm activated"
|
::= { notifications 176160812 }
|
|
tAlCHR2FHistCHR2Emsg12L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 12 - alarm disappeared"
|
::= { notifications 176160813 }
|
|
tAlCHR2FHistCHR2Emsg12L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 12 - alarm reset"
|
::= { notifications 176160814 }
|
|
tAlCHR2FHistCHR2Emsg12SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 12 - alarm activated"
|
::= { notifications 310378540 }
|
|
tAlCHR2FHistCHR2Emsg12SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 12 - alarm disappeared"
|
::= { notifications 310378541 }
|
|
tAlCHR2FHistCHR2Emsg12SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 12 - alarm reset"
|
::= { notifications 310378542 }
|
|
tAlCHR2FHistCHR2Emsg13L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 13 - alarm activated"
|
::= { notifications 41943088 }
|
|
tAlCHR2FHistCHR2Emsg13L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 13 - alarm disappeared"
|
::= { notifications 41943089 }
|
|
tAlCHR2FHistCHR2Emsg13L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 13 - alarm reset"
|
::= { notifications 41943090 }
|
|
tAlCHR2FHistCHR2Emsg13L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 13 - alarm activated"
|
::= { notifications 176160816 }
|
|
tAlCHR2FHistCHR2Emsg13L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 13 - alarm disappeared"
|
::= { notifications 176160817 }
|
|
tAlCHR2FHistCHR2Emsg13L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 13 - alarm reset"
|
::= { notifications 176160818 }
|
|
tAlCHR2FHistCHR2Emsg13SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 13 - alarm activated"
|
::= { notifications 310378544 }
|
|
tAlCHR2FHistCHR2Emsg13SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 13 - alarm disappeared"
|
::= { notifications 310378545 }
|
|
tAlCHR2FHistCHR2Emsg13SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 13 - alarm reset"
|
::= { notifications 310378546 }
|
|
tAlCHR2FHistCHR2Emsg14L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 14 - alarm activated"
|
::= { notifications 41943092 }
|
|
tAlCHR2FHistCHR2Emsg14L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 14 - alarm disappeared"
|
::= { notifications 41943093 }
|
|
tAlCHR2FHistCHR2Emsg14L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 14 - alarm reset"
|
::= { notifications 41943094 }
|
|
tAlCHR2FHistCHR2Emsg14L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 14 - alarm activated"
|
::= { notifications 176160820 }
|
|
tAlCHR2FHistCHR2Emsg14L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 14 - alarm disappeared"
|
::= { notifications 176160821 }
|
|
tAlCHR2FHistCHR2Emsg14L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 14 - alarm reset"
|
::= { notifications 176160822 }
|
|
tAlCHR2FHistCHR2Emsg14SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 14 - alarm activated"
|
::= { notifications 310378548 }
|
|
tAlCHR2FHistCHR2Emsg14SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 14 - alarm disappeared"
|
::= { notifications 310378549 }
|
|
tAlCHR2FHistCHR2Emsg14SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 14 - alarm reset"
|
::= { notifications 310378550 }
|
|
tAlCHR2FHistCHR2Emsg15L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 15 - alarm activated"
|
::= { notifications 41943096 }
|
|
tAlCHR2FHistCHR2Emsg15L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 15 - alarm disappeared"
|
::= { notifications 41943097 }
|
|
tAlCHR2FHistCHR2Emsg15L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 15 - alarm reset"
|
::= { notifications 41943098 }
|
|
tAlCHR2FHistCHR2Emsg15L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 15 - alarm activated"
|
::= { notifications 176160824 }
|
|
tAlCHR2FHistCHR2Emsg15L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 15 - alarm disappeared"
|
::= { notifications 176160825 }
|
|
tAlCHR2FHistCHR2Emsg15L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 15 - alarm reset"
|
::= { notifications 176160826 }
|
|
tAlCHR2FHistCHR2Emsg15SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 15 - alarm activated"
|
::= { notifications 310378552 }
|
|
tAlCHR2FHistCHR2Emsg15SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 15 - alarm disappeared"
|
::= { notifications 310378553 }
|
|
tAlCHR2FHistCHR2Emsg15SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 15 - alarm reset"
|
::= { notifications 310378554 }
|
|
tAlCHR2FHistCHR2Emsg16L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 16 - alarm activated"
|
::= { notifications 41943100 }
|
|
tAlCHR2FHistCHR2Emsg16L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 16 - alarm disappeared"
|
::= { notifications 41943101 }
|
|
tAlCHR2FHistCHR2Emsg16L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Al/Hist.msg 16 - alarm reset"
|
::= { notifications 41943102 }
|
|
tAlCHR2FHistCHR2Emsg16L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 16 - alarm activated"
|
::= { notifications 176160828 }
|
|
tAlCHR2FHistCHR2Emsg16L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 16 - alarm disappeared"
|
::= { notifications 176160829 }
|
|
tAlCHR2FHistCHR2Emsg16L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Al/Hist.msg 16 - alarm reset"
|
::= { notifications 176160830 }
|
|
tAlCHR2FHistCHR2Emsg16SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 16 - alarm activated"
|
::= { notifications 310378556 }
|
|
tAlCHR2FHistCHR2Emsg16SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 16 - alarm disappeared"
|
::= { notifications 310378557 }
|
|
tAlCHR2FHistCHR2Emsg16SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Al/Hist.msg 16 - alarm reset"
|
::= { notifications 310378558 }
|
|
tBatteryChargerL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Battery Charger - alarm activated"
|
::= { notifications 50331648 }
|
|
tBatteryChargerL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Battery Charger - alarm disappeared"
|
::= { notifications 50331649 }
|
|
tBatteryChargerL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Battery Charger - alarm reset"
|
::= { notifications 50331650 }
|
|
tBatteryChargerL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Battery Charger - alarm activated"
|
::= { notifications 184549376 }
|
|
tBatteryChargerL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Battery Charger - alarm disappeared"
|
::= { notifications 184549377 }
|
|
tBatteryChargerL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Battery Charger - alarm reset"
|
::= { notifications 184549378 }
|
|
tBatteryChargerSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Battery Charger - alarm activated"
|
::= { notifications 318767104 }
|
|
tBatteryChargerSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Battery Charger - alarm disappeared"
|
::= { notifications 318767105 }
|
|
tBatteryChargerSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Battery Charger - alarm reset"
|
::= { notifications 318767106 }
|
|
tForceProtCHR2E2L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Force Prot. 2 - alarm activated"
|
::= { notifications 50331652 }
|
|
tForceProtCHR2E2L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Force Prot. 2 - alarm disappeared"
|
::= { notifications 50331653 }
|
|
tForceProtCHR2E2L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Force Prot. 2 - alarm reset"
|
::= { notifications 50331654 }
|
|
tForceProtCHR2E2L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Force Prot. 2 - alarm activated"
|
::= { notifications 184549380 }
|
|
tForceProtCHR2E2L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Force Prot. 2 - alarm disappeared"
|
::= { notifications 184549381 }
|
|
tForceProtCHR2E2L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Force Prot. 2 - alarm reset"
|
::= { notifications 184549382 }
|
|
tForceProtCHR2E2SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Force Prot. 2 - alarm activated"
|
::= { notifications 318767108 }
|
|
tForceProtCHR2E2SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Force Prot. 2 - alarm disappeared"
|
::= { notifications 318767109 }
|
|
tForceProtCHR2E2SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Force Prot. 2 - alarm reset"
|
::= { notifications 318767110 }
|
|
tModuleBroSlotABrcFalseModuleL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - false module - alarm activated"
|
::= { notifications 25168816 }
|
|
tModuleBroSlotABrcFalseModuleL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - false module - alarm disappeared"
|
::= { notifications 25168817 }
|
|
tModuleBroSlotABrcFalseModuleL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - false module - alarm reset"
|
::= { notifications 25168818 }
|
|
tModuleBroSlotABrcFalseModuleL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - false module - alarm activated"
|
::= { notifications 159386544 }
|
|
tModuleBroSlotABrcFalseModuleL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - false module - alarm disappeared"
|
::= { notifications 159386545 }
|
|
tModuleBroSlotABrcFalseModuleL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - false module - alarm reset"
|
::= { notifications 159386546 }
|
|
tModuleBroSlotABrcFalseModuleSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - false module - alarm activated"
|
::= { notifications 293604272 }
|
|
tModuleBroSlotABrcFalseModuleSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - false module - alarm disappeared"
|
::= { notifications 293604273 }
|
|
tModuleBroSlotABrcFalseModuleSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - false module - alarm reset"
|
::= { notifications 293604274 }
|
|
tModuleBroSlotBBrcFalseModuleL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - false module - alarm activated"
|
::= { notifications 25168840 }
|
|
tModuleBroSlotBBrcFalseModuleL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - false module - alarm disappeared"
|
::= { notifications 25168841 }
|
|
tModuleBroSlotBBrcFalseModuleL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - false module - alarm reset"
|
::= { notifications 25168842 }
|
|
tModuleBroSlotBBrcFalseModuleL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - false module - alarm activated"
|
::= { notifications 159386568 }
|
|
tModuleBroSlotBBrcFalseModuleL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - false module - alarm disappeared"
|
::= { notifications 159386569 }
|
|
tModuleBroSlotBBrcFalseModuleL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - false module - alarm reset"
|
::= { notifications 159386570 }
|
|
tModuleBroSlotBBrcFalseModuleSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - false module - alarm activated"
|
::= { notifications 293604296 }
|
|
tModuleBroSlotBBrcFalseModuleSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - false module - alarm disappeared"
|
::= { notifications 293604297 }
|
|
tModuleBroSlotBBrcFalseModuleSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - false module - alarm reset"
|
::= { notifications 293604298 }
|
|
tModuleBroSlotABrcUnknownModuleL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - unknown module - alarm activated"
|
::= { notifications 25168820 }
|
|
tModuleBroSlotABrcUnknownModuleL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - unknown module - alarm disappeared"
|
::= { notifications 25168821 }
|
|
tModuleBroSlotABrcUnknownModuleL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - unknown module - alarm reset"
|
::= { notifications 25168822 }
|
|
tModuleBroSlotABrcUnknownModuleL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - unknown module - alarm activated"
|
::= { notifications 159386548 }
|
|
tModuleBroSlotABrcUnknownModuleL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - unknown module - alarm disappeared"
|
::= { notifications 159386549 }
|
|
tModuleBroSlotABrcUnknownModuleL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - unknown module - alarm reset"
|
::= { notifications 159386550 }
|
|
tModuleBroSlotABrcUnknownModuleSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - unknown module - alarm activated"
|
::= { notifications 293604276 }
|
|
tModuleBroSlotABrcUnknownModuleSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - unknown module - alarm disappeared"
|
::= { notifications 293604277 }
|
|
tModuleBroSlotABrcUnknownModuleSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - unknown module - alarm reset"
|
::= { notifications 293604278 }
|
|
tModuleBroSlotBBrcUnknownModuleL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - unknown module - alarm activated"
|
::= { notifications 25168844 }
|
|
tModuleBroSlotBBrcUnknownModuleL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - unknown module - alarm disappeared"
|
::= { notifications 25168845 }
|
|
tModuleBroSlotBBrcUnknownModuleL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - unknown module - alarm reset"
|
::= { notifications 25168846 }
|
|
tModuleBroSlotBBrcUnknownModuleL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - unknown module - alarm activated"
|
::= { notifications 159386572 }
|
|
tModuleBroSlotBBrcUnknownModuleL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - unknown module - alarm disappeared"
|
::= { notifications 159386573 }
|
|
tModuleBroSlotBBrcUnknownModuleL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - unknown module - alarm reset"
|
::= { notifications 159386574 }
|
|
tModuleBroSlotBBrcUnknownModuleSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - unknown module - alarm activated"
|
::= { notifications 293604300 }
|
|
tModuleBroSlotBBrcUnknownModuleSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - unknown module - alarm disappeared"
|
::= { notifications 293604301 }
|
|
tModuleBroSlotBBrcUnknownModuleSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - unknown module - alarm reset"
|
::= { notifications 293604302 }
|
|
tModuleBroSlotABrcUnattendedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - unattended - alarm activated"
|
::= { notifications 25168824 }
|
|
tModuleBroSlotABrcUnattendedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - unattended - alarm disappeared"
|
::= { notifications 25168825 }
|
|
tModuleBroSlotABrcUnattendedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - unattended - alarm reset"
|
::= { notifications 25168826 }
|
|
tModuleBroSlotABrcUnattendedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - unattended - alarm activated"
|
::= { notifications 159386552 }
|
|
tModuleBroSlotABrcUnattendedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - unattended - alarm disappeared"
|
::= { notifications 159386553 }
|
|
tModuleBroSlotABrcUnattendedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - unattended - alarm reset"
|
::= { notifications 159386554 }
|
|
tModuleBroSlotABrcUnattendedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - unattended - alarm activated"
|
::= { notifications 293604280 }
|
|
tModuleBroSlotABrcUnattendedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - unattended - alarm disappeared"
|
::= { notifications 293604281 }
|
|
tModuleBroSlotABrcUnattendedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - unattended - alarm reset"
|
::= { notifications 293604282 }
|
|
tModuleBroSlotBBrcUnattendedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - unattended - alarm activated"
|
::= { notifications 25168848 }
|
|
tModuleBroSlotBBrcUnattendedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - unattended - alarm disappeared"
|
::= { notifications 25168849 }
|
|
tModuleBroSlotBBrcUnattendedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - unattended - alarm reset"
|
::= { notifications 25168850 }
|
|
tModuleBroSlotBBrcUnattendedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - unattended - alarm activated"
|
::= { notifications 159386576 }
|
|
tModuleBroSlotBBrcUnattendedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - unattended - alarm disappeared"
|
::= { notifications 159386577 }
|
|
tModuleBroSlotBBrcUnattendedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - unattended - alarm reset"
|
::= { notifications 159386578 }
|
|
tModuleBroSlotBBrcUnattendedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - unattended - alarm activated"
|
::= { notifications 293604304 }
|
|
tModuleBroSlotBBrcUnattendedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - unattended - alarm disappeared"
|
::= { notifications 293604305 }
|
|
tModuleBroSlotBBrcUnattendedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - unattended - alarm reset"
|
::= { notifications 293604306 }
|
|
tModuleBroSlotABrcCommCHR2EOutageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - comm. outage - alarm activated"
|
::= { notifications 25168832 }
|
|
tModuleBroSlotABrcCommCHR2EOutageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - comm. outage - alarm disappeared"
|
::= { notifications 25168833 }
|
|
tModuleBroSlotABrcCommCHR2EOutageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - comm. outage - alarm reset"
|
::= { notifications 25168834 }
|
|
tModuleBroSlotABrcCommCHR2EOutageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - comm. outage - alarm activated"
|
::= { notifications 159386560 }
|
|
tModuleBroSlotABrcCommCHR2EOutageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - comm. outage - alarm disappeared"
|
::= { notifications 159386561 }
|
|
tModuleBroSlotABrcCommCHR2EOutageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - comm. outage - alarm reset"
|
::= { notifications 159386562 }
|
|
tModuleBroSlotABrcCommCHR2EOutageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - comm. outage - alarm activated"
|
::= { notifications 293604288 }
|
|
tModuleBroSlotABrcCommCHR2EOutageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - comm. outage - alarm disappeared"
|
::= { notifications 293604289 }
|
|
tModuleBroSlotABrcCommCHR2EOutageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - comm. outage - alarm reset"
|
::= { notifications 293604290 }
|
|
tModuleBroSlotBBrcCommCHR2EOutageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - comm. outage - alarm activated"
|
::= { notifications 25168856 }
|
|
tModuleBroSlotBBrcCommCHR2EOutageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - comm. outage - alarm disappeared"
|
::= { notifications 25168857 }
|
|
tModuleBroSlotBBrcCommCHR2EOutageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - comm. outage - alarm reset"
|
::= { notifications 25168858 }
|
|
tModuleBroSlotBBrcCommCHR2EOutageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - comm. outage - alarm activated"
|
::= { notifications 159386584 }
|
|
tModuleBroSlotBBrcCommCHR2EOutageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - comm. outage - alarm disappeared"
|
::= { notifications 159386585 }
|
|
tModuleBroSlotBBrcCommCHR2EOutageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - comm. outage - alarm reset"
|
::= { notifications 159386586 }
|
|
tModuleBroSlotBBrcCommCHR2EOutageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - comm. outage - alarm activated"
|
::= { notifications 293604312 }
|
|
tModuleBroSlotBBrcCommCHR2EOutageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - comm. outage - alarm disappeared"
|
::= { notifications 293604313 }
|
|
tModuleBroSlotBBrcCommCHR2EOutageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - comm. outage - alarm reset"
|
::= { notifications 293604314 }
|
|
tModuleBroSlotABrcUnexpectedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - unexpected - alarm activated"
|
::= { notifications 25168864 }
|
|
tModuleBroSlotABrcUnexpectedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - unexpected - alarm disappeared"
|
::= { notifications 25168865 }
|
|
tModuleBroSlotABrcUnexpectedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotA) - unexpected - alarm reset"
|
::= { notifications 25168866 }
|
|
tModuleBroSlotABrcUnexpectedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - unexpected - alarm activated"
|
::= { notifications 159386592 }
|
|
tModuleBroSlotABrcUnexpectedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - unexpected - alarm disappeared"
|
::= { notifications 159386593 }
|
|
tModuleBroSlotABrcUnexpectedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotA) - unexpected - alarm reset"
|
::= { notifications 159386594 }
|
|
tModuleBroSlotABrcUnexpectedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - unexpected - alarm activated"
|
::= { notifications 293604320 }
|
|
tModuleBroSlotABrcUnexpectedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - unexpected - alarm disappeared"
|
::= { notifications 293604321 }
|
|
tModuleBroSlotABrcUnexpectedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotA) - unexpected - alarm reset"
|
::= { notifications 293604322 }
|
|
tModuleBroSlotBBrcUnexpectedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - unexpected - alarm activated"
|
::= { notifications 25168868 }
|
|
tModuleBroSlotBBrcUnexpectedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - unexpected - alarm disappeared"
|
::= { notifications 25168869 }
|
|
tModuleBroSlotBBrcUnexpectedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module(slotB) - unexpected - alarm reset"
|
::= { notifications 25168870 }
|
|
tModuleBroSlotBBrcUnexpectedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - unexpected - alarm activated"
|
::= { notifications 159386596 }
|
|
tModuleBroSlotBBrcUnexpectedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - unexpected - alarm disappeared"
|
::= { notifications 159386597 }
|
|
tModuleBroSlotBBrcUnexpectedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module(slotB) - unexpected - alarm reset"
|
::= { notifications 159386598 }
|
|
tModuleBroSlotBBrcUnexpectedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - unexpected - alarm activated"
|
::= { notifications 293604324 }
|
|
tModuleBroSlotBBrcUnexpectedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - unexpected - alarm disappeared"
|
::= { notifications 293604325 }
|
|
tModuleBroSlotBBrcUnexpectedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module(slotB) - unexpected - alarm reset"
|
::= { notifications 293604326 }
|
|
tEMBroABrcAMessageLostL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - a message lost - alarm activated"
|
::= { notifications 25168828 }
|
|
tEMBroABrcAMessageLostL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - a message lost - alarm disappeared"
|
::= { notifications 25168829 }
|
|
tEMBroABrcAMessageLostL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - a message lost - alarm reset"
|
::= { notifications 25168830 }
|
|
tEMBroABrcAMessageLostL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - a message lost - alarm activated"
|
::= { notifications 159386556 }
|
|
tEMBroABrcAMessageLostL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - a message lost - alarm disappeared"
|
::= { notifications 159386557 }
|
|
tEMBroABrcAMessageLostL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - a message lost - alarm reset"
|
::= { notifications 159386558 }
|
|
tEMBroABrcAMessageLostSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - a message lost - alarm activated"
|
::= { notifications 293604284 }
|
|
tEMBroABrcAMessageLostSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - a message lost - alarm disappeared"
|
::= { notifications 293604285 }
|
|
tEMBroABrcAMessageLostSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - a message lost - alarm reset"
|
::= { notifications 293604286 }
|
|
tEMBroBBrcAMessageLostL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - a message lost - alarm activated"
|
::= { notifications 25168852 }
|
|
tEMBroBBrcAMessageLostL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - a message lost - alarm disappeared"
|
::= { notifications 25168853 }
|
|
tEMBroBBrcAMessageLostL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - a message lost - alarm reset"
|
::= { notifications 25168854 }
|
|
tEMBroBBrcAMessageLostL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - a message lost - alarm activated"
|
::= { notifications 159386580 }
|
|
tEMBroBBrcAMessageLostL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - a message lost - alarm disappeared"
|
::= { notifications 159386581 }
|
|
tEMBroBBrcAMessageLostL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - a message lost - alarm reset"
|
::= { notifications 159386582 }
|
|
tEMBroBBrcAMessageLostSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - a message lost - alarm activated"
|
::= { notifications 293604308 }
|
|
tEMBroBBrcAMessageLostSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - a message lost - alarm disappeared"
|
::= { notifications 293604309 }
|
|
tEMBroBBrcAMessageLostSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - a message lost - alarm reset"
|
::= { notifications 293604310 }
|
|
tEMBroABrcConfigurationMistakeL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - configuration mistake - alarm activated"
|
::= { notifications 25168872 }
|
|
tEMBroABrcConfigurationMistakeL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - configuration mistake - alarm disappeared"
|
::= { notifications 25168873 }
|
|
tEMBroABrcConfigurationMistakeL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - configuration mistake - alarm reset"
|
::= { notifications 25168874 }
|
|
tEMBroABrcConfigurationMistakeL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - configuration mistake - alarm activated"
|
::= { notifications 159386600 }
|
|
tEMBroABrcConfigurationMistakeL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - configuration mistake - alarm disappeared"
|
::= { notifications 159386601 }
|
|
tEMBroABrcConfigurationMistakeL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - configuration mistake - alarm reset"
|
::= { notifications 159386602 }
|
|
tEMBroABrcConfigurationMistakeSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - configuration mistake - alarm activated"
|
::= { notifications 293604328 }
|
|
tEMBroABrcConfigurationMistakeSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - configuration mistake - alarm disappeared"
|
::= { notifications 293604329 }
|
|
tEMBroABrcConfigurationMistakeSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - configuration mistake - alarm reset"
|
::= { notifications 293604330 }
|
|
tEMBroBBrcConfigurationMistakeL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - configuration mistake - alarm activated"
|
::= { notifications 25168876 }
|
|
tEMBroBBrcConfigurationMistakeL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - configuration mistake - alarm disappeared"
|
::= { notifications 25168877 }
|
|
tEMBroBBrcConfigurationMistakeL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - configuration mistake - alarm reset"
|
::= { notifications 25168878 }
|
|
tEMBroBBrcConfigurationMistakeL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - configuration mistake - alarm activated"
|
::= { notifications 159386604 }
|
|
tEMBroBBrcConfigurationMistakeL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - configuration mistake - alarm disappeared"
|
::= { notifications 159386605 }
|
|
tEMBroBBrcConfigurationMistakeL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - configuration mistake - alarm reset"
|
::= { notifications 159386606 }
|
|
tEMBroBBrcConfigurationMistakeSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - configuration mistake - alarm activated"
|
::= { notifications 293604332 }
|
|
tEMBroBBrcConfigurationMistakeSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - configuration mistake - alarm disappeared"
|
::= { notifications 293604333 }
|
|
tEMBroBBrcConfigurationMistakeSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - configuration mistake - alarm reset"
|
::= { notifications 293604334 }
|
|
tEMBroABrcInsufficientL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - insufficient - alarm activated"
|
::= { notifications 25168880 }
|
|
tEMBroABrcInsufficientL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - insufficient - alarm disappeared"
|
::= { notifications 25168881 }
|
|
tEMBroABrcInsufficientL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - insufficient - alarm reset"
|
::= { notifications 25168882 }
|
|
tEMBroABrcInsufficientL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - insufficient - alarm activated"
|
::= { notifications 159386608 }
|
|
tEMBroABrcInsufficientL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - insufficient - alarm disappeared"
|
::= { notifications 159386609 }
|
|
tEMBroABrcInsufficientL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - insufficient - alarm reset"
|
::= { notifications 159386610 }
|
|
tEMBroABrcInsufficientSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - insufficient - alarm activated"
|
::= { notifications 293604336 }
|
|
tEMBroABrcInsufficientSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - insufficient - alarm disappeared"
|
::= { notifications 293604337 }
|
|
tEMBroABrcInsufficientSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - insufficient - alarm reset"
|
::= { notifications 293604338 }
|
|
tEMBroBBrcInsufficientL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - insufficient - alarm activated"
|
::= { notifications 25168884 }
|
|
tEMBroBBrcInsufficientL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - insufficient - alarm disappeared"
|
::= { notifications 25168885 }
|
|
tEMBroBBrcInsufficientL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - insufficient - alarm reset"
|
::= { notifications 25168886 }
|
|
tEMBroBBrcInsufficientL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - insufficient - alarm activated"
|
::= { notifications 159386612 }
|
|
tEMBroBBrcInsufficientL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - insufficient - alarm disappeared"
|
::= { notifications 159386613 }
|
|
tEMBroBBrcInsufficientL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - insufficient - alarm reset"
|
::= { notifications 159386614 }
|
|
tEMBroBBrcInsufficientSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - insufficient - alarm activated"
|
::= { notifications 293604340 }
|
|
tEMBroBBrcInsufficientSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - insufficient - alarm disappeared"
|
::= { notifications 293604341 }
|
|
tEMBroBBrcInsufficientSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - insufficient - alarm reset"
|
::= { notifications 293604342 }
|
|
tEMBroABrcMissingOrDamagedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - missing or damaged - alarm activated"
|
::= { notifications 25168812 }
|
|
tEMBroABrcMissingOrDamagedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - missing or damaged - alarm disappeared"
|
::= { notifications 25168813 }
|
|
tEMBroABrcMissingOrDamagedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(A) - missing or damaged - alarm reset"
|
::= { notifications 25168814 }
|
|
tEMBroABrcMissingOrDamagedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - missing or damaged - alarm activated"
|
::= { notifications 159386540 }
|
|
tEMBroABrcMissingOrDamagedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - missing or damaged - alarm disappeared"
|
::= { notifications 159386541 }
|
|
tEMBroABrcMissingOrDamagedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(A) - missing or damaged - alarm reset"
|
::= { notifications 159386542 }
|
|
tEMBroABrcMissingOrDamagedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - missing or damaged - alarm activated"
|
::= { notifications 293604268 }
|
|
tEMBroABrcMissingOrDamagedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - missing or damaged - alarm disappeared"
|
::= { notifications 293604269 }
|
|
tEMBroABrcMissingOrDamagedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(A) - missing or damaged - alarm reset"
|
::= { notifications 293604270 }
|
|
tEMBroBBrcMissingOrDamagedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - missing or damaged - alarm activated"
|
::= { notifications 25168836 }
|
|
tEMBroBBrcMissingOrDamagedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - missing or damaged - alarm disappeared"
|
::= { notifications 25168837 }
|
|
tEMBroBBrcMissingOrDamagedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - EM(B) - missing or damaged - alarm reset"
|
::= { notifications 25168838 }
|
|
tEMBroBBrcMissingOrDamagedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - missing or damaged - alarm activated"
|
::= { notifications 159386564 }
|
|
tEMBroBBrcMissingOrDamagedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - missing or damaged - alarm disappeared"
|
::= { notifications 159386565 }
|
|
tEMBroBBrcMissingOrDamagedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - EM(B) - missing or damaged - alarm reset"
|
::= { notifications 159386566 }
|
|
tEMBroBBrcMissingOrDamagedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - missing or damaged - alarm activated"
|
::= { notifications 293604292 }
|
|
tEMBroBBrcMissingOrDamagedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - missing or damaged - alarm disappeared"
|
::= { notifications 293604293 }
|
|
tEMBroBBrcMissingOrDamagedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - EM(B) - missing or damaged - alarm reset"
|
::= { notifications 293604294 }
|
|
tEventEMail1FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 1 Fail - alarm activated"
|
::= { notifications 25168760 }
|
|
tEventEMail1FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 1 Fail - alarm disappeared"
|
::= { notifications 25168761 }
|
|
tEventEMail1FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 1 Fail - alarm reset"
|
::= { notifications 25168762 }
|
|
tEventEMail1FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 1 Fail - alarm activated"
|
::= { notifications 159386488 }
|
|
tEventEMail1FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 1 Fail - alarm disappeared"
|
::= { notifications 159386489 }
|
|
tEventEMail1FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 1 Fail - alarm reset"
|
::= { notifications 159386490 }
|
|
tEventEMail1FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 1 Fail - alarm activated"
|
::= { notifications 293604216 }
|
|
tEventEMail1FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 1 Fail - alarm disappeared"
|
::= { notifications 293604217 }
|
|
tEventEMail1FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 1 Fail - alarm reset"
|
::= { notifications 293604218 }
|
|
tEventEMail2FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 2 Fail - alarm activated"
|
::= { notifications 25168764 }
|
|
tEventEMail2FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 2 Fail - alarm disappeared"
|
::= { notifications 25168765 }
|
|
tEventEMail2FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 2 Fail - alarm reset"
|
::= { notifications 25168766 }
|
|
tEventEMail2FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 2 Fail - alarm activated"
|
::= { notifications 159386492 }
|
|
tEventEMail2FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 2 Fail - alarm disappeared"
|
::= { notifications 159386493 }
|
|
tEventEMail2FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 2 Fail - alarm reset"
|
::= { notifications 159386494 }
|
|
tEventEMail2FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 2 Fail - alarm activated"
|
::= { notifications 293604220 }
|
|
tEventEMail2FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 2 Fail - alarm disappeared"
|
::= { notifications 293604221 }
|
|
tEventEMail2FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 2 Fail - alarm reset"
|
::= { notifications 293604222 }
|
|
tEventEMail3FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 3 Fail - alarm activated"
|
::= { notifications 25168768 }
|
|
tEventEMail3FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 3 Fail - alarm disappeared"
|
::= { notifications 25168769 }
|
|
tEventEMail3FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 3 Fail - alarm reset"
|
::= { notifications 25168770 }
|
|
tEventEMail3FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 3 Fail - alarm activated"
|
::= { notifications 159386496 }
|
|
tEventEMail3FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 3 Fail - alarm disappeared"
|
::= { notifications 159386497 }
|
|
tEventEMail3FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 3 Fail - alarm reset"
|
::= { notifications 159386498 }
|
|
tEventEMail3FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 3 Fail - alarm activated"
|
::= { notifications 293604224 }
|
|
tEventEMail3FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 3 Fail - alarm disappeared"
|
::= { notifications 293604225 }
|
|
tEventEMail3FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 3 Fail - alarm reset"
|
::= { notifications 293604226 }
|
|
tEventEMail4FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 4 Fail - alarm activated"
|
::= { notifications 25168772 }
|
|
tEventEMail4FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 4 Fail - alarm disappeared"
|
::= { notifications 25168773 }
|
|
tEventEMail4FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event e-mail 4 Fail - alarm reset"
|
::= { notifications 25168774 }
|
|
tEventEMail4FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 4 Fail - alarm activated"
|
::= { notifications 159386500 }
|
|
tEventEMail4FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 4 Fail - alarm disappeared"
|
::= { notifications 159386501 }
|
|
tEventEMail4FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event e-mail 4 Fail - alarm reset"
|
::= { notifications 159386502 }
|
|
tEventEMail4FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 4 Fail - alarm activated"
|
::= { notifications 293604228 }
|
|
tEventEMail4FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 4 Fail - alarm disappeared"
|
::= { notifications 293604229 }
|
|
tEventEMail4FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event e-mail 4 Fail - alarm reset"
|
::= { notifications 293604230 }
|
|
tEventSMS1FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 1 Fail - alarm activated"
|
::= { notifications 25168776 }
|
|
tEventSMS1FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 1 Fail - alarm disappeared"
|
::= { notifications 25168777 }
|
|
tEventSMS1FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 1 Fail - alarm reset"
|
::= { notifications 25168778 }
|
|
tEventSMS1FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 1 Fail - alarm activated"
|
::= { notifications 159386504 }
|
|
tEventSMS1FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 1 Fail - alarm disappeared"
|
::= { notifications 159386505 }
|
|
tEventSMS1FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 1 Fail - alarm reset"
|
::= { notifications 159386506 }
|
|
tEventSMS1FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 1 Fail - alarm activated"
|
::= { notifications 293604232 }
|
|
tEventSMS1FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 1 Fail - alarm disappeared"
|
::= { notifications 293604233 }
|
|
tEventSMS1FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 1 Fail - alarm reset"
|
::= { notifications 293604234 }
|
|
tEventSMS2FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 2 Fail - alarm activated"
|
::= { notifications 25168780 }
|
|
tEventSMS2FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 2 Fail - alarm disappeared"
|
::= { notifications 25168781 }
|
|
tEventSMS2FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 2 Fail - alarm reset"
|
::= { notifications 25168782 }
|
|
tEventSMS2FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 2 Fail - alarm activated"
|
::= { notifications 159386508 }
|
|
tEventSMS2FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 2 Fail - alarm disappeared"
|
::= { notifications 159386509 }
|
|
tEventSMS2FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 2 Fail - alarm reset"
|
::= { notifications 159386510 }
|
|
tEventSMS2FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 2 Fail - alarm activated"
|
::= { notifications 293604236 }
|
|
tEventSMS2FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 2 Fail - alarm disappeared"
|
::= { notifications 293604237 }
|
|
tEventSMS2FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 2 Fail - alarm reset"
|
::= { notifications 293604238 }
|
|
tEventSMS3FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 3 Fail - alarm activated"
|
::= { notifications 25168784 }
|
|
tEventSMS3FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 3 Fail - alarm disappeared"
|
::= { notifications 25168785 }
|
|
tEventSMS3FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 3 Fail - alarm reset"
|
::= { notifications 25168786 }
|
|
tEventSMS3FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 3 Fail - alarm activated"
|
::= { notifications 159386512 }
|
|
tEventSMS3FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 3 Fail - alarm disappeared"
|
::= { notifications 159386513 }
|
|
tEventSMS3FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 3 Fail - alarm reset"
|
::= { notifications 159386514 }
|
|
tEventSMS3FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 3 Fail - alarm activated"
|
::= { notifications 293604240 }
|
|
tEventSMS3FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 3 Fail - alarm disappeared"
|
::= { notifications 293604241 }
|
|
tEventSMS3FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 3 Fail - alarm reset"
|
::= { notifications 293604242 }
|
|
tEventSMS4FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 4 Fail - alarm activated"
|
::= { notifications 25168788 }
|
|
tEventSMS4FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 4 Fail - alarm disappeared"
|
::= { notifications 25168789 }
|
|
tEventSMS4FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Event SMS 4 Fail - alarm reset"
|
::= { notifications 25168790 }
|
|
tEventSMS4FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 4 Fail - alarm activated"
|
::= { notifications 159386516 }
|
|
tEventSMS4FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 4 Fail - alarm disappeared"
|
::= { notifications 159386517 }
|
|
tEventSMS4FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Event SMS 4 Fail - alarm reset"
|
::= { notifications 159386518 }
|
|
tEventSMS4FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 4 Fail - alarm activated"
|
::= { notifications 293604244 }
|
|
tEventSMS4FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 4 Fail - alarm disappeared"
|
::= { notifications 293604245 }
|
|
tEventSMS4FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Event SMS 4 Fail - alarm reset"
|
::= { notifications 293604246 }
|
|
tAlarmEMail1FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 1 Fail - alarm activated"
|
::= { notifications 25169084 }
|
|
tAlarmEMail1FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 1 Fail - alarm disappeared"
|
::= { notifications 25169085 }
|
|
tAlarmEMail1FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 1 Fail - alarm reset"
|
::= { notifications 25169086 }
|
|
tAlarmEMail1FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 1 Fail - alarm activated"
|
::= { notifications 159386812 }
|
|
tAlarmEMail1FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 1 Fail - alarm disappeared"
|
::= { notifications 159386813 }
|
|
tAlarmEMail1FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 1 Fail - alarm reset"
|
::= { notifications 159386814 }
|
|
tAlarmEMail1FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 1 Fail - alarm activated"
|
::= { notifications 293604540 }
|
|
tAlarmEMail1FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 1 Fail - alarm disappeared"
|
::= { notifications 293604541 }
|
|
tAlarmEMail1FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 1 Fail - alarm reset"
|
::= { notifications 293604542 }
|
|
tAlarmEMail2FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 2 Fail - alarm activated"
|
::= { notifications 25169088 }
|
|
tAlarmEMail2FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 2 Fail - alarm disappeared"
|
::= { notifications 25169089 }
|
|
tAlarmEMail2FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 2 Fail - alarm reset"
|
::= { notifications 25169090 }
|
|
tAlarmEMail2FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 2 Fail - alarm activated"
|
::= { notifications 159386816 }
|
|
tAlarmEMail2FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 2 Fail - alarm disappeared"
|
::= { notifications 159386817 }
|
|
tAlarmEMail2FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 2 Fail - alarm reset"
|
::= { notifications 159386818 }
|
|
tAlarmEMail2FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 2 Fail - alarm activated"
|
::= { notifications 293604544 }
|
|
tAlarmEMail2FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 2 Fail - alarm disappeared"
|
::= { notifications 293604545 }
|
|
tAlarmEMail2FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 2 Fail - alarm reset"
|
::= { notifications 293604546 }
|
|
tAlarmEMail3FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 3 Fail - alarm activated"
|
::= { notifications 25169092 }
|
|
tAlarmEMail3FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 3 Fail - alarm disappeared"
|
::= { notifications 25169093 }
|
|
tAlarmEMail3FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 3 Fail - alarm reset"
|
::= { notifications 25169094 }
|
|
tAlarmEMail3FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 3 Fail - alarm activated"
|
::= { notifications 159386820 }
|
|
tAlarmEMail3FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 3 Fail - alarm disappeared"
|
::= { notifications 159386821 }
|
|
tAlarmEMail3FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 3 Fail - alarm reset"
|
::= { notifications 159386822 }
|
|
tAlarmEMail3FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 3 Fail - alarm activated"
|
::= { notifications 293604548 }
|
|
tAlarmEMail3FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 3 Fail - alarm disappeared"
|
::= { notifications 293604549 }
|
|
tAlarmEMail3FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 3 Fail - alarm reset"
|
::= { notifications 293604550 }
|
|
tAlarmEMail4FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 4 Fail - alarm activated"
|
::= { notifications 25169096 }
|
|
tAlarmEMail4FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 4 Fail - alarm disappeared"
|
::= { notifications 25169097 }
|
|
tAlarmEMail4FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm e-mail 4 Fail - alarm reset"
|
::= { notifications 25169098 }
|
|
tAlarmEMail4FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 4 Fail - alarm activated"
|
::= { notifications 159386824 }
|
|
tAlarmEMail4FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 4 Fail - alarm disappeared"
|
::= { notifications 159386825 }
|
|
tAlarmEMail4FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm e-mail 4 Fail - alarm reset"
|
::= { notifications 159386826 }
|
|
tAlarmEMail4FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 4 Fail - alarm activated"
|
::= { notifications 293604552 }
|
|
tAlarmEMail4FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 4 Fail - alarm disappeared"
|
::= { notifications 293604553 }
|
|
tAlarmEMail4FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm e-mail 4 Fail - alarm reset"
|
::= { notifications 293604554 }
|
|
tAlarmSMS1FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 1 Fail - alarm activated"
|
::= { notifications 25169100 }
|
|
tAlarmSMS1FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 1 Fail - alarm disappeared"
|
::= { notifications 25169101 }
|
|
tAlarmSMS1FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 1 Fail - alarm reset"
|
::= { notifications 25169102 }
|
|
tAlarmSMS1FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 1 Fail - alarm activated"
|
::= { notifications 159386828 }
|
|
tAlarmSMS1FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 1 Fail - alarm disappeared"
|
::= { notifications 159386829 }
|
|
tAlarmSMS1FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 1 Fail - alarm reset"
|
::= { notifications 159386830 }
|
|
tAlarmSMS1FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 1 Fail - alarm activated"
|
::= { notifications 293604556 }
|
|
tAlarmSMS1FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 1 Fail - alarm disappeared"
|
::= { notifications 293604557 }
|
|
tAlarmSMS1FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 1 Fail - alarm reset"
|
::= { notifications 293604558 }
|
|
tAlarmSMS2FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 2 Fail - alarm activated"
|
::= { notifications 25169104 }
|
|
tAlarmSMS2FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 2 Fail - alarm disappeared"
|
::= { notifications 25169105 }
|
|
tAlarmSMS2FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 2 Fail - alarm reset"
|
::= { notifications 25169106 }
|
|
tAlarmSMS2FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 2 Fail - alarm activated"
|
::= { notifications 159386832 }
|
|
tAlarmSMS2FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 2 Fail - alarm disappeared"
|
::= { notifications 159386833 }
|
|
tAlarmSMS2FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 2 Fail - alarm reset"
|
::= { notifications 159386834 }
|
|
tAlarmSMS2FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 2 Fail - alarm activated"
|
::= { notifications 293604560 }
|
|
tAlarmSMS2FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 2 Fail - alarm disappeared"
|
::= { notifications 293604561 }
|
|
tAlarmSMS2FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 2 Fail - alarm reset"
|
::= { notifications 293604562 }
|
|
tAlarmSMS3FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 3 Fail - alarm activated"
|
::= { notifications 25169108 }
|
|
tAlarmSMS3FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 3 Fail - alarm disappeared"
|
::= { notifications 25169109 }
|
|
tAlarmSMS3FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 3 Fail - alarm reset"
|
::= { notifications 25169110 }
|
|
tAlarmSMS3FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 3 Fail - alarm activated"
|
::= { notifications 159386836 }
|
|
tAlarmSMS3FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 3 Fail - alarm disappeared"
|
::= { notifications 159386837 }
|
|
tAlarmSMS3FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 3 Fail - alarm reset"
|
::= { notifications 159386838 }
|
|
tAlarmSMS3FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 3 Fail - alarm activated"
|
::= { notifications 293604564 }
|
|
tAlarmSMS3FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 3 Fail - alarm disappeared"
|
::= { notifications 293604565 }
|
|
tAlarmSMS3FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 3 Fail - alarm reset"
|
::= { notifications 293604566 }
|
|
tAlarmSMS4FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 4 Fail - alarm activated"
|
::= { notifications 25169112 }
|
|
tAlarmSMS4FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 4 Fail - alarm disappeared"
|
::= { notifications 25169113 }
|
|
tAlarmSMS4FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Alarm SMS 4 Fail - alarm reset"
|
::= { notifications 25169114 }
|
|
tAlarmSMS4FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 4 Fail - alarm activated"
|
::= { notifications 159386840 }
|
|
tAlarmSMS4FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 4 Fail - alarm disappeared"
|
::= { notifications 159386841 }
|
|
tAlarmSMS4FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Alarm SMS 4 Fail - alarm reset"
|
::= { notifications 159386842 }
|
|
tAlarmSMS4FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 4 Fail - alarm activated"
|
::= { notifications 293604568 }
|
|
tAlarmSMS4FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 4 Fail - alarm disappeared"
|
::= { notifications 293604569 }
|
|
tAlarmSMS4FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Alarm SMS 4 Fail - alarm reset"
|
::= { notifications 293604570 }
|
|
tSNMPTRAP1FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - SNMP TRAP 1 Fail - alarm activated"
|
::= { notifications 25169116 }
|
|
tSNMPTRAP1FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - SNMP TRAP 1 Fail - alarm disappeared"
|
::= { notifications 25169117 }
|
|
tSNMPTRAP1FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - SNMP TRAP 1 Fail - alarm reset"
|
::= { notifications 25169118 }
|
|
tSNMPTRAP1FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - SNMP TRAP 1 Fail - alarm activated"
|
::= { notifications 159386844 }
|
|
tSNMPTRAP1FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - SNMP TRAP 1 Fail - alarm disappeared"
|
::= { notifications 159386845 }
|
|
tSNMPTRAP1FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - SNMP TRAP 1 Fail - alarm reset"
|
::= { notifications 159386846 }
|
|
tSNMPTRAP1FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - SNMP TRAP 1 Fail - alarm activated"
|
::= { notifications 293604572 }
|
|
tSNMPTRAP1FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - SNMP TRAP 1 Fail - alarm disappeared"
|
::= { notifications 293604573 }
|
|
tSNMPTRAP1FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - SNMP TRAP 1 Fail - alarm reset"
|
::= { notifications 293604574 }
|
|
tSNMPTRAP2FailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - SNMP TRAP 2 Fail - alarm activated"
|
::= { notifications 25169120 }
|
|
tSNMPTRAP2FailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - SNMP TRAP 2 Fail - alarm disappeared"
|
::= { notifications 25169121 }
|
|
tSNMPTRAP2FailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - SNMP TRAP 2 Fail - alarm reset"
|
::= { notifications 25169122 }
|
|
tSNMPTRAP2FailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - SNMP TRAP 2 Fail - alarm activated"
|
::= { notifications 159386848 }
|
|
tSNMPTRAP2FailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - SNMP TRAP 2 Fail - alarm disappeared"
|
::= { notifications 159386849 }
|
|
tSNMPTRAP2FailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - SNMP TRAP 2 Fail - alarm reset"
|
::= { notifications 159386850 }
|
|
tSNMPTRAP2FailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - SNMP TRAP 2 Fail - alarm activated"
|
::= { notifications 293604576 }
|
|
tSNMPTRAP2FailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - SNMP TRAP 2 Fail - alarm disappeared"
|
::= { notifications 293604577 }
|
|
tSNMPTRAP2FailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - SNMP TRAP 2 Fail - alarm reset"
|
::= { notifications 293604578 }
|
|
tECUYellowLampL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Yellow Lamp - alarm activated"
|
::= { notifications 25168536 }
|
|
tECUYellowLampL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Yellow Lamp - alarm disappeared"
|
::= { notifications 25168537 }
|
|
tECUYellowLampL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Yellow Lamp - alarm reset"
|
::= { notifications 25168538 }
|
|
tECUYellowLampL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Yellow Lamp - alarm activated"
|
::= { notifications 159386264 }
|
|
tECUYellowLampL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Yellow Lamp - alarm disappeared"
|
::= { notifications 159386265 }
|
|
tECUYellowLampL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Yellow Lamp - alarm reset"
|
::= { notifications 159386266 }
|
|
tECUYellowLampSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Yellow Lamp - alarm activated"
|
::= { notifications 293603992 }
|
|
tECUYellowLampSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Yellow Lamp - alarm disappeared"
|
::= { notifications 293603993 }
|
|
tECUYellowLampSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Yellow Lamp - alarm reset"
|
::= { notifications 293603994 }
|
|
tECURedLampL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Red Lamp - alarm activated"
|
::= { notifications 25168540 }
|
|
tECURedLampL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Red Lamp - alarm disappeared"
|
::= { notifications 25168541 }
|
|
tECURedLampL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Red Lamp - alarm reset"
|
::= { notifications 25168542 }
|
|
tECURedLampL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Red Lamp - alarm activated"
|
::= { notifications 159386268 }
|
|
tECURedLampL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Red Lamp - alarm disappeared"
|
::= { notifications 159386269 }
|
|
tECURedLampL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Red Lamp - alarm reset"
|
::= { notifications 159386270 }
|
|
tECURedLampSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Red Lamp - alarm activated"
|
::= { notifications 293603996 }
|
|
tECURedLampSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Red Lamp - alarm disappeared"
|
::= { notifications 293603997 }
|
|
tECURedLampSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Red Lamp - alarm reset"
|
::= { notifications 293603998 }
|
|
tECUWaitToStartL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Wait To Start - alarm activated"
|
::= { notifications 25168544 }
|
|
tECUWaitToStartL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Wait To Start - alarm disappeared"
|
::= { notifications 25168545 }
|
|
tECUWaitToStartL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Wait To Start - alarm reset"
|
::= { notifications 25168546 }
|
|
tECUWaitToStartL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Wait To Start - alarm activated"
|
::= { notifications 159386272 }
|
|
tECUWaitToStartL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Wait To Start - alarm disappeared"
|
::= { notifications 159386273 }
|
|
tECUWaitToStartL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Wait To Start - alarm reset"
|
::= { notifications 159386274 }
|
|
tECUWaitToStartSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Wait To Start - alarm activated"
|
::= { notifications 293604000 }
|
|
tECUWaitToStartSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Wait To Start - alarm disappeared"
|
::= { notifications 293604001 }
|
|
tECUWaitToStartSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Wait To Start - alarm reset"
|
::= { notifications 293604002 }
|
|
tECUStateDash3L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_3 - alarm activated"
|
::= { notifications 25168796 }
|
|
tECUStateDash3L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_3 - alarm disappeared"
|
::= { notifications 25168797 }
|
|
tECUStateDash3L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_3 - alarm reset"
|
::= { notifications 25168798 }
|
|
tECUStateDash3L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_3 - alarm activated"
|
::= { notifications 159386524 }
|
|
tECUStateDash3L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_3 - alarm disappeared"
|
::= { notifications 159386525 }
|
|
tECUStateDash3L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_3 - alarm reset"
|
::= { notifications 159386526 }
|
|
tECUStateDash3SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_3 - alarm activated"
|
::= { notifications 293604252 }
|
|
tECUStateDash3SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_3 - alarm disappeared"
|
::= { notifications 293604253 }
|
|
tECUStateDash3SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_3 - alarm reset"
|
::= { notifications 293604254 }
|
|
tECUStateDash4L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_4 - alarm activated"
|
::= { notifications 25168800 }
|
|
tECUStateDash4L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_4 - alarm disappeared"
|
::= { notifications 25168801 }
|
|
tECUStateDash4L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_4 - alarm reset"
|
::= { notifications 25168802 }
|
|
tECUStateDash4L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_4 - alarm activated"
|
::= { notifications 159386528 }
|
|
tECUStateDash4L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_4 - alarm disappeared"
|
::= { notifications 159386529 }
|
|
tECUStateDash4L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_4 - alarm reset"
|
::= { notifications 159386530 }
|
|
tECUStateDash4SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_4 - alarm activated"
|
::= { notifications 293604256 }
|
|
tECUStateDash4SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_4 - alarm disappeared"
|
::= { notifications 293604257 }
|
|
tECUStateDash4SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_4 - alarm reset"
|
::= { notifications 293604258 }
|
|
tECUStateDash5L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_5 - alarm activated"
|
::= { notifications 25168804 }
|
|
tECUStateDash5L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_5 - alarm disappeared"
|
::= { notifications 25168805 }
|
|
tECUStateDash5L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_5 - alarm reset"
|
::= { notifications 25168806 }
|
|
tECUStateDash5L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_5 - alarm activated"
|
::= { notifications 159386532 }
|
|
tECUStateDash5L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_5 - alarm disappeared"
|
::= { notifications 159386533 }
|
|
tECUStateDash5L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_5 - alarm reset"
|
::= { notifications 159386534 }
|
|
tECUStateDash5SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_5 - alarm activated"
|
::= { notifications 293604260 }
|
|
tECUStateDash5SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_5 - alarm disappeared"
|
::= { notifications 293604261 }
|
|
tECUStateDash5SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_5 - alarm reset"
|
::= { notifications 293604262 }
|
|
tECUStateDash6L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_6 - alarm activated"
|
::= { notifications 25168808 }
|
|
tECUStateDash6L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_6 - alarm disappeared"
|
::= { notifications 25168809 }
|
|
tECUStateDash6L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_6 - alarm reset"
|
::= { notifications 25168810 }
|
|
tECUStateDash6L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_6 - alarm activated"
|
::= { notifications 159386536 }
|
|
tECUStateDash6L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_6 - alarm disappeared"
|
::= { notifications 159386537 }
|
|
tECUStateDash6L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_6 - alarm reset"
|
::= { notifications 159386538 }
|
|
tECUStateDash6SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_6 - alarm activated"
|
::= { notifications 293604264 }
|
|
tECUStateDash6SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_6 - alarm disappeared"
|
::= { notifications 293604265 }
|
|
tECUStateDash6SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_6 - alarm reset"
|
::= { notifications 293604266 }
|
|
tECUStateDash7L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_7 - alarm activated"
|
::= { notifications 25168792 }
|
|
tECUStateDash7L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_7 - alarm disappeared"
|
::= { notifications 25168793 }
|
|
tECUStateDash7L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU State_7 - alarm reset"
|
::= { notifications 25168794 }
|
|
tECUStateDash7L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_7 - alarm activated"
|
::= { notifications 159386520 }
|
|
tECUStateDash7L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_7 - alarm disappeared"
|
::= { notifications 159386521 }
|
|
tECUStateDash7L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU State_7 - alarm reset"
|
::= { notifications 159386522 }
|
|
tECUStateDash7SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_7 - alarm activated"
|
::= { notifications 293604248 }
|
|
tECUStateDash7SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_7 - alarm disappeared"
|
::= { notifications 293604249 }
|
|
tECUStateDash7SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU State_7 - alarm reset"
|
::= { notifications 293604250 }
|
|
tAfterTreatmentL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - After-Treatment - alarm activated"
|
::= { notifications 25168592 }
|
|
tAfterTreatmentL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - After-Treatment - alarm disappeared"
|
::= { notifications 25168593 }
|
|
tAfterTreatmentL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - After-Treatment - alarm reset"
|
::= { notifications 25168594 }
|
|
tAfterTreatmentL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - After-Treatment - alarm activated"
|
::= { notifications 159386320 }
|
|
tAfterTreatmentL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - After-Treatment - alarm disappeared"
|
::= { notifications 159386321 }
|
|
tAfterTreatmentL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - After-Treatment - alarm reset"
|
::= { notifications 159386322 }
|
|
tAfterTreatmentSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - After-Treatment - alarm activated"
|
::= { notifications 293604048 }
|
|
tAfterTreatmentSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - After-Treatment - alarm disappeared"
|
::= { notifications 293604049 }
|
|
tAfterTreatmentSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - After-Treatment - alarm reset"
|
::= { notifications 293604050 }
|
|
tEmergencyStopL1Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Emergency Stop - alarm activated"
|
::= { notifications 25166000 }
|
|
tEmergencyStopL1Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Emergency Stop - alarm disappeared"
|
::= { notifications 25166001 }
|
|
tEmergencyStopL1AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Emergency Stop - alarm reset"
|
::= { notifications 25166002 }
|
|
tEmergencyStopL2Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Emergency Stop - alarm activated"
|
::= { notifications 159383728 }
|
|
tEmergencyStopL2Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Emergency Stop - alarm disappeared"
|
::= { notifications 159383729 }
|
|
tEmergencyStopL2AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Emergency Stop - alarm reset"
|
::= { notifications 159383730 }
|
|
tEmergencyStopSFActivated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Emergency Stop - alarm activated"
|
::= { notifications 293601456 }
|
|
tEmergencyStopSFDisappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Emergency Stop - alarm disappeared"
|
::= { notifications 293601457 }
|
|
tEmergencyStopSFAlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Emergency Stop - alarm reset"
|
::= { notifications 293601458 }
|
|
tRPML1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - RPM - alarm activated"
|
::= { notifications 25166004 }
|
|
tRPML1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - RPM - alarm disappeared"
|
::= { notifications 25166005 }
|
|
tRPML1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - RPM - alarm reset"
|
::= { notifications 25166006 }
|
|
tRPML2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - RPM - alarm activated"
|
::= { notifications 159383732 }
|
|
tRPML2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - RPM - alarm disappeared"
|
::= { notifications 159383733 }
|
|
tRPML2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - RPM - alarm reset"
|
::= { notifications 159383734 }
|
|
tRPMSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - RPM - alarm activated"
|
::= { notifications 293601460 }
|
|
tRPMSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - RPM - alarm disappeared"
|
::= { notifications 293601461 }
|
|
tRPMSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - RPM - alarm reset"
|
::= { notifications 293601462 }
|
|
tWrnChargingAlternatorFailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Charging Alternator Fail - alarm activated"
|
::= { notifications 25166012 }
|
|
tWrnChargingAlternatorFailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Charging Alternator Fail - alarm disappeared"
|
::= { notifications 25166013 }
|
|
tWrnChargingAlternatorFailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Charging Alternator Fail - alarm reset"
|
::= { notifications 25166014 }
|
|
tWrnChargingAlternatorFailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Charging Alternator Fail - alarm activated"
|
::= { notifications 159383740 }
|
|
tWrnChargingAlternatorFailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Charging Alternator Fail - alarm disappeared"
|
::= { notifications 159383741 }
|
|
tWrnChargingAlternatorFailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Charging Alternator Fail - alarm reset"
|
::= { notifications 159383742 }
|
|
tWrnChargingAlternatorFailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Charging Alternator Fail - alarm activated"
|
::= { notifications 293601468 }
|
|
tWrnChargingAlternatorFailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Charging Alternator Fail - alarm disappeared"
|
::= { notifications 293601469 }
|
|
tWrnChargingAlternatorFailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Charging Alternator Fail - alarm reset"
|
::= { notifications 293601470 }
|
|
tWrnStopFailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Stop fail - alarm activated"
|
::= { notifications 25166016 }
|
|
tWrnStopFailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Stop fail - alarm disappeared"
|
::= { notifications 25166017 }
|
|
tWrnStopFailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Stop fail - alarm reset"
|
::= { notifications 25166018 }
|
|
tWrnStopFailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Stop fail - alarm activated"
|
::= { notifications 159383744 }
|
|
tWrnStopFailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Stop fail - alarm disappeared"
|
::= { notifications 159383745 }
|
|
tWrnStopFailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Stop fail - alarm reset"
|
::= { notifications 159383746 }
|
|
tWrnStopFailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Stop fail - alarm activated"
|
::= { notifications 293601472 }
|
|
tWrnStopFailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Stop fail - alarm disappeared"
|
::= { notifications 293601473 }
|
|
tWrnStopFailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Stop fail - alarm reset"
|
::= { notifications 293601474 }
|
|
tSdOverspeedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Overspeed - alarm activated"
|
::= { notifications 25166020 }
|
|
tSdOverspeedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Overspeed - alarm disappeared"
|
::= { notifications 25166021 }
|
|
tSdOverspeedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Overspeed - alarm reset"
|
::= { notifications 25166022 }
|
|
tSdOverspeedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Overspeed - alarm activated"
|
::= { notifications 159383748 }
|
|
tSdOverspeedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Overspeed - alarm disappeared"
|
::= { notifications 159383749 }
|
|
tSdOverspeedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Overspeed - alarm reset"
|
::= { notifications 159383750 }
|
|
tSdOverspeedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Overspeed - alarm activated"
|
::= { notifications 293601476 }
|
|
tSdOverspeedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Overspeed - alarm disappeared"
|
::= { notifications 293601477 }
|
|
tSdOverspeedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Overspeed - alarm reset"
|
::= { notifications 293601478 }
|
|
tSdUnderspeedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Underspeed - alarm activated"
|
::= { notifications 25166024 }
|
|
tSdUnderspeedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Underspeed - alarm disappeared"
|
::= { notifications 25166025 }
|
|
tSdUnderspeedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Underspeed - alarm reset"
|
::= { notifications 25166026 }
|
|
tSdUnderspeedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Underspeed - alarm activated"
|
::= { notifications 159383752 }
|
|
tSdUnderspeedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Underspeed - alarm disappeared"
|
::= { notifications 159383753 }
|
|
tSdUnderspeedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Underspeed - alarm reset"
|
::= { notifications 159383754 }
|
|
tSdUnderspeedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Underspeed - alarm activated"
|
::= { notifications 293601480 }
|
|
tSdUnderspeedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Underspeed - alarm disappeared"
|
::= { notifications 293601481 }
|
|
tSdUnderspeedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Underspeed - alarm reset"
|
::= { notifications 293601482 }
|
|
tSdRPMMeasurementFailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd RPM Measurement Fail - alarm activated"
|
::= { notifications 25166028 }
|
|
tSdRPMMeasurementFailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd RPM Measurement Fail - alarm disappeared"
|
::= { notifications 25166029 }
|
|
tSdRPMMeasurementFailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd RPM Measurement Fail - alarm reset"
|
::= { notifications 25166030 }
|
|
tSdRPMMeasurementFailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd RPM Measurement Fail - alarm activated"
|
::= { notifications 159383756 }
|
|
tSdRPMMeasurementFailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd RPM Measurement Fail - alarm disappeared"
|
::= { notifications 159383757 }
|
|
tSdRPMMeasurementFailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd RPM Measurement Fail - alarm reset"
|
::= { notifications 159383758 }
|
|
tSdRPMMeasurementFailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd RPM Measurement Fail - alarm activated"
|
::= { notifications 293601484 }
|
|
tSdRPMMeasurementFailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd RPM Measurement Fail - alarm disappeared"
|
::= { notifications 293601485 }
|
|
tSdRPMMeasurementFailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd RPM Measurement Fail - alarm reset"
|
::= { notifications 293601486 }
|
|
tSdBatteryFlatL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Battery Flat - alarm activated"
|
::= { notifications 25166032 }
|
|
tSdBatteryFlatL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Battery Flat - alarm disappeared"
|
::= { notifications 25166033 }
|
|
tSdBatteryFlatL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Battery Flat - alarm reset"
|
::= { notifications 25166034 }
|
|
tSdBatteryFlatL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Battery Flat - alarm activated"
|
::= { notifications 159383760 }
|
|
tSdBatteryFlatL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Battery Flat - alarm disappeared"
|
::= { notifications 159383761 }
|
|
tSdBatteryFlatL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Battery Flat - alarm reset"
|
::= { notifications 159383762 }
|
|
tSdBatteryFlatSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Battery Flat - alarm activated"
|
::= { notifications 293601488 }
|
|
tSdBatteryFlatSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Battery Flat - alarm disappeared"
|
::= { notifications 293601489 }
|
|
tSdBatteryFlatSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Battery Flat - alarm reset"
|
::= { notifications 293601490 }
|
|
tWrnMaintenance1L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Maintenance 1 - alarm activated"
|
::= { notifications 25168164 }
|
|
tWrnMaintenance1L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Maintenance 1 - alarm disappeared"
|
::= { notifications 25168165 }
|
|
tWrnMaintenance1L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Maintenance 1 - alarm reset"
|
::= { notifications 25168166 }
|
|
tWrnMaintenance1L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Maintenance 1 - alarm activated"
|
::= { notifications 159385892 }
|
|
tWrnMaintenance1L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Maintenance 1 - alarm disappeared"
|
::= { notifications 159385893 }
|
|
tWrnMaintenance1L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Maintenance 1 - alarm reset"
|
::= { notifications 159385894 }
|
|
tWrnMaintenance1SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Maintenance 1 - alarm activated"
|
::= { notifications 293603620 }
|
|
tWrnMaintenance1SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Maintenance 1 - alarm disappeared"
|
::= { notifications 293603621 }
|
|
tWrnMaintenance1SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Maintenance 1 - alarm reset"
|
::= { notifications 293603622 }
|
|
tWrnMaintenance2L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Maintenance 2 - alarm activated"
|
::= { notifications 25168168 }
|
|
tWrnMaintenance2L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Maintenance 2 - alarm disappeared"
|
::= { notifications 25168169 }
|
|
tWrnMaintenance2L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Maintenance 2 - alarm reset"
|
::= { notifications 25168170 }
|
|
tWrnMaintenance2L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Maintenance 2 - alarm activated"
|
::= { notifications 159385896 }
|
|
tWrnMaintenance2L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Maintenance 2 - alarm disappeared"
|
::= { notifications 159385897 }
|
|
tWrnMaintenance2L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Maintenance 2 - alarm reset"
|
::= { notifications 159385898 }
|
|
tWrnMaintenance2SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Maintenance 2 - alarm activated"
|
::= { notifications 293603624 }
|
|
tWrnMaintenance2SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Maintenance 2 - alarm disappeared"
|
::= { notifications 293603625 }
|
|
tWrnMaintenance2SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Maintenance 2 - alarm reset"
|
::= { notifications 293603626 }
|
|
tWrnMaintenance3L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Maintenance 3 - alarm activated"
|
::= { notifications 25168172 }
|
|
tWrnMaintenance3L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Maintenance 3 - alarm disappeared"
|
::= { notifications 25168173 }
|
|
tWrnMaintenance3L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Maintenance 3 - alarm reset"
|
::= { notifications 25168174 }
|
|
tWrnMaintenance3L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Maintenance 3 - alarm activated"
|
::= { notifications 159385900 }
|
|
tWrnMaintenance3L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Maintenance 3 - alarm disappeared"
|
::= { notifications 159385901 }
|
|
tWrnMaintenance3L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Maintenance 3 - alarm reset"
|
::= { notifications 159385902 }
|
|
tWrnMaintenance3SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Maintenance 3 - alarm activated"
|
::= { notifications 293603628 }
|
|
tWrnMaintenance3SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Maintenance 3 - alarm disappeared"
|
::= { notifications 293603629 }
|
|
tWrnMaintenance3SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Maintenance 3 - alarm reset"
|
::= { notifications 293603630 }
|
|
tSdStartFailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Start Fail - alarm activated"
|
::= { notifications 25166044 }
|
|
tSdStartFailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Start Fail - alarm disappeared"
|
::= { notifications 25166045 }
|
|
tSdStartFailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Start Fail - alarm reset"
|
::= { notifications 25166046 }
|
|
tSdStartFailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Start Fail - alarm activated"
|
::= { notifications 159383772 }
|
|
tSdStartFailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Start Fail - alarm disappeared"
|
::= { notifications 159383773 }
|
|
tSdStartFailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Start Fail - alarm reset"
|
::= { notifications 159383774 }
|
|
tSdStartFailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Start Fail - alarm activated"
|
::= { notifications 293601500 }
|
|
tSdStartFailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Start Fail - alarm disappeared"
|
::= { notifications 293601501 }
|
|
tSdStartFailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Start Fail - alarm reset"
|
::= { notifications 293601502 }
|
|
tWrnMCBFailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn MCB Fail - alarm activated"
|
::= { notifications 25166184 }
|
|
tWrnMCBFailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn MCB Fail - alarm disappeared"
|
::= { notifications 25166185 }
|
|
tWrnMCBFailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn MCB Fail - alarm reset"
|
::= { notifications 25166186 }
|
|
tWrnMCBFailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn MCB Fail - alarm activated"
|
::= { notifications 159383912 }
|
|
tWrnMCBFailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn MCB Fail - alarm disappeared"
|
::= { notifications 159383913 }
|
|
tWrnMCBFailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn MCB Fail - alarm reset"
|
::= { notifications 159383914 }
|
|
tWrnMCBFailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn MCB Fail - alarm activated"
|
::= { notifications 293601640 }
|
|
tWrnMCBFailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn MCB Fail - alarm disappeared"
|
::= { notifications 293601641 }
|
|
tWrnMCBFailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn MCB Fail - alarm reset"
|
::= { notifications 293601642 }
|
|
tSdGCBFailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd GCB Fail - alarm activated"
|
::= { notifications 25166188 }
|
|
tSdGCBFailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd GCB Fail - alarm disappeared"
|
::= { notifications 25166189 }
|
|
tSdGCBFailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd GCB Fail - alarm reset"
|
::= { notifications 25166190 }
|
|
tSdGCBFailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd GCB Fail - alarm activated"
|
::= { notifications 159383916 }
|
|
tSdGCBFailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd GCB Fail - alarm disappeared"
|
::= { notifications 159383917 }
|
|
tSdGCBFailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd GCB Fail - alarm reset"
|
::= { notifications 159383918 }
|
|
tSdGCBFailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd GCB Fail - alarm activated"
|
::= { notifications 293601644 }
|
|
tSdGCBFailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd GCB Fail - alarm disappeared"
|
::= { notifications 293601645 }
|
|
tSdGCBFailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd GCB Fail - alarm reset"
|
::= { notifications 293601646 }
|
|
tGeneratorVoltageL1NL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L1-N - alarm activated"
|
::= { notifications 25166276 }
|
|
tGeneratorVoltageL1NL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L1-N - alarm disappeared"
|
::= { notifications 25166277 }
|
|
tGeneratorVoltageL1NL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L1-N - alarm reset"
|
::= { notifications 25166278 }
|
|
tGeneratorVoltageL1NL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L1-N - alarm activated"
|
::= { notifications 159384004 }
|
|
tGeneratorVoltageL1NL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L1-N - alarm disappeared"
|
::= { notifications 159384005 }
|
|
tGeneratorVoltageL1NL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L1-N - alarm reset"
|
::= { notifications 159384006 }
|
|
tGeneratorVoltageL1NSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L1-N - alarm activated"
|
::= { notifications 293601732 }
|
|
tGeneratorVoltageL1NSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L1-N - alarm disappeared"
|
::= { notifications 293601733 }
|
|
tGeneratorVoltageL1NSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L1-N - alarm reset"
|
::= { notifications 293601734 }
|
|
tGeneratorVoltageL2NL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L2-N - alarm activated"
|
::= { notifications 25166280 }
|
|
tGeneratorVoltageL2NL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L2-N - alarm disappeared"
|
::= { notifications 25166281 }
|
|
tGeneratorVoltageL2NL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L2-N - alarm reset"
|
::= { notifications 25166282 }
|
|
tGeneratorVoltageL2NL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L2-N - alarm activated"
|
::= { notifications 159384008 }
|
|
tGeneratorVoltageL2NL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L2-N - alarm disappeared"
|
::= { notifications 159384009 }
|
|
tGeneratorVoltageL2NL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L2-N - alarm reset"
|
::= { notifications 159384010 }
|
|
tGeneratorVoltageL2NSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L2-N - alarm activated"
|
::= { notifications 293601736 }
|
|
tGeneratorVoltageL2NSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L2-N - alarm disappeared"
|
::= { notifications 293601737 }
|
|
tGeneratorVoltageL2NSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L2-N - alarm reset"
|
::= { notifications 293601738 }
|
|
tGeneratorVoltageL3NL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L3-N - alarm activated"
|
::= { notifications 25166284 }
|
|
tGeneratorVoltageL3NL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L3-N - alarm disappeared"
|
::= { notifications 25166285 }
|
|
tGeneratorVoltageL3NL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L3-N - alarm reset"
|
::= { notifications 25166286 }
|
|
tGeneratorVoltageL3NL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L3-N - alarm activated"
|
::= { notifications 159384012 }
|
|
tGeneratorVoltageL3NL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L3-N - alarm disappeared"
|
::= { notifications 159384013 }
|
|
tGeneratorVoltageL3NL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L3-N - alarm reset"
|
::= { notifications 159384014 }
|
|
tGeneratorVoltageL3NSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L3-N - alarm activated"
|
::= { notifications 293601740 }
|
|
tGeneratorVoltageL3NSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L3-N - alarm disappeared"
|
::= { notifications 293601741 }
|
|
tGeneratorVoltageL3NSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L3-N - alarm reset"
|
::= { notifications 293601742 }
|
|
tGeneratorVoltageL1L2L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L1-L2 - alarm activated"
|
::= { notifications 25166288 }
|
|
tGeneratorVoltageL1L2L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L1-L2 - alarm disappeared"
|
::= { notifications 25166289 }
|
|
tGeneratorVoltageL1L2L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L1-L2 - alarm reset"
|
::= { notifications 25166290 }
|
|
tGeneratorVoltageL1L2L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L1-L2 - alarm activated"
|
::= { notifications 159384016 }
|
|
tGeneratorVoltageL1L2L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L1-L2 - alarm disappeared"
|
::= { notifications 159384017 }
|
|
tGeneratorVoltageL1L2L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L1-L2 - alarm reset"
|
::= { notifications 159384018 }
|
|
tGeneratorVoltageL1L2SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L1-L2 - alarm activated"
|
::= { notifications 293601744 }
|
|
tGeneratorVoltageL1L2SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L1-L2 - alarm disappeared"
|
::= { notifications 293601745 }
|
|
tGeneratorVoltageL1L2SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L1-L2 - alarm reset"
|
::= { notifications 293601746 }
|
|
tGeneratorVoltageL2L3L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L2-L3 - alarm activated"
|
::= { notifications 25166292 }
|
|
tGeneratorVoltageL2L3L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L2-L3 - alarm disappeared"
|
::= { notifications 25166293 }
|
|
tGeneratorVoltageL2L3L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L2-L3 - alarm reset"
|
::= { notifications 25166294 }
|
|
tGeneratorVoltageL2L3L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L2-L3 - alarm activated"
|
::= { notifications 159384020 }
|
|
tGeneratorVoltageL2L3L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L2-L3 - alarm disappeared"
|
::= { notifications 159384021 }
|
|
tGeneratorVoltageL2L3L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L2-L3 - alarm reset"
|
::= { notifications 159384022 }
|
|
tGeneratorVoltageL2L3SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L2-L3 - alarm activated"
|
::= { notifications 293601748 }
|
|
tGeneratorVoltageL2L3SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L2-L3 - alarm disappeared"
|
::= { notifications 293601749 }
|
|
tGeneratorVoltageL2L3SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L2-L3 - alarm reset"
|
::= { notifications 293601750 }
|
|
tGeneratorVoltageL3L1L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L3-L1 - alarm activated"
|
::= { notifications 25166296 }
|
|
tGeneratorVoltageL3L1L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L3-L1 - alarm disappeared"
|
::= { notifications 25166297 }
|
|
tGeneratorVoltageL3L1L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Voltage L3-L1 - alarm reset"
|
::= { notifications 25166298 }
|
|
tGeneratorVoltageL3L1L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L3-L1 - alarm activated"
|
::= { notifications 159384024 }
|
|
tGeneratorVoltageL3L1L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L3-L1 - alarm disappeared"
|
::= { notifications 159384025 }
|
|
tGeneratorVoltageL3L1L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Voltage L3-L1 - alarm reset"
|
::= { notifications 159384026 }
|
|
tGeneratorVoltageL3L1SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L3-L1 - alarm activated"
|
::= { notifications 293601752 }
|
|
tGeneratorVoltageL3L1SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L3-L1 - alarm disappeared"
|
::= { notifications 293601753 }
|
|
tGeneratorVoltageL3L1SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Voltage L3-L1 - alarm reset"
|
::= { notifications 293601754 }
|
|
tBOCGenVoltageUnbalancePhPhL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Gen Voltage Unbalance ph-ph - alarm activated"
|
::= { notifications 25168176 }
|
|
tBOCGenVoltageUnbalancePhPhL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Gen Voltage Unbalance ph-ph - alarm disappeared"
|
::= { notifications 25168177 }
|
|
tBOCGenVoltageUnbalancePhPhL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Gen Voltage Unbalance ph-ph - alarm reset"
|
::= { notifications 25168178 }
|
|
tBOCGenVoltageUnbalancePhPhL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Gen Voltage Unbalance ph-ph - alarm activated"
|
::= { notifications 159385904 }
|
|
tBOCGenVoltageUnbalancePhPhL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Gen Voltage Unbalance ph-ph - alarm disappeared"
|
::= { notifications 159385905 }
|
|
tBOCGenVoltageUnbalancePhPhL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Gen Voltage Unbalance ph-ph - alarm reset"
|
::= { notifications 159385906 }
|
|
tBOCGenVoltageUnbalancePhPhSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Gen Voltage Unbalance ph-ph - alarm activated"
|
::= { notifications 293603632 }
|
|
tBOCGenVoltageUnbalancePhPhSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Gen Voltage Unbalance ph-ph - alarm disappeared"
|
::= { notifications 293603633 }
|
|
tBOCGenVoltageUnbalancePhPhSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Gen Voltage Unbalance ph-ph - alarm reset"
|
::= { notifications 293603634 }
|
|
tBOCGenVoltageUnbalancePhNL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Gen Voltage Unbalance ph-n - alarm activated"
|
::= { notifications 25168180 }
|
|
tBOCGenVoltageUnbalancePhNL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Gen Voltage Unbalance ph-n - alarm disappeared"
|
::= { notifications 25168181 }
|
|
tBOCGenVoltageUnbalancePhNL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Gen Voltage Unbalance ph-n - alarm reset"
|
::= { notifications 25168182 }
|
|
tBOCGenVoltageUnbalancePhNL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Gen Voltage Unbalance ph-n - alarm activated"
|
::= { notifications 159385908 }
|
|
tBOCGenVoltageUnbalancePhNL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Gen Voltage Unbalance ph-n - alarm disappeared"
|
::= { notifications 159385909 }
|
|
tBOCGenVoltageUnbalancePhNL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Gen Voltage Unbalance ph-n - alarm reset"
|
::= { notifications 159385910 }
|
|
tBOCGenVoltageUnbalancePhNSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Gen Voltage Unbalance ph-n - alarm activated"
|
::= { notifications 293603636 }
|
|
tBOCGenVoltageUnbalancePhNSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Gen Voltage Unbalance ph-n - alarm disappeared"
|
::= { notifications 293603637 }
|
|
tBOCGenVoltageUnbalancePhNSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Gen Voltage Unbalance ph-n - alarm reset"
|
::= { notifications 293603638 }
|
|
tGeneratorFrequencyL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Frequency - alarm activated"
|
::= { notifications 25166300 }
|
|
tGeneratorFrequencyL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Frequency - alarm disappeared"
|
::= { notifications 25166301 }
|
|
tGeneratorFrequencyL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator Frequency - alarm reset"
|
::= { notifications 25166302 }
|
|
tGeneratorFrequencyL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Frequency - alarm activated"
|
::= { notifications 159384028 }
|
|
tGeneratorFrequencyL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Frequency - alarm disappeared"
|
::= { notifications 159384029 }
|
|
tGeneratorFrequencyL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator Frequency - alarm reset"
|
::= { notifications 159384030 }
|
|
tGeneratorFrequencySFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Frequency - alarm activated"
|
::= { notifications 293601756 }
|
|
tGeneratorFrequencySFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Frequency - alarm disappeared"
|
::= { notifications 293601757 }
|
|
tGeneratorFrequencySFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator Frequency - alarm reset"
|
::= { notifications 293601758 }
|
|
tMainsVoltageL1NL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L1-N - alarm activated"
|
::= { notifications 25166368 }
|
|
tMainsVoltageL1NL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L1-N - alarm disappeared"
|
::= { notifications 25166369 }
|
|
tMainsVoltageL1NL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L1-N - alarm reset"
|
::= { notifications 25166370 }
|
|
tMainsVoltageL1NL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L1-N - alarm activated"
|
::= { notifications 159384096 }
|
|
tMainsVoltageL1NL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L1-N - alarm disappeared"
|
::= { notifications 159384097 }
|
|
tMainsVoltageL1NL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L1-N - alarm reset"
|
::= { notifications 159384098 }
|
|
tMainsVoltageL1NSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L1-N - alarm activated"
|
::= { notifications 293601824 }
|
|
tMainsVoltageL1NSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L1-N - alarm disappeared"
|
::= { notifications 293601825 }
|
|
tMainsVoltageL1NSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L1-N - alarm reset"
|
::= { notifications 293601826 }
|
|
tMainsVoltageL2NL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L2-N - alarm activated"
|
::= { notifications 25166372 }
|
|
tMainsVoltageL2NL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L2-N - alarm disappeared"
|
::= { notifications 25166373 }
|
|
tMainsVoltageL2NL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L2-N - alarm reset"
|
::= { notifications 25166374 }
|
|
tMainsVoltageL2NL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L2-N - alarm activated"
|
::= { notifications 159384100 }
|
|
tMainsVoltageL2NL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L2-N - alarm disappeared"
|
::= { notifications 159384101 }
|
|
tMainsVoltageL2NL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L2-N - alarm reset"
|
::= { notifications 159384102 }
|
|
tMainsVoltageL2NSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L2-N - alarm activated"
|
::= { notifications 293601828 }
|
|
tMainsVoltageL2NSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L2-N - alarm disappeared"
|
::= { notifications 293601829 }
|
|
tMainsVoltageL2NSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L2-N - alarm reset"
|
::= { notifications 293601830 }
|
|
tMainsVoltageL3NL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L3-N - alarm activated"
|
::= { notifications 25166376 }
|
|
tMainsVoltageL3NL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L3-N - alarm disappeared"
|
::= { notifications 25166377 }
|
|
tMainsVoltageL3NL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L3-N - alarm reset"
|
::= { notifications 25166378 }
|
|
tMainsVoltageL3NL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L3-N - alarm activated"
|
::= { notifications 159384104 }
|
|
tMainsVoltageL3NL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L3-N - alarm disappeared"
|
::= { notifications 159384105 }
|
|
tMainsVoltageL3NL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L3-N - alarm reset"
|
::= { notifications 159384106 }
|
|
tMainsVoltageL3NSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L3-N - alarm activated"
|
::= { notifications 293601832 }
|
|
tMainsVoltageL3NSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L3-N - alarm disappeared"
|
::= { notifications 293601833 }
|
|
tMainsVoltageL3NSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L3-N - alarm reset"
|
::= { notifications 293601834 }
|
|
tMainsVoltageL1L2L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L1-L2 - alarm activated"
|
::= { notifications 25166380 }
|
|
tMainsVoltageL1L2L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L1-L2 - alarm disappeared"
|
::= { notifications 25166381 }
|
|
tMainsVoltageL1L2L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L1-L2 - alarm reset"
|
::= { notifications 25166382 }
|
|
tMainsVoltageL1L2L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L1-L2 - alarm activated"
|
::= { notifications 159384108 }
|
|
tMainsVoltageL1L2L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L1-L2 - alarm disappeared"
|
::= { notifications 159384109 }
|
|
tMainsVoltageL1L2L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L1-L2 - alarm reset"
|
::= { notifications 159384110 }
|
|
tMainsVoltageL1L2SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L1-L2 - alarm activated"
|
::= { notifications 293601836 }
|
|
tMainsVoltageL1L2SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L1-L2 - alarm disappeared"
|
::= { notifications 293601837 }
|
|
tMainsVoltageL1L2SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L1-L2 - alarm reset"
|
::= { notifications 293601838 }
|
|
tMainsVoltageL2L3L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L2-L3 - alarm activated"
|
::= { notifications 25166384 }
|
|
tMainsVoltageL2L3L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L2-L3 - alarm disappeared"
|
::= { notifications 25166385 }
|
|
tMainsVoltageL2L3L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L2-L3 - alarm reset"
|
::= { notifications 25166386 }
|
|
tMainsVoltageL2L3L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L2-L3 - alarm activated"
|
::= { notifications 159384112 }
|
|
tMainsVoltageL2L3L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L2-L3 - alarm disappeared"
|
::= { notifications 159384113 }
|
|
tMainsVoltageL2L3L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L2-L3 - alarm reset"
|
::= { notifications 159384114 }
|
|
tMainsVoltageL2L3SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L2-L3 - alarm activated"
|
::= { notifications 293601840 }
|
|
tMainsVoltageL2L3SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L2-L3 - alarm disappeared"
|
::= { notifications 293601841 }
|
|
tMainsVoltageL2L3SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L2-L3 - alarm reset"
|
::= { notifications 293601842 }
|
|
tMainsVoltageL3L1L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L3-L1 - alarm activated"
|
::= { notifications 25166388 }
|
|
tMainsVoltageL3L1L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L3-L1 - alarm disappeared"
|
::= { notifications 25166389 }
|
|
tMainsVoltageL3L1L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage L3-L1 - alarm reset"
|
::= { notifications 25166390 }
|
|
tMainsVoltageL3L1L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L3-L1 - alarm activated"
|
::= { notifications 159384116 }
|
|
tMainsVoltageL3L1L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L3-L1 - alarm disappeared"
|
::= { notifications 159384117 }
|
|
tMainsVoltageL3L1L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage L3-L1 - alarm reset"
|
::= { notifications 159384118 }
|
|
tMainsVoltageL3L1SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L3-L1 - alarm activated"
|
::= { notifications 293601844 }
|
|
tMainsVoltageL3L1SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L3-L1 - alarm disappeared"
|
::= { notifications 293601845 }
|
|
tMainsVoltageL3L1SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage L3-L1 - alarm reset"
|
::= { notifications 293601846 }
|
|
tMainsFrequencyL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Frequency - alarm activated"
|
::= { notifications 25166392 }
|
|
tMainsFrequencyL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Frequency - alarm disappeared"
|
::= { notifications 25166393 }
|
|
tMainsFrequencyL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Frequency - alarm reset"
|
::= { notifications 25166394 }
|
|
tMainsFrequencyL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Frequency - alarm activated"
|
::= { notifications 159384120 }
|
|
tMainsFrequencyL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Frequency - alarm disappeared"
|
::= { notifications 159384121 }
|
|
tMainsFrequencyL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Frequency - alarm reset"
|
::= { notifications 159384122 }
|
|
tMainsFrequencySFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Frequency - alarm activated"
|
::= { notifications 293601848 }
|
|
tMainsFrequencySFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Frequency - alarm disappeared"
|
::= { notifications 293601849 }
|
|
tMainsFrequencySFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Frequency - alarm reset"
|
::= { notifications 293601850 }
|
|
tMainsL1GtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L1 >V - alarm activated"
|
::= { notifications 25166324 }
|
|
tMainsL1GtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L1 >V - alarm disappeared"
|
::= { notifications 25166325 }
|
|
tMainsL1GtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L1 >V - alarm reset"
|
::= { notifications 25166326 }
|
|
tMainsL1GtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L1 >V - alarm activated"
|
::= { notifications 159384052 }
|
|
tMainsL1GtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L1 >V - alarm disappeared"
|
::= { notifications 159384053 }
|
|
tMainsL1GtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L1 >V - alarm reset"
|
::= { notifications 159384054 }
|
|
tMainsL1GtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L1 >V - alarm activated"
|
::= { notifications 293601780 }
|
|
tMainsL1GtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L1 >V - alarm disappeared"
|
::= { notifications 293601781 }
|
|
tMainsL1GtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L1 >V - alarm reset"
|
::= { notifications 293601782 }
|
|
tMainsL1LtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L1 <V - alarm activated"
|
::= { notifications 25166312 }
|
|
tMainsL1LtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L1 <V - alarm disappeared"
|
::= { notifications 25166313 }
|
|
tMainsL1LtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L1 <V - alarm reset"
|
::= { notifications 25166314 }
|
|
tMainsL1LtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L1 <V - alarm activated"
|
::= { notifications 159384040 }
|
|
tMainsL1LtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L1 <V - alarm disappeared"
|
::= { notifications 159384041 }
|
|
tMainsL1LtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L1 <V - alarm reset"
|
::= { notifications 159384042 }
|
|
tMainsL1LtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L1 <V - alarm activated"
|
::= { notifications 293601768 }
|
|
tMainsL1LtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L1 <V - alarm disappeared"
|
::= { notifications 293601769 }
|
|
tMainsL1LtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L1 <V - alarm reset"
|
::= { notifications 293601770 }
|
|
tMainsL2GtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L2 >V - alarm activated"
|
::= { notifications 25166328 }
|
|
tMainsL2GtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L2 >V - alarm disappeared"
|
::= { notifications 25166329 }
|
|
tMainsL2GtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L2 >V - alarm reset"
|
::= { notifications 25166330 }
|
|
tMainsL2GtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L2 >V - alarm activated"
|
::= { notifications 159384056 }
|
|
tMainsL2GtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L2 >V - alarm disappeared"
|
::= { notifications 159384057 }
|
|
tMainsL2GtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L2 >V - alarm reset"
|
::= { notifications 159384058 }
|
|
tMainsL2GtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L2 >V - alarm activated"
|
::= { notifications 293601784 }
|
|
tMainsL2GtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L2 >V - alarm disappeared"
|
::= { notifications 293601785 }
|
|
tMainsL2GtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L2 >V - alarm reset"
|
::= { notifications 293601786 }
|
|
tMainsL2LtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L2 <V - alarm activated"
|
::= { notifications 25166316 }
|
|
tMainsL2LtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L2 <V - alarm disappeared"
|
::= { notifications 25166317 }
|
|
tMainsL2LtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L2 <V - alarm reset"
|
::= { notifications 25166318 }
|
|
tMainsL2LtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L2 <V - alarm activated"
|
::= { notifications 159384044 }
|
|
tMainsL2LtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L2 <V - alarm disappeared"
|
::= { notifications 159384045 }
|
|
tMainsL2LtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L2 <V - alarm reset"
|
::= { notifications 159384046 }
|
|
tMainsL2LtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L2 <V - alarm activated"
|
::= { notifications 293601772 }
|
|
tMainsL2LtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L2 <V - alarm disappeared"
|
::= { notifications 293601773 }
|
|
tMainsL2LtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L2 <V - alarm reset"
|
::= { notifications 293601774 }
|
|
tMainsL3GtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L3 >V - alarm activated"
|
::= { notifications 25166332 }
|
|
tMainsL3GtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L3 >V - alarm disappeared"
|
::= { notifications 25166333 }
|
|
tMainsL3GtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L3 >V - alarm reset"
|
::= { notifications 25166334 }
|
|
tMainsL3GtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L3 >V - alarm activated"
|
::= { notifications 159384060 }
|
|
tMainsL3GtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L3 >V - alarm disappeared"
|
::= { notifications 159384061 }
|
|
tMainsL3GtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L3 >V - alarm reset"
|
::= { notifications 159384062 }
|
|
tMainsL3GtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L3 >V - alarm activated"
|
::= { notifications 293601788 }
|
|
tMainsL3GtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L3 >V - alarm disappeared"
|
::= { notifications 293601789 }
|
|
tMainsL3GtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L3 >V - alarm reset"
|
::= { notifications 293601790 }
|
|
tMainsL3LtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L3 <V - alarm activated"
|
::= { notifications 25166320 }
|
|
tMainsL3LtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L3 <V - alarm disappeared"
|
::= { notifications 25166321 }
|
|
tMainsL3LtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L3 <V - alarm reset"
|
::= { notifications 25166322 }
|
|
tMainsL3LtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L3 <V - alarm activated"
|
::= { notifications 159384048 }
|
|
tMainsL3LtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L3 <V - alarm disappeared"
|
::= { notifications 159384049 }
|
|
tMainsL3LtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L3 <V - alarm reset"
|
::= { notifications 159384050 }
|
|
tMainsL3LtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L3 <V - alarm activated"
|
::= { notifications 293601776 }
|
|
tMainsL3LtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L3 <V - alarm disappeared"
|
::= { notifications 293601777 }
|
|
tMainsL3LtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L3 <V - alarm reset"
|
::= { notifications 293601778 }
|
|
tMainsL12GtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L12 >V - alarm activated"
|
::= { notifications 25166348 }
|
|
tMainsL12GtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L12 >V - alarm disappeared"
|
::= { notifications 25166349 }
|
|
tMainsL12GtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L12 >V - alarm reset"
|
::= { notifications 25166350 }
|
|
tMainsL12GtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L12 >V - alarm activated"
|
::= { notifications 159384076 }
|
|
tMainsL12GtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L12 >V - alarm disappeared"
|
::= { notifications 159384077 }
|
|
tMainsL12GtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L12 >V - alarm reset"
|
::= { notifications 159384078 }
|
|
tMainsL12GtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L12 >V - alarm activated"
|
::= { notifications 293601804 }
|
|
tMainsL12GtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L12 >V - alarm disappeared"
|
::= { notifications 293601805 }
|
|
tMainsL12GtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L12 >V - alarm reset"
|
::= { notifications 293601806 }
|
|
tMainsL12LtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L12 <V - alarm activated"
|
::= { notifications 25166336 }
|
|
tMainsL12LtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L12 <V - alarm disappeared"
|
::= { notifications 25166337 }
|
|
tMainsL12LtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L12 <V - alarm reset"
|
::= { notifications 25166338 }
|
|
tMainsL12LtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L12 <V - alarm activated"
|
::= { notifications 159384064 }
|
|
tMainsL12LtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L12 <V - alarm disappeared"
|
::= { notifications 159384065 }
|
|
tMainsL12LtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L12 <V - alarm reset"
|
::= { notifications 159384066 }
|
|
tMainsL12LtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L12 <V - alarm activated"
|
::= { notifications 293601792 }
|
|
tMainsL12LtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L12 <V - alarm disappeared"
|
::= { notifications 293601793 }
|
|
tMainsL12LtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L12 <V - alarm reset"
|
::= { notifications 293601794 }
|
|
tMainsL23GtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L23 >V - alarm activated"
|
::= { notifications 25166352 }
|
|
tMainsL23GtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L23 >V - alarm disappeared"
|
::= { notifications 25166353 }
|
|
tMainsL23GtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L23 >V - alarm reset"
|
::= { notifications 25166354 }
|
|
tMainsL23GtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L23 >V - alarm activated"
|
::= { notifications 159384080 }
|
|
tMainsL23GtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L23 >V - alarm disappeared"
|
::= { notifications 159384081 }
|
|
tMainsL23GtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L23 >V - alarm reset"
|
::= { notifications 159384082 }
|
|
tMainsL23GtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L23 >V - alarm activated"
|
::= { notifications 293601808 }
|
|
tMainsL23GtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L23 >V - alarm disappeared"
|
::= { notifications 293601809 }
|
|
tMainsL23GtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L23 >V - alarm reset"
|
::= { notifications 293601810 }
|
|
tMainsL23LtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L23 <V - alarm activated"
|
::= { notifications 25166340 }
|
|
tMainsL23LtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L23 <V - alarm disappeared"
|
::= { notifications 25166341 }
|
|
tMainsL23LtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L23 <V - alarm reset"
|
::= { notifications 25166342 }
|
|
tMainsL23LtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L23 <V - alarm activated"
|
::= { notifications 159384068 }
|
|
tMainsL23LtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L23 <V - alarm disappeared"
|
::= { notifications 159384069 }
|
|
tMainsL23LtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L23 <V - alarm reset"
|
::= { notifications 159384070 }
|
|
tMainsL23LtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L23 <V - alarm activated"
|
::= { notifications 293601796 }
|
|
tMainsL23LtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L23 <V - alarm disappeared"
|
::= { notifications 293601797 }
|
|
tMainsL23LtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L23 <V - alarm reset"
|
::= { notifications 293601798 }
|
|
tMainsL31GtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L31 >V - alarm activated"
|
::= { notifications 25166356 }
|
|
tMainsL31GtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L31 >V - alarm disappeared"
|
::= { notifications 25166357 }
|
|
tMainsL31GtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L31 >V - alarm reset"
|
::= { notifications 25166358 }
|
|
tMainsL31GtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L31 >V - alarm activated"
|
::= { notifications 159384084 }
|
|
tMainsL31GtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L31 >V - alarm disappeared"
|
::= { notifications 159384085 }
|
|
tMainsL31GtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L31 >V - alarm reset"
|
::= { notifications 159384086 }
|
|
tMainsL31GtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L31 >V - alarm activated"
|
::= { notifications 293601812 }
|
|
tMainsL31GtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L31 >V - alarm disappeared"
|
::= { notifications 293601813 }
|
|
tMainsL31GtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L31 >V - alarm reset"
|
::= { notifications 293601814 }
|
|
tMainsL31LtVL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L31 <V - alarm activated"
|
::= { notifications 25166344 }
|
|
tMainsL31LtVL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L31 <V - alarm disappeared"
|
::= { notifications 25166345 }
|
|
tMainsL31LtVL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains L31 <V - alarm reset"
|
::= { notifications 25166346 }
|
|
tMainsL31LtVL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L31 <V - alarm activated"
|
::= { notifications 159384072 }
|
|
tMainsL31LtVL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L31 <V - alarm disappeared"
|
::= { notifications 159384073 }
|
|
tMainsL31LtVL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains L31 <V - alarm reset"
|
::= { notifications 159384074 }
|
|
tMainsL31LtVSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L31 <V - alarm activated"
|
::= { notifications 293601800 }
|
|
tMainsL31LtVSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L31 <V - alarm disappeared"
|
::= { notifications 293601801 }
|
|
tMainsL31LtVSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains L31 <V - alarm reset"
|
::= { notifications 293601802 }
|
|
tMainsVoltageUnbalancePhPhL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage Unbalance ph-ph - alarm activated"
|
::= { notifications 25168192 }
|
|
tMainsVoltageUnbalancePhPhL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage Unbalance ph-ph - alarm disappeared"
|
::= { notifications 25168193 }
|
|
tMainsVoltageUnbalancePhPhL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage Unbalance ph-ph - alarm reset"
|
::= { notifications 25168194 }
|
|
tMainsVoltageUnbalancePhPhL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage Unbalance ph-ph - alarm activated"
|
::= { notifications 159385920 }
|
|
tMainsVoltageUnbalancePhPhL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage Unbalance ph-ph - alarm disappeared"
|
::= { notifications 159385921 }
|
|
tMainsVoltageUnbalancePhPhL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage Unbalance ph-ph - alarm reset"
|
::= { notifications 159385922 }
|
|
tMainsVoltageUnbalancePhPhSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage Unbalance ph-ph - alarm activated"
|
::= { notifications 293603648 }
|
|
tMainsVoltageUnbalancePhPhSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage Unbalance ph-ph - alarm disappeared"
|
::= { notifications 293603649 }
|
|
tMainsVoltageUnbalancePhPhSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage Unbalance ph-ph - alarm reset"
|
::= { notifications 293603650 }
|
|
tMainsVoltageUnbalancePhNL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage Unbalance ph-n - alarm activated"
|
::= { notifications 25168196 }
|
|
tMainsVoltageUnbalancePhNL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage Unbalance ph-n - alarm disappeared"
|
::= { notifications 25168197 }
|
|
tMainsVoltageUnbalancePhNL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains Voltage Unbalance ph-n - alarm reset"
|
::= { notifications 25168198 }
|
|
tMainsVoltageUnbalancePhNL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage Unbalance ph-n - alarm activated"
|
::= { notifications 159385924 }
|
|
tMainsVoltageUnbalancePhNL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage Unbalance ph-n - alarm disappeared"
|
::= { notifications 159385925 }
|
|
tMainsVoltageUnbalancePhNL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains Voltage Unbalance ph-n - alarm reset"
|
::= { notifications 159385926 }
|
|
tMainsVoltageUnbalancePhNSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage Unbalance ph-n - alarm activated"
|
::= { notifications 293603652 }
|
|
tMainsVoltageUnbalancePhNSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage Unbalance ph-n - alarm disappeared"
|
::= { notifications 293603653 }
|
|
tMainsVoltageUnbalancePhNSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains Voltage Unbalance ph-n - alarm reset"
|
::= { notifications 293603654 }
|
|
tMainsGtFrequencyL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains > Frequency - alarm activated"
|
::= { notifications 25166364 }
|
|
tMainsGtFrequencyL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains > Frequency - alarm disappeared"
|
::= { notifications 25166365 }
|
|
tMainsGtFrequencyL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains > Frequency - alarm reset"
|
::= { notifications 25166366 }
|
|
tMainsGtFrequencyL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains > Frequency - alarm activated"
|
::= { notifications 159384092 }
|
|
tMainsGtFrequencyL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains > Frequency - alarm disappeared"
|
::= { notifications 159384093 }
|
|
tMainsGtFrequencyL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains > Frequency - alarm reset"
|
::= { notifications 159384094 }
|
|
tMainsGtFrequencySFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains > Frequency - alarm activated"
|
::= { notifications 293601820 }
|
|
tMainsGtFrequencySFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains > Frequency - alarm disappeared"
|
::= { notifications 293601821 }
|
|
tMainsGtFrequencySFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains > Frequency - alarm reset"
|
::= { notifications 293601822 }
|
|
tMainsLtFrequencyL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains < Frequency - alarm activated"
|
::= { notifications 25166360 }
|
|
tMainsLtFrequencyL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains < Frequency - alarm disappeared"
|
::= { notifications 25166361 }
|
|
tMainsLtFrequencyL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains < Frequency - alarm reset"
|
::= { notifications 25166362 }
|
|
tMainsLtFrequencyL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains < Frequency - alarm activated"
|
::= { notifications 159384088 }
|
|
tMainsLtFrequencyL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains < Frequency - alarm disappeared"
|
::= { notifications 159384089 }
|
|
tMainsLtFrequencyL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains < Frequency - alarm reset"
|
::= { notifications 159384090 }
|
|
tMainsLtFrequencySFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains < Frequency - alarm activated"
|
::= { notifications 293601816 }
|
|
tMainsLtFrequencySFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains < Frequency - alarm disappeared"
|
::= { notifications 293601817 }
|
|
tMainsLtFrequencySFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains < Frequency - alarm reset"
|
::= { notifications 293601818 }
|
|
tGeneratorCCWRotationL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator CCW Rotation - alarm activated"
|
::= { notifications 25166440 }
|
|
tGeneratorCCWRotationL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator CCW Rotation - alarm disappeared"
|
::= { notifications 25166441 }
|
|
tGeneratorCCWRotationL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator CCW Rotation - alarm reset"
|
::= { notifications 25166442 }
|
|
tGeneratorCCWRotationL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator CCW Rotation - alarm activated"
|
::= { notifications 159384168 }
|
|
tGeneratorCCWRotationL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator CCW Rotation - alarm disappeared"
|
::= { notifications 159384169 }
|
|
tGeneratorCCWRotationL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator CCW Rotation - alarm reset"
|
::= { notifications 159384170 }
|
|
tGeneratorCCWRotationSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator CCW Rotation - alarm activated"
|
::= { notifications 293601896 }
|
|
tGeneratorCCWRotationSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator CCW Rotation - alarm disappeared"
|
::= { notifications 293601897 }
|
|
tGeneratorCCWRotationSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator CCW Rotation - alarm reset"
|
::= { notifications 293601898 }
|
|
tMainsCCWRotationL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains CCW Rotation - alarm activated"
|
::= { notifications 25166456 }
|
|
tMainsCCWRotationL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains CCW Rotation - alarm disappeared"
|
::= { notifications 25166457 }
|
|
tMainsCCWRotationL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Mains CCW Rotation - alarm reset"
|
::= { notifications 25166458 }
|
|
tMainsCCWRotationL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains CCW Rotation - alarm activated"
|
::= { notifications 159384184 }
|
|
tMainsCCWRotationL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains CCW Rotation - alarm disappeared"
|
::= { notifications 159384185 }
|
|
tMainsCCWRotationL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Mains CCW Rotation - alarm reset"
|
::= { notifications 159384186 }
|
|
tMainsCCWRotationSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains CCW Rotation - alarm activated"
|
::= { notifications 293601912 }
|
|
tMainsCCWRotationSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains CCW Rotation - alarm disappeared"
|
::= { notifications 293601913 }
|
|
tMainsCCWRotationSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Mains CCW Rotation - alarm reset"
|
::= { notifications 293601914 }
|
|
tSdEarthFaultCurrentL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Earth Fault Current - alarm activated"
|
::= { notifications 25168208 }
|
|
tSdEarthFaultCurrentL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Earth Fault Current - alarm disappeared"
|
::= { notifications 25168209 }
|
|
tSdEarthFaultCurrentL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Sd Earth Fault Current - alarm reset"
|
::= { notifications 25168210 }
|
|
tSdEarthFaultCurrentL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Earth Fault Current - alarm activated"
|
::= { notifications 159385936 }
|
|
tSdEarthFaultCurrentL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Earth Fault Current - alarm disappeared"
|
::= { notifications 159385937 }
|
|
tSdEarthFaultCurrentL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Sd Earth Fault Current - alarm reset"
|
::= { notifications 159385938 }
|
|
tSdEarthFaultCurrentSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Earth Fault Current - alarm activated"
|
::= { notifications 293603664 }
|
|
tSdEarthFaultCurrentSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Earth Fault Current - alarm disappeared"
|
::= { notifications 293603665 }
|
|
tSdEarthFaultCurrentSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Sd Earth Fault Current - alarm reset"
|
::= { notifications 293603666 }
|
|
tBOCOvercurrentIDMTL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Overcurrent IDMT - alarm activated"
|
::= { notifications 25168212 }
|
|
tBOCOvercurrentIDMTL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Overcurrent IDMT - alarm disappeared"
|
::= { notifications 25168213 }
|
|
tBOCOvercurrentIDMTL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Overcurrent IDMT - alarm reset"
|
::= { notifications 25168214 }
|
|
tBOCOvercurrentIDMTL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Overcurrent IDMT - alarm activated"
|
::= { notifications 159385940 }
|
|
tBOCOvercurrentIDMTL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Overcurrent IDMT - alarm disappeared"
|
::= { notifications 159385941 }
|
|
tBOCOvercurrentIDMTL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Overcurrent IDMT - alarm reset"
|
::= { notifications 159385942 }
|
|
tBOCOvercurrentIDMTSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Overcurrent IDMT - alarm activated"
|
::= { notifications 293603668 }
|
|
tBOCOvercurrentIDMTSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Overcurrent IDMT - alarm disappeared"
|
::= { notifications 293603669 }
|
|
tBOCOvercurrentIDMTSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Overcurrent IDMT - alarm reset"
|
::= { notifications 293603670 }
|
|
tGenGtIeBroIDMTBrcL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Gen > Ie (IDMT) - alarm activated"
|
::= { notifications 25168216 }
|
|
tGenGtIeBroIDMTBrcL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Gen > Ie (IDMT) - alarm disappeared"
|
::= { notifications 25168217 }
|
|
tGenGtIeBroIDMTBrcL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Gen > Ie (IDMT) - alarm reset"
|
::= { notifications 25168218 }
|
|
tGenGtIeBroIDMTBrcL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Gen > Ie (IDMT) - alarm activated"
|
::= { notifications 159385944 }
|
|
tGenGtIeBroIDMTBrcL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Gen > Ie (IDMT) - alarm disappeared"
|
::= { notifications 159385945 }
|
|
tGenGtIeBroIDMTBrcL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Gen > Ie (IDMT) - alarm reset"
|
::= { notifications 159385946 }
|
|
tGenGtIeBroIDMTBrcSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Gen > Ie (IDMT) - alarm activated"
|
::= { notifications 293603672 }
|
|
tGenGtIeBroIDMTBrcSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Gen > Ie (IDMT) - alarm disappeared"
|
::= { notifications 293603673 }
|
|
tGenGtIeBroIDMTBrcSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Gen > Ie (IDMT) - alarm reset"
|
::= { notifications 293603674 }
|
|
tTransferringFuelL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Transferring Fuel - alarm activated"
|
::= { notifications 25168220 }
|
|
tTransferringFuelL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Transferring Fuel - alarm disappeared"
|
::= { notifications 25168221 }
|
|
tTransferringFuelL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Transferring Fuel - alarm reset"
|
::= { notifications 25168222 }
|
|
tTransferringFuelL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Transferring Fuel - alarm activated"
|
::= { notifications 159385948 }
|
|
tTransferringFuelL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Transferring Fuel - alarm disappeared"
|
::= { notifications 159385949 }
|
|
tTransferringFuelL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Transferring Fuel - alarm reset"
|
::= { notifications 159385950 }
|
|
tTransferringFuelSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Transferring Fuel - alarm activated"
|
::= { notifications 293603676 }
|
|
tTransferringFuelSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Transferring Fuel - alarm disappeared"
|
::= { notifications 293603677 }
|
|
tTransferringFuelSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Transferring Fuel - alarm reset"
|
::= { notifications 293603678 }
|
|
tFuelTransferFailedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Transfer Failed - alarm activated"
|
::= { notifications 25168224 }
|
|
tFuelTransferFailedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Transfer Failed - alarm disappeared"
|
::= { notifications 25168225 }
|
|
tFuelTransferFailedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fuel Transfer Failed - alarm reset"
|
::= { notifications 25168226 }
|
|
tFuelTransferFailedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Transfer Failed - alarm activated"
|
::= { notifications 159385952 }
|
|
tFuelTransferFailedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Transfer Failed - alarm disappeared"
|
::= { notifications 159385953 }
|
|
tFuelTransferFailedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fuel Transfer Failed - alarm reset"
|
::= { notifications 159385954 }
|
|
tFuelTransferFailedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Transfer Failed - alarm activated"
|
::= { notifications 293603680 }
|
|
tFuelTransferFailedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Transfer Failed - alarm disappeared"
|
::= { notifications 293603681 }
|
|
tFuelTransferFailedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fuel Transfer Failed - alarm reset"
|
::= { notifications 293603682 }
|
|
tWrnBatteryUndervoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Battery Undervoltage - alarm activated"
|
::= { notifications 25169584 }
|
|
tWrnBatteryUndervoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Battery Undervoltage - alarm disappeared"
|
::= { notifications 25169585 }
|
|
tWrnBatteryUndervoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Battery Undervoltage - alarm reset"
|
::= { notifications 25169586 }
|
|
tWrnBatteryUndervoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Battery Undervoltage - alarm activated"
|
::= { notifications 159387312 }
|
|
tWrnBatteryUndervoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Battery Undervoltage - alarm disappeared"
|
::= { notifications 159387313 }
|
|
tWrnBatteryUndervoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Battery Undervoltage - alarm reset"
|
::= { notifications 159387314 }
|
|
tWrnBatteryUndervoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Battery Undervoltage - alarm activated"
|
::= { notifications 293605040 }
|
|
tWrnBatteryUndervoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Battery Undervoltage - alarm disappeared"
|
::= { notifications 293605041 }
|
|
tWrnBatteryUndervoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Battery Undervoltage - alarm reset"
|
::= { notifications 293605042 }
|
|
tWrnBatteryOvervoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Battery Overvoltage - alarm activated"
|
::= { notifications 25169588 }
|
|
tWrnBatteryOvervoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Battery Overvoltage - alarm disappeared"
|
::= { notifications 25169589 }
|
|
tWrnBatteryOvervoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Battery Overvoltage - alarm reset"
|
::= { notifications 25169590 }
|
|
tWrnBatteryOvervoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Battery Overvoltage - alarm activated"
|
::= { notifications 159387316 }
|
|
tWrnBatteryOvervoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Battery Overvoltage - alarm disappeared"
|
::= { notifications 159387317 }
|
|
tWrnBatteryOvervoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Battery Overvoltage - alarm reset"
|
::= { notifications 159387318 }
|
|
tWrnBatteryOvervoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Battery Overvoltage - alarm activated"
|
::= { notifications 293605044 }
|
|
tWrnBatteryOvervoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Battery Overvoltage - alarm disappeared"
|
::= { notifications 293605045 }
|
|
tWrnBatteryOvervoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Battery Overvoltage - alarm reset"
|
::= { notifications 293605046 }
|
|
tBatteryVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BatteryVoltage - alarm activated"
|
::= { notifications 25168232 }
|
|
tBatteryVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BatteryVoltage - alarm disappeared"
|
::= { notifications 25168233 }
|
|
tBatteryVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BatteryVoltage - alarm reset"
|
::= { notifications 25168234 }
|
|
tBatteryVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BatteryVoltage - alarm activated"
|
::= { notifications 159385960 }
|
|
tBatteryVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BatteryVoltage - alarm disappeared"
|
::= { notifications 159385961 }
|
|
tBatteryVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BatteryVoltage - alarm reset"
|
::= { notifications 159385962 }
|
|
tBatteryVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BatteryVoltage - alarm activated"
|
::= { notifications 293603688 }
|
|
tBatteryVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BatteryVoltage - alarm disappeared"
|
::= { notifications 293603689 }
|
|
tBatteryVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BatteryVoltage - alarm reset"
|
::= { notifications 293603690 }
|
|
tWrnCoolantTemperatureLowL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Coolant Temperature Low - alarm activated"
|
::= { notifications 25168236 }
|
|
tWrnCoolantTemperatureLowL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Coolant Temperature Low - alarm disappeared"
|
::= { notifications 25168237 }
|
|
tWrnCoolantTemperatureLowL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Coolant Temperature Low - alarm reset"
|
::= { notifications 25168238 }
|
|
tWrnCoolantTemperatureLowL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Coolant Temperature Low - alarm activated"
|
::= { notifications 159385964 }
|
|
tWrnCoolantTemperatureLowL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Coolant Temperature Low - alarm disappeared"
|
::= { notifications 159385965 }
|
|
tWrnCoolantTemperatureLowL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Coolant Temperature Low - alarm reset"
|
::= { notifications 159385966 }
|
|
tWrnCoolantTemperatureLowSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Coolant Temperature Low - alarm activated"
|
::= { notifications 293603692 }
|
|
tWrnCoolantTemperatureLowSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Coolant Temperature Low - alarm disappeared"
|
::= { notifications 293603693 }
|
|
tWrnCoolantTemperatureLowSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Coolant Temperature Low - alarm reset"
|
::= { notifications 293603694 }
|
|
tBatteryChargeFailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Battery Charge Fail - alarm activated"
|
::= { notifications 25168240 }
|
|
tBatteryChargeFailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Battery Charge Fail - alarm disappeared"
|
::= { notifications 25168241 }
|
|
tBatteryChargeFailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Battery Charge Fail - alarm reset"
|
::= { notifications 25168242 }
|
|
tBatteryChargeFailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Battery Charge Fail - alarm activated"
|
::= { notifications 159385968 }
|
|
tBatteryChargeFailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Battery Charge Fail - alarm disappeared"
|
::= { notifications 159385969 }
|
|
tBatteryChargeFailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Battery Charge Fail - alarm reset"
|
::= { notifications 159385970 }
|
|
tBatteryChargeFailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Battery Charge Fail - alarm activated"
|
::= { notifications 293603696 }
|
|
tBatteryChargeFailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Battery Charge Fail - alarm disappeared"
|
::= { notifications 293603697 }
|
|
tBatteryChargeFailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Battery Charge Fail - alarm reset"
|
::= { notifications 293603698 }
|
|
tWrnOverrideAllSdL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Override All Sd - alarm activated"
|
::= { notifications 25168520 }
|
|
tWrnOverrideAllSdL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Override All Sd - alarm disappeared"
|
::= { notifications 25168521 }
|
|
tWrnOverrideAllSdL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Override All Sd - alarm reset"
|
::= { notifications 25168522 }
|
|
tWrnOverrideAllSdL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Override All Sd - alarm activated"
|
::= { notifications 159386248 }
|
|
tWrnOverrideAllSdL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Override All Sd - alarm disappeared"
|
::= { notifications 159386249 }
|
|
tWrnOverrideAllSdL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Override All Sd - alarm reset"
|
::= { notifications 159386250 }
|
|
tWrnOverrideAllSdSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Override All Sd - alarm activated"
|
::= { notifications 293603976 }
|
|
tWrnOverrideAllSdSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Override All Sd - alarm disappeared"
|
::= { notifications 293603977 }
|
|
tWrnOverrideAllSdSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Override All Sd - alarm reset"
|
::= { notifications 293603978 }
|
|
tWrnRentalTimer1L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Rental Timer 1 - alarm activated"
|
::= { notifications 25168596 }
|
|
tWrnRentalTimer1L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Rental Timer 1 - alarm disappeared"
|
::= { notifications 25168597 }
|
|
tWrnRentalTimer1L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Rental Timer 1 - alarm reset"
|
::= { notifications 25168598 }
|
|
tWrnRentalTimer1L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Rental Timer 1 - alarm activated"
|
::= { notifications 159386324 }
|
|
tWrnRentalTimer1L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Rental Timer 1 - alarm disappeared"
|
::= { notifications 159386325 }
|
|
tWrnRentalTimer1L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Rental Timer 1 - alarm reset"
|
::= { notifications 159386326 }
|
|
tWrnRentalTimer1SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Rental Timer 1 - alarm activated"
|
::= { notifications 293604052 }
|
|
tWrnRentalTimer1SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Rental Timer 1 - alarm disappeared"
|
::= { notifications 293604053 }
|
|
tWrnRentalTimer1SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Rental Timer 1 - alarm reset"
|
::= { notifications 293604054 }
|
|
tWrnRentalTimer2L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Rental Timer 2 - alarm activated"
|
::= { notifications 25168600 }
|
|
tWrnRentalTimer2L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Rental Timer 2 - alarm disappeared"
|
::= { notifications 25168601 }
|
|
tWrnRentalTimer2L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Rental Timer 2 - alarm reset"
|
::= { notifications 25168602 }
|
|
tWrnRentalTimer2L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Rental Timer 2 - alarm activated"
|
::= { notifications 159386328 }
|
|
tWrnRentalTimer2L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Rental Timer 2 - alarm disappeared"
|
::= { notifications 159386329 }
|
|
tWrnRentalTimer2L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Rental Timer 2 - alarm reset"
|
::= { notifications 159386330 }
|
|
tWrnRentalTimer2SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Rental Timer 2 - alarm activated"
|
::= { notifications 293604056 }
|
|
tWrnRentalTimer2SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Rental Timer 2 - alarm disappeared"
|
::= { notifications 293604057 }
|
|
tWrnRentalTimer2SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Rental Timer 2 - alarm reset"
|
::= { notifications 293604058 }
|
|
tRentalTimer1ElapsedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rental Timer 1 Elapsed - alarm activated"
|
::= { notifications 25168604 }
|
|
tRentalTimer1ElapsedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rental Timer 1 Elapsed - alarm disappeared"
|
::= { notifications 25168605 }
|
|
tRentalTimer1ElapsedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rental Timer 1 Elapsed - alarm reset"
|
::= { notifications 25168606 }
|
|
tRentalTimer1ElapsedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rental Timer 1 Elapsed - alarm activated"
|
::= { notifications 159386332 }
|
|
tRentalTimer1ElapsedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rental Timer 1 Elapsed - alarm disappeared"
|
::= { notifications 159386333 }
|
|
tRentalTimer1ElapsedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rental Timer 1 Elapsed - alarm reset"
|
::= { notifications 159386334 }
|
|
tRentalTimer1ElapsedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rental Timer 1 Elapsed - alarm activated"
|
::= { notifications 293604060 }
|
|
tRentalTimer1ElapsedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rental Timer 1 Elapsed - alarm disappeared"
|
::= { notifications 293604061 }
|
|
tRentalTimer1ElapsedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rental Timer 1 Elapsed - alarm reset"
|
::= { notifications 293604062 }
|
|
tRentalTimer2ElapsedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rental Timer 2 Elapsed - alarm activated"
|
::= { notifications 25168608 }
|
|
tRentalTimer2ElapsedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rental Timer 2 Elapsed - alarm disappeared"
|
::= { notifications 25168609 }
|
|
tRentalTimer2ElapsedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rental Timer 2 Elapsed - alarm reset"
|
::= { notifications 25168610 }
|
|
tRentalTimer2ElapsedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rental Timer 2 Elapsed - alarm activated"
|
::= { notifications 159386336 }
|
|
tRentalTimer2ElapsedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rental Timer 2 Elapsed - alarm disappeared"
|
::= { notifications 159386337 }
|
|
tRentalTimer2ElapsedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rental Timer 2 Elapsed - alarm reset"
|
::= { notifications 159386338 }
|
|
tRentalTimer2ElapsedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rental Timer 2 Elapsed - alarm activated"
|
::= { notifications 293604064 }
|
|
tRentalTimer2ElapsedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rental Timer 2 Elapsed - alarm disappeared"
|
::= { notifications 293604065 }
|
|
tRentalTimer2ElapsedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rental Timer 2 Elapsed - alarm reset"
|
::= { notifications 293604066 }
|
|
tBOCRentalTimer1ExceededL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Rental Timer 1 Exceeded - alarm activated"
|
::= { notifications 25168612 }
|
|
tBOCRentalTimer1ExceededL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Rental Timer 1 Exceeded - alarm disappeared"
|
::= { notifications 25168613 }
|
|
tBOCRentalTimer1ExceededL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Rental Timer 1 Exceeded - alarm reset"
|
::= { notifications 25168614 }
|
|
tBOCRentalTimer1ExceededL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Rental Timer 1 Exceeded - alarm activated"
|
::= { notifications 159386340 }
|
|
tBOCRentalTimer1ExceededL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Rental Timer 1 Exceeded - alarm disappeared"
|
::= { notifications 159386341 }
|
|
tBOCRentalTimer1ExceededL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Rental Timer 1 Exceeded - alarm reset"
|
::= { notifications 159386342 }
|
|
tBOCRentalTimer1ExceededSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Rental Timer 1 Exceeded - alarm activated"
|
::= { notifications 293604068 }
|
|
tBOCRentalTimer1ExceededSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Rental Timer 1 Exceeded - alarm disappeared"
|
::= { notifications 293604069 }
|
|
tBOCRentalTimer1ExceededSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Rental Timer 1 Exceeded - alarm reset"
|
::= { notifications 293604070 }
|
|
tBOCRentalTimer2ExceededL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Rental Timer 2 Exceeded - alarm activated"
|
::= { notifications 25168616 }
|
|
tBOCRentalTimer2ExceededL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Rental Timer 2 Exceeded - alarm disappeared"
|
::= { notifications 25168617 }
|
|
tBOCRentalTimer2ExceededL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - BOC Rental Timer 2 Exceeded - alarm reset"
|
::= { notifications 25168618 }
|
|
tBOCRentalTimer2ExceededL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Rental Timer 2 Exceeded - alarm activated"
|
::= { notifications 159386344 }
|
|
tBOCRentalTimer2ExceededL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Rental Timer 2 Exceeded - alarm disappeared"
|
::= { notifications 159386345 }
|
|
tBOCRentalTimer2ExceededL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - BOC Rental Timer 2 Exceeded - alarm reset"
|
::= { notifications 159386346 }
|
|
tBOCRentalTimer2ExceededSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Rental Timer 2 Exceeded - alarm activated"
|
::= { notifications 293604072 }
|
|
tBOCRentalTimer2ExceededSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Rental Timer 2 Exceeded - alarm disappeared"
|
::= { notifications 293604073 }
|
|
tBOCRentalTimer2ExceededSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - BOC Rental Timer 2 Exceeded - alarm reset"
|
::= { notifications 293604074 }
|
|
tRentalTimerBlockStartL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rental Timer Block Start - alarm activated"
|
::= { notifications 25168936 }
|
|
tRentalTimerBlockStartL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rental Timer Block Start - alarm disappeared"
|
::= { notifications 25168937 }
|
|
tRentalTimerBlockStartL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Rental Timer Block Start - alarm reset"
|
::= { notifications 25168938 }
|
|
tRentalTimerBlockStartL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rental Timer Block Start - alarm activated"
|
::= { notifications 159386664 }
|
|
tRentalTimerBlockStartL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rental Timer Block Start - alarm disappeared"
|
::= { notifications 159386665 }
|
|
tRentalTimerBlockStartL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Rental Timer Block Start - alarm reset"
|
::= { notifications 159386666 }
|
|
tRentalTimerBlockStartSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rental Timer Block Start - alarm activated"
|
::= { notifications 293604392 }
|
|
tRentalTimerBlockStartSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rental Timer Block Start - alarm disappeared"
|
::= { notifications 293604393 }
|
|
tRentalTimerBlockStartSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Rental Timer Block Start - alarm reset"
|
::= { notifications 293604394 }
|
|
tManualRestoreL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Manual Restore - alarm activated"
|
::= { notifications 25168956 }
|
|
tManualRestoreL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Manual Restore - alarm disappeared"
|
::= { notifications 25168957 }
|
|
tManualRestoreL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Manual Restore - alarm reset"
|
::= { notifications 25168958 }
|
|
tManualRestoreL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Manual Restore - alarm activated"
|
::= { notifications 159386684 }
|
|
tManualRestoreL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Manual Restore - alarm disappeared"
|
::= { notifications 159386685 }
|
|
tManualRestoreL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Manual Restore - alarm reset"
|
::= { notifications 159386686 }
|
|
tManualRestoreSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Manual Restore - alarm activated"
|
::= { notifications 293604412 }
|
|
tManualRestoreSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Manual Restore - alarm disappeared"
|
::= { notifications 293604413 }
|
|
tManualRestoreSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Manual Restore - alarm reset"
|
::= { notifications 293604414 }
|
|
tWrnMainsVoltageDetectedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Mains Voltage Detected - alarm activated"
|
::= { notifications 25168960 }
|
|
tWrnMainsVoltageDetectedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Mains Voltage Detected - alarm disappeared"
|
::= { notifications 25168961 }
|
|
tWrnMainsVoltageDetectedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Mains Voltage Detected - alarm reset"
|
::= { notifications 25168962 }
|
|
tWrnMainsVoltageDetectedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Mains Voltage Detected - alarm activated"
|
::= { notifications 159386688 }
|
|
tWrnMainsVoltageDetectedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Mains Voltage Detected - alarm disappeared"
|
::= { notifications 159386689 }
|
|
tWrnMainsVoltageDetectedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Mains Voltage Detected - alarm reset"
|
::= { notifications 159386690 }
|
|
tWrnMainsVoltageDetectedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Mains Voltage Detected - alarm activated"
|
::= { notifications 293604416 }
|
|
tWrnMainsVoltageDetectedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Mains Voltage Detected - alarm disappeared"
|
::= { notifications 293604417 }
|
|
tWrnMainsVoltageDetectedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Mains Voltage Detected - alarm reset"
|
::= { notifications 293604418 }
|
|
tWrnFuelTheftL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Fuel Theft - alarm activated"
|
::= { notifications 25169128 }
|
|
tWrnFuelTheftL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Fuel Theft - alarm disappeared"
|
::= { notifications 25169129 }
|
|
tWrnFuelTheftL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrn Fuel Theft - alarm reset"
|
::= { notifications 25169130 }
|
|
tWrnFuelTheftL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Fuel Theft - alarm activated"
|
::= { notifications 159386856 }
|
|
tWrnFuelTheftL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Fuel Theft - alarm disappeared"
|
::= { notifications 159386857 }
|
|
tWrnFuelTheftL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrn Fuel Theft - alarm reset"
|
::= { notifications 159386858 }
|
|
tWrnFuelTheftSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Fuel Theft - alarm activated"
|
::= { notifications 293604584 }
|
|
tWrnFuelTheftSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Fuel Theft - alarm disappeared"
|
::= { notifications 293604585 }
|
|
tWrnFuelTheftSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrn Fuel Theft - alarm reset"
|
::= { notifications 293604586 }
|
|
tModuleCHR3ASlot1L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module: Slot 1 - alarm activated"
|
::= { notifications 25169248 }
|
|
tModuleCHR3ASlot1L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module: Slot 1 - alarm disappeared"
|
::= { notifications 25169249 }
|
|
tModuleCHR3ASlot1L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module: Slot 1 - alarm reset"
|
::= { notifications 25169250 }
|
|
tModuleCHR3ASlot1L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module: Slot 1 - alarm activated"
|
::= { notifications 159386976 }
|
|
tModuleCHR3ASlot1L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module: Slot 1 - alarm disappeared"
|
::= { notifications 159386977 }
|
|
tModuleCHR3ASlot1L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module: Slot 1 - alarm reset"
|
::= { notifications 159386978 }
|
|
tModuleCHR3ASlot1SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module: Slot 1 - alarm activated"
|
::= { notifications 293604704 }
|
|
tModuleCHR3ASlot1SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module: Slot 1 - alarm disappeared"
|
::= { notifications 293604705 }
|
|
tModuleCHR3ASlot1SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module: Slot 1 - alarm reset"
|
::= { notifications 293604706 }
|
|
tModuleCHR3ASlot2L1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module: Slot 2 - alarm activated"
|
::= { notifications 25169252 }
|
|
tModuleCHR3ASlot2L1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module: Slot 2 - alarm disappeared"
|
::= { notifications 25169253 }
|
|
tModuleCHR3ASlot2L1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Module: Slot 2 - alarm reset"
|
::= { notifications 25169254 }
|
|
tModuleCHR3ASlot2L2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module: Slot 2 - alarm activated"
|
::= { notifications 159386980 }
|
|
tModuleCHR3ASlot2L2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module: Slot 2 - alarm disappeared"
|
::= { notifications 159386981 }
|
|
tModuleCHR3ASlot2L2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Module: Slot 2 - alarm reset"
|
::= { notifications 159386982 }
|
|
tModuleCHR3ASlot2SFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module: Slot 2 - alarm activated"
|
::= { notifications 293604708 }
|
|
tModuleCHR3ASlot2SFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module: Slot 2 - alarm disappeared"
|
::= { notifications 293604709 }
|
|
tModuleCHR3ASlot2SFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Module: Slot 2 - alarm reset"
|
::= { notifications 293604710 }
|
|
tECUL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU - alarm activated"
|
::= { notifications 25165948 }
|
|
tECUL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU - alarm disappeared"
|
::= { notifications 25165949 }
|
|
tECUL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU - alarm reset"
|
::= { notifications 25165950 }
|
|
tECUL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU - alarm activated"
|
::= { notifications 159383676 }
|
|
tECUL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU - alarm disappeared"
|
::= { notifications 159383677 }
|
|
tECUL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU - alarm reset"
|
::= { notifications 159383678 }
|
|
tECUSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU - alarm activated"
|
::= { notifications 293601404 }
|
|
tECUSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU - alarm disappeared"
|
::= { notifications 293601405 }
|
|
tECUSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU - alarm reset"
|
::= { notifications 293601406 }
|
|
tECUDiagBlockedL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECUDiagBlocked - alarm activated"
|
::= { notifications 25165984 }
|
|
tECUDiagBlockedL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECUDiagBlocked - alarm disappeared"
|
::= { notifications 25165985 }
|
|
tECUDiagBlockedL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECUDiagBlocked - alarm reset"
|
::= { notifications 25165986 }
|
|
tECUDiagBlockedL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECUDiagBlocked - alarm activated"
|
::= { notifications 159383712 }
|
|
tECUDiagBlockedL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECUDiagBlocked - alarm disappeared"
|
::= { notifications 159383713 }
|
|
tECUDiagBlockedL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECUDiagBlocked - alarm reset"
|
::= { notifications 159383714 }
|
|
tECUDiagBlockedSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECUDiagBlocked - alarm activated"
|
::= { notifications 293601440 }
|
|
tECUDiagBlockedSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECUDiagBlocked - alarm disappeared"
|
::= { notifications 293601441 }
|
|
tECUDiagBlockedSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECUDiagBlocked - alarm reset"
|
::= { notifications 293601442 }
|
|
tWrongConfigL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrong config - alarm activated"
|
::= { notifications 25165988 }
|
|
tWrongConfigL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrong config - alarm disappeared"
|
::= { notifications 25165989 }
|
|
tWrongConfigL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Wrong config - alarm reset"
|
::= { notifications 25165990 }
|
|
tWrongConfigL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrong config - alarm activated"
|
::= { notifications 159383716 }
|
|
tWrongConfigL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrong config - alarm disappeared"
|
::= { notifications 159383717 }
|
|
tWrongConfigL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Wrong config - alarm reset"
|
::= { notifications 159383718 }
|
|
tWrongConfigSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrong config - alarm activated"
|
::= { notifications 293601444 }
|
|
tWrongConfigSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrong config - alarm disappeared"
|
::= { notifications 293601445 }
|
|
tWrongConfigSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Wrong config - alarm reset"
|
::= { notifications 293601446 }
|
|
tRTCBatteryFlatL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - RTC Battery Flat - alarm activated"
|
::= { notifications 25165992 }
|
|
tRTCBatteryFlatL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - RTC Battery Flat - alarm disappeared"
|
::= { notifications 25165993 }
|
|
tRTCBatteryFlatL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - RTC Battery Flat - alarm reset"
|
::= { notifications 25165994 }
|
|
tRTCBatteryFlatL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - RTC Battery Flat - alarm activated"
|
::= { notifications 159383720 }
|
|
tRTCBatteryFlatL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - RTC Battery Flat - alarm disappeared"
|
::= { notifications 159383721 }
|
|
tRTCBatteryFlatL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - RTC Battery Flat - alarm reset"
|
::= { notifications 159383722 }
|
|
tRTCBatteryFlatSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - RTC Battery Flat - alarm activated"
|
::= { notifications 293601448 }
|
|
tRTCBatteryFlatSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - RTC Battery Flat - alarm disappeared"
|
::= { notifications 293601449 }
|
|
tRTCBatteryFlatSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - RTC Battery Flat - alarm reset"
|
::= { notifications 293601450 }
|
|
tECUCommunicationFailL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Communication Fail - alarm activated"
|
::= { notifications 25168532 }
|
|
tECUCommunicationFailL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Communication Fail - alarm disappeared"
|
::= { notifications 25168533 }
|
|
tECUCommunicationFailL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - ECU Communication Fail - alarm reset"
|
::= { notifications 25168534 }
|
|
tECUCommunicationFailL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Communication Fail - alarm activated"
|
::= { notifications 159386260 }
|
|
tECUCommunicationFailL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Communication Fail - alarm disappeared"
|
::= { notifications 159386261 }
|
|
tECUCommunicationFailL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - ECU Communication Fail - alarm reset"
|
::= { notifications 159386262 }
|
|
tECUCommunicationFailSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Communication Fail - alarm activated"
|
::= { notifications 293603988 }
|
|
tECUCommunicationFailSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Communication Fail - alarm disappeared"
|
::= { notifications 293603989 }
|
|
tECUCommunicationFailSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - ECU Communication Fail - alarm reset"
|
::= { notifications 293603990 }
|
|
tGeneratorL1GtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1 > Voltage - alarm activated"
|
::= { notifications 25166216 }
|
|
tGeneratorL1GtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1 > Voltage - alarm disappeared"
|
::= { notifications 25166217 }
|
|
tGeneratorL1GtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1 > Voltage - alarm reset"
|
::= { notifications 25166218 }
|
|
tGeneratorL1GtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1 > Voltage - alarm activated"
|
::= { notifications 159383944 }
|
|
tGeneratorL1GtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1 > Voltage - alarm disappeared"
|
::= { notifications 159383945 }
|
|
tGeneratorL1GtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1 > Voltage - alarm reset"
|
::= { notifications 159383946 }
|
|
tGeneratorL1GtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1 > Voltage - alarm activated"
|
::= { notifications 293601672 }
|
|
tGeneratorL1GtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1 > Voltage - alarm disappeared"
|
::= { notifications 293601673 }
|
|
tGeneratorL1GtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1 > Voltage - alarm reset"
|
::= { notifications 293601674 }
|
|
tGeneratorL2GtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2 > Voltage - alarm activated"
|
::= { notifications 25166220 }
|
|
tGeneratorL2GtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2 > Voltage - alarm disappeared"
|
::= { notifications 25166221 }
|
|
tGeneratorL2GtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2 > Voltage - alarm reset"
|
::= { notifications 25166222 }
|
|
tGeneratorL2GtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2 > Voltage - alarm activated"
|
::= { notifications 159383948 }
|
|
tGeneratorL2GtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2 > Voltage - alarm disappeared"
|
::= { notifications 159383949 }
|
|
tGeneratorL2GtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2 > Voltage - alarm reset"
|
::= { notifications 159383950 }
|
|
tGeneratorL2GtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2 > Voltage - alarm activated"
|
::= { notifications 293601676 }
|
|
tGeneratorL2GtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2 > Voltage - alarm disappeared"
|
::= { notifications 293601677 }
|
|
tGeneratorL2GtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2 > Voltage - alarm reset"
|
::= { notifications 293601678 }
|
|
tGeneratorL3GtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3 > Voltage - alarm activated"
|
::= { notifications 25166224 }
|
|
tGeneratorL3GtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3 > Voltage - alarm disappeared"
|
::= { notifications 25166225 }
|
|
tGeneratorL3GtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3 > Voltage - alarm reset"
|
::= { notifications 25166226 }
|
|
tGeneratorL3GtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3 > Voltage - alarm activated"
|
::= { notifications 159383952 }
|
|
tGeneratorL3GtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3 > Voltage - alarm disappeared"
|
::= { notifications 159383953 }
|
|
tGeneratorL3GtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3 > Voltage - alarm reset"
|
::= { notifications 159383954 }
|
|
tGeneratorL3GtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3 > Voltage - alarm activated"
|
::= { notifications 293601680 }
|
|
tGeneratorL3GtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3 > Voltage - alarm disappeared"
|
::= { notifications 293601681 }
|
|
tGeneratorL3GtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3 > Voltage - alarm reset"
|
::= { notifications 293601682 }
|
|
tGeneratorL1L2GtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1L2 > Voltage - alarm activated"
|
::= { notifications 25166252 }
|
|
tGeneratorL1L2GtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1L2 > Voltage - alarm disappeared"
|
::= { notifications 25166253 }
|
|
tGeneratorL1L2GtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1L2 > Voltage - alarm reset"
|
::= { notifications 25166254 }
|
|
tGeneratorL1L2GtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1L2 > Voltage - alarm activated"
|
::= { notifications 159383980 }
|
|
tGeneratorL1L2GtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1L2 > Voltage - alarm disappeared"
|
::= { notifications 159383981 }
|
|
tGeneratorL1L2GtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1L2 > Voltage - alarm reset"
|
::= { notifications 159383982 }
|
|
tGeneratorL1L2GtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1L2 > Voltage - alarm activated"
|
::= { notifications 293601708 }
|
|
tGeneratorL1L2GtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1L2 > Voltage - alarm disappeared"
|
::= { notifications 293601709 }
|
|
tGeneratorL1L2GtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1L2 > Voltage - alarm reset"
|
::= { notifications 293601710 }
|
|
tGeneratorL2L3GtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2L3 > Voltage - alarm activated"
|
::= { notifications 25166256 }
|
|
tGeneratorL2L3GtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2L3 > Voltage - alarm disappeared"
|
::= { notifications 25166257 }
|
|
tGeneratorL2L3GtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2L3 > Voltage - alarm reset"
|
::= { notifications 25166258 }
|
|
tGeneratorL2L3GtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2L3 > Voltage - alarm activated"
|
::= { notifications 159383984 }
|
|
tGeneratorL2L3GtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2L3 > Voltage - alarm disappeared"
|
::= { notifications 159383985 }
|
|
tGeneratorL2L3GtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2L3 > Voltage - alarm reset"
|
::= { notifications 159383986 }
|
|
tGeneratorL2L3GtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2L3 > Voltage - alarm activated"
|
::= { notifications 293601712 }
|
|
tGeneratorL2L3GtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2L3 > Voltage - alarm disappeared"
|
::= { notifications 293601713 }
|
|
tGeneratorL2L3GtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2L3 > Voltage - alarm reset"
|
::= { notifications 293601714 }
|
|
tGeneratorL3L1GtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3L1 > Voltage - alarm activated"
|
::= { notifications 25166260 }
|
|
tGeneratorL3L1GtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3L1 > Voltage - alarm disappeared"
|
::= { notifications 25166261 }
|
|
tGeneratorL3L1GtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3L1 > Voltage - alarm reset"
|
::= { notifications 25166262 }
|
|
tGeneratorL3L1GtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3L1 > Voltage - alarm activated"
|
::= { notifications 159383988 }
|
|
tGeneratorL3L1GtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3L1 > Voltage - alarm disappeared"
|
::= { notifications 159383989 }
|
|
tGeneratorL3L1GtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3L1 > Voltage - alarm reset"
|
::= { notifications 159383990 }
|
|
tGeneratorL3L1GtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3L1 > Voltage - alarm activated"
|
::= { notifications 293601716 }
|
|
tGeneratorL3L1GtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3L1 > Voltage - alarm disappeared"
|
::= { notifications 293601717 }
|
|
tGeneratorL3L1GtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3L1 > Voltage - alarm reset"
|
::= { notifications 293601718 }
|
|
tGeneratorL1LtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1 < Voltage - alarm activated"
|
::= { notifications 25166204 }
|
|
tGeneratorL1LtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1 < Voltage - alarm disappeared"
|
::= { notifications 25166205 }
|
|
tGeneratorL1LtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1 < Voltage - alarm reset"
|
::= { notifications 25166206 }
|
|
tGeneratorL1LtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1 < Voltage - alarm activated"
|
::= { notifications 159383932 }
|
|
tGeneratorL1LtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1 < Voltage - alarm disappeared"
|
::= { notifications 159383933 }
|
|
tGeneratorL1LtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1 < Voltage - alarm reset"
|
::= { notifications 159383934 }
|
|
tGeneratorL1LtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1 < Voltage - alarm activated"
|
::= { notifications 293601660 }
|
|
tGeneratorL1LtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1 < Voltage - alarm disappeared"
|
::= { notifications 293601661 }
|
|
tGeneratorL1LtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1 < Voltage - alarm reset"
|
::= { notifications 293601662 }
|
|
tGeneratorL2LtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2 < Voltage - alarm activated"
|
::= { notifications 25166208 }
|
|
tGeneratorL2LtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2 < Voltage - alarm disappeared"
|
::= { notifications 25166209 }
|
|
tGeneratorL2LtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2 < Voltage - alarm reset"
|
::= { notifications 25166210 }
|
|
tGeneratorL2LtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2 < Voltage - alarm activated"
|
::= { notifications 159383936 }
|
|
tGeneratorL2LtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2 < Voltage - alarm disappeared"
|
::= { notifications 159383937 }
|
|
tGeneratorL2LtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2 < Voltage - alarm reset"
|
::= { notifications 159383938 }
|
|
tGeneratorL2LtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2 < Voltage - alarm activated"
|
::= { notifications 293601664 }
|
|
tGeneratorL2LtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2 < Voltage - alarm disappeared"
|
::= { notifications 293601665 }
|
|
tGeneratorL2LtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2 < Voltage - alarm reset"
|
::= { notifications 293601666 }
|
|
tGeneratorL3LtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3 < Voltage - alarm activated"
|
::= { notifications 25166212 }
|
|
tGeneratorL3LtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3 < Voltage - alarm disappeared"
|
::= { notifications 25166213 }
|
|
tGeneratorL3LtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3 < Voltage - alarm reset"
|
::= { notifications 25166214 }
|
|
tGeneratorL3LtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3 < Voltage - alarm activated"
|
::= { notifications 159383940 }
|
|
tGeneratorL3LtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3 < Voltage - alarm disappeared"
|
::= { notifications 159383941 }
|
|
tGeneratorL3LtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3 < Voltage - alarm reset"
|
::= { notifications 159383942 }
|
|
tGeneratorL3LtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3 < Voltage - alarm activated"
|
::= { notifications 293601668 }
|
|
tGeneratorL3LtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3 < Voltage - alarm disappeared"
|
::= { notifications 293601669 }
|
|
tGeneratorL3LtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3 < Voltage - alarm reset"
|
::= { notifications 293601670 }
|
|
tGeneratorL1L2LtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1L2 < Voltage - alarm activated"
|
::= { notifications 25166240 }
|
|
tGeneratorL1L2LtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1L2 < Voltage - alarm disappeared"
|
::= { notifications 25166241 }
|
|
tGeneratorL1L2LtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L1L2 < Voltage - alarm reset"
|
::= { notifications 25166242 }
|
|
tGeneratorL1L2LtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1L2 < Voltage - alarm activated"
|
::= { notifications 159383968 }
|
|
tGeneratorL1L2LtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1L2 < Voltage - alarm disappeared"
|
::= { notifications 159383969 }
|
|
tGeneratorL1L2LtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L1L2 < Voltage - alarm reset"
|
::= { notifications 159383970 }
|
|
tGeneratorL1L2LtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1L2 < Voltage - alarm activated"
|
::= { notifications 293601696 }
|
|
tGeneratorL1L2LtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1L2 < Voltage - alarm disappeared"
|
::= { notifications 293601697 }
|
|
tGeneratorL1L2LtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L1L2 < Voltage - alarm reset"
|
::= { notifications 293601698 }
|
|
tGeneratorL2L3LtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2L3 < Voltage - alarm activated"
|
::= { notifications 25166244 }
|
|
tGeneratorL2L3LtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2L3 < Voltage - alarm disappeared"
|
::= { notifications 25166245 }
|
|
tGeneratorL2L3LtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L2L3 < Voltage - alarm reset"
|
::= { notifications 25166246 }
|
|
tGeneratorL2L3LtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2L3 < Voltage - alarm activated"
|
::= { notifications 159383972 }
|
|
tGeneratorL2L3LtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2L3 < Voltage - alarm disappeared"
|
::= { notifications 159383973 }
|
|
tGeneratorL2L3LtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L2L3 < Voltage - alarm reset"
|
::= { notifications 159383974 }
|
|
tGeneratorL2L3LtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2L3 < Voltage - alarm activated"
|
::= { notifications 293601700 }
|
|
tGeneratorL2L3LtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2L3 < Voltage - alarm disappeared"
|
::= { notifications 293601701 }
|
|
tGeneratorL2L3LtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L2L3 < Voltage - alarm reset"
|
::= { notifications 293601702 }
|
|
tGeneratorL3L1LtVoltageL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3L1 < Voltage - alarm activated"
|
::= { notifications 25166248 }
|
|
tGeneratorL3L1LtVoltageL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3L1 < Voltage - alarm disappeared"
|
::= { notifications 25166249 }
|
|
tGeneratorL3L1LtVoltageL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator L3L1 < Voltage - alarm reset"
|
::= { notifications 25166250 }
|
|
tGeneratorL3L1LtVoltageL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3L1 < Voltage - alarm activated"
|
::= { notifications 159383976 }
|
|
tGeneratorL3L1LtVoltageL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3L1 < Voltage - alarm disappeared"
|
::= { notifications 159383977 }
|
|
tGeneratorL3L1LtVoltageL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator L3L1 < Voltage - alarm reset"
|
::= { notifications 159383978 }
|
|
tGeneratorL3L1LtVoltageSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3L1 < Voltage - alarm activated"
|
::= { notifications 293601704 }
|
|
tGeneratorL3L1LtVoltageSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3L1 < Voltage - alarm disappeared"
|
::= { notifications 293601705 }
|
|
tGeneratorL3L1LtVoltageSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator L3L1 < Voltage - alarm reset"
|
::= { notifications 293601706 }
|
|
tGeneratorGtFrequencyL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator > Frequency - alarm activated"
|
::= { notifications 25166308 }
|
|
tGeneratorGtFrequencyL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator > Frequency - alarm disappeared"
|
::= { notifications 25166309 }
|
|
tGeneratorGtFrequencyL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator > Frequency - alarm reset"
|
::= { notifications 25166310 }
|
|
tGeneratorGtFrequencyL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator > Frequency - alarm activated"
|
::= { notifications 159384036 }
|
|
tGeneratorGtFrequencyL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator > Frequency - alarm disappeared"
|
::= { notifications 159384037 }
|
|
tGeneratorGtFrequencyL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator > Frequency - alarm reset"
|
::= { notifications 159384038 }
|
|
tGeneratorGtFrequencySFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator > Frequency - alarm activated"
|
::= { notifications 293601764 }
|
|
tGeneratorGtFrequencySFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator > Frequency - alarm disappeared"
|
::= { notifications 293601765 }
|
|
tGeneratorGtFrequencySFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator > Frequency - alarm reset"
|
::= { notifications 293601766 }
|
|
tGeneratorLtFrequencyL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator < Frequency - alarm activated"
|
::= { notifications 25166304 }
|
|
tGeneratorLtFrequencyL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator < Frequency - alarm disappeared"
|
::= { notifications 25166305 }
|
|
tGeneratorLtFrequencyL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Generator < Frequency - alarm reset"
|
::= { notifications 25166306 }
|
|
tGeneratorLtFrequencyL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator < Frequency - alarm activated"
|
::= { notifications 159384032 }
|
|
tGeneratorLtFrequencyL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator < Frequency - alarm disappeared"
|
::= { notifications 159384033 }
|
|
tGeneratorLtFrequencyL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Generator < Frequency - alarm reset"
|
::= { notifications 159384034 }
|
|
tGeneratorLtFrequencySFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator < Frequency - alarm activated"
|
::= { notifications 293601760 }
|
|
tGeneratorLtFrequencySFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator < Frequency - alarm disappeared"
|
::= { notifications 293601761 }
|
|
tGeneratorLtFrequencySFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Generator < Frequency - alarm reset"
|
::= { notifications 293601762 }
|
|
tCurrentUnbalanceL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Current Unbalance - alarm activated"
|
::= { notifications 25168188 }
|
|
tCurrentUnbalanceL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Current Unbalance - alarm disappeared"
|
::= { notifications 25168189 }
|
|
tCurrentUnbalanceL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Current Unbalance - alarm reset"
|
::= { notifications 25168190 }
|
|
tCurrentUnbalanceL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Current Unbalance - alarm activated"
|
::= { notifications 159385916 }
|
|
tCurrentUnbalanceL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Current Unbalance - alarm disappeared"
|
::= { notifications 159385917 }
|
|
tCurrentUnbalanceL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Current Unbalance - alarm reset"
|
::= { notifications 159385918 }
|
|
tCurrentUnbalanceSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Current Unbalance - alarm activated"
|
::= { notifications 293603644 }
|
|
tCurrentUnbalanceSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Current Unbalance - alarm disappeared"
|
::= { notifications 293603645 }
|
|
tCurrentUnbalanceSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Current Unbalance - alarm reset"
|
::= { notifications 293603646 }
|
|
tOverloadL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Overload - alarm activated"
|
::= { notifications 25168200 }
|
|
tOverloadL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Overload - alarm disappeared"
|
::= { notifications 25168201 }
|
|
tOverloadL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Overload - alarm reset"
|
::= { notifications 25168202 }
|
|
tOverloadL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Overload - alarm activated"
|
::= { notifications 159385928 }
|
|
tOverloadL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Overload - alarm disappeared"
|
::= { notifications 159385929 }
|
|
tOverloadL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Overload - alarm reset"
|
::= { notifications 159385930 }
|
|
tOverloadSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Overload - alarm activated"
|
::= { notifications 293603656 }
|
|
tOverloadSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Overload - alarm disappeared"
|
::= { notifications 293603657 }
|
|
tOverloadSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Overload - alarm reset"
|
::= { notifications 293603658 }
|
|
tShortCircuitL1Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Short Circuit - alarm activated"
|
::= { notifications 25168204 }
|
|
tShortCircuitL1Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Short Circuit - alarm disappeared"
|
::= { notifications 25168205 }
|
|
tShortCircuitL1AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Short Circuit - alarm reset"
|
::= { notifications 25168206 }
|
|
tShortCircuitL2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Short Circuit - alarm activated"
|
::= { notifications 159385932 }
|
|
tShortCircuitL2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Short Circuit - alarm disappeared"
|
::= { notifications 159385933 }
|
|
tShortCircuitL2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Short Circuit - alarm reset"
|
::= { notifications 159385934 }
|
|
tShortCircuitSFActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Short Circuit - alarm activated"
|
::= { notifications 293603660 }
|
|
tShortCircuitSFDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Short Circuit - alarm disappeared"
|
::= { notifications 293603661 }
|
|
tShortCircuitSFAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Short Circuit - alarm reset"
|
::= { notifications 293603662 }
|
|
tFence1AlarmL1Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 1 Alarm - alarm activated"
|
::= { notifications 25169068 }
|
|
tFence1AlarmL1Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 1 Alarm - alarm disappeared"
|
::= { notifications 25169069 }
|
|
tFence1AlarmL1AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 1 Alarm - alarm reset"
|
::= { notifications 25169070 }
|
|
tFence1AlarmL2Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 1 Alarm - alarm activated"
|
::= { notifications 159386796 }
|
|
tFence1AlarmL2Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 1 Alarm - alarm disappeared"
|
::= { notifications 159386797 }
|
|
tFence1AlarmL2AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 1 Alarm - alarm reset"
|
::= { notifications 159386798 }
|
|
tFence1AlarmSFActivated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 1 Alarm - alarm activated"
|
::= { notifications 293604524 }
|
|
tFence1AlarmSFDisappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 1 Alarm - alarm disappeared"
|
::= { notifications 293604525 }
|
|
tFence1AlarmSFAlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 1 Alarm - alarm reset"
|
::= { notifications 293604526 }
|
|
tFence1AlarmL1Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 1 Alarm - alarm activated"
|
::= { notifications 25169072 }
|
|
tFence1AlarmL1Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 1 Alarm - alarm disappeared"
|
::= { notifications 25169073 }
|
|
tFence1AlarmL1AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 1 Alarm - alarm reset"
|
::= { notifications 25169074 }
|
|
tFence1AlarmL2Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 1 Alarm - alarm activated"
|
::= { notifications 159386800 }
|
|
tFence1AlarmL2Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 1 Alarm - alarm disappeared"
|
::= { notifications 159386801 }
|
|
tFence1AlarmL2AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 1 Alarm - alarm reset"
|
::= { notifications 159386802 }
|
|
tFence1AlarmSFActivated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 1 Alarm - alarm activated"
|
::= { notifications 293604528 }
|
|
tFence1AlarmSFDisappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 1 Alarm - alarm disappeared"
|
::= { notifications 293604529 }
|
|
tFence1AlarmSFAlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 1 Alarm - alarm reset"
|
::= { notifications 293604530 }
|
|
tFence2AlarmL1Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 2 Alarm - alarm activated"
|
::= { notifications 25169076 }
|
|
tFence2AlarmL1Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 2 Alarm - alarm disappeared"
|
::= { notifications 25169077 }
|
|
tFence2AlarmL1AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 2 Alarm - alarm reset"
|
::= { notifications 25169078 }
|
|
tFence2AlarmL2Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 2 Alarm - alarm activated"
|
::= { notifications 159386804 }
|
|
tFence2AlarmL2Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 2 Alarm - alarm disappeared"
|
::= { notifications 159386805 }
|
|
tFence2AlarmL2AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 2 Alarm - alarm reset"
|
::= { notifications 159386806 }
|
|
tFence2AlarmSFActivated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 2 Alarm - alarm activated"
|
::= { notifications 293604532 }
|
|
tFence2AlarmSFDisappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 2 Alarm - alarm disappeared"
|
::= { notifications 293604533 }
|
|
tFence2AlarmSFAlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 2 Alarm - alarm reset"
|
::= { notifications 293604534 }
|
|
tFence2AlarmL1Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 2 Alarm - alarm activated"
|
::= { notifications 25169080 }
|
|
tFence2AlarmL1Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 2 Alarm - alarm disappeared"
|
::= { notifications 25169081 }
|
|
tFence2AlarmL1AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 1. level - Fence 2 Alarm - alarm reset"
|
::= { notifications 25169082 }
|
|
tFence2AlarmL2Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 2 Alarm - alarm activated"
|
::= { notifications 159386808 }
|
|
tFence2AlarmL2Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 2 Alarm - alarm disappeared"
|
::= { notifications 159386809 }
|
|
tFence2AlarmL2AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection 2. level - Fence 2 Alarm - alarm reset"
|
::= { notifications 159386810 }
|
|
tFence2AlarmSFActivated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 2 Alarm - alarm activated"
|
::= { notifications 293604536 }
|
|
tFence2AlarmSFDisappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 2 Alarm - alarm disappeared"
|
::= { notifications 293604537 }
|
|
tFence2AlarmSFAlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Protection Sensor Fail - Fence 2 Alarm - alarm reset"
|
::= { notifications 293604538 }
|
|
tInjectorCylHash1Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#1"
|
::= { notifications 536870916 }
|
|
tInjectorCylHash2Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#2"
|
::= { notifications 536870920 }
|
|
tInjectorCylHash3Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#3"
|
::= { notifications 536870924 }
|
|
tInjectorCylHash4Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#4"
|
::= { notifications 536870928 }
|
|
tInjectorCylHash5Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#5"
|
::= { notifications 536870932 }
|
|
tInjectorCylHash6Activated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#6"
|
::= { notifications 536870936 }
|
|
t8VSensPwrSuppActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: 8VSensPwrSupp"
|
::= { notifications 536871076 }
|
|
tThrottlePosActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ThrottlePos"
|
::= { notifications 536871116 }
|
|
tAccelPedalPosActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AccelPedalPos"
|
::= { notifications 536871276 }
|
|
tPercentLoadActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: PercentLoad"
|
::= { notifications 536871280 }
|
|
tFuelDelPressActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: FuelDelPress"
|
::= { notifications 536871288 }
|
|
tWaterInFuelIndActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: WaterInFuelInd"
|
::= { notifications 536871300 }
|
|
tEngineOilLevelActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngineOilLevel"
|
::= { notifications 536871304 }
|
|
tEngOilPressActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngOil Press"
|
::= { notifications 536871312 }
|
|
tCrankcasePressActivated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CrankcasePress"
|
::= { notifications 536871316 }
|
|
tBoostPressActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Boost Press"
|
::= { notifications 536871320 }
|
|
tIntakeTempActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Intake Temp"
|
::= { notifications 536871332 }
|
|
tAirInletPressActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AirInletPress"
|
::= { notifications 536871336 }
|
|
tAirFiltDifPresActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AirFiltDifPres"
|
::= { notifications 536871340 }
|
|
tBarometricPresActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: BarometricPres"
|
::= { notifications 536871344 }
|
|
tCoolantPressActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Coolant Press"
|
::= { notifications 536871348 }
|
|
tEngCoolTempActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngCool Temp"
|
::= { notifications 536871352 }
|
|
tCoolantLevelActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Coolant Level"
|
::= { notifications 536871356 }
|
|
tCrankcasePressActivated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CrankcasePress"
|
::= { notifications 536871524 }
|
|
tFuelRailPressActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: FuelRailPress"
|
::= { notifications 536871540 }
|
|
tBattPotentialActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: BattPotential"
|
::= { notifications 536871544 }
|
|
tBatteryVoltageActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: BatteryVoltage"
|
::= { notifications 536871584 }
|
|
tAirInletTempActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AirInlet Temp"
|
::= { notifications 536871600 }
|
|
tFuelTempActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Fuel Temp"
|
::= { notifications 536871608 }
|
|
tEngOilTempActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngOil Temp"
|
::= { notifications 536871612 }
|
|
tFuelRateActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Fuel Rate"
|
::= { notifications 536871644 }
|
|
tRatedEngSpeedActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: RatedEngSpeed"
|
::= { notifications 536871668 }
|
|
tEngineSpeedActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngineSpeed"
|
::= { notifications 536871672 }
|
|
tTimingCalibrActivated1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TimingCalibr"
|
::= { notifications 536871824 }
|
|
tJ1939DatalinkActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: J1939 Datalink"
|
::= { notifications 536871836 }
|
|
tIncorrectFWActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Incorrect FW"
|
::= { notifications 536871848 }
|
|
tVINActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: VIN"
|
::= { notifications 536871860 }
|
|
tTotalEngHoursActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TotalEngHours"
|
::= { notifications 536871900 }
|
|
tDataLinkCommActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: DataLinkComm"
|
::= { notifications 536871904 }
|
|
tCheckSysParamsActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CheckSysParams"
|
::= { notifications 536871924 }
|
|
tECMFaultActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ECM Fault"
|
::= { notifications 536871928 }
|
|
tTimingCalibrActivated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TimingCalibr"
|
::= { notifications 536871956 }
|
|
t5VSensPwrSuppActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: 5VSensPwrSupp"
|
::= { notifications 536871960 }
|
|
tCheckPrgParamsActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CheckPrgParams"
|
::= { notifications 536871984 }
|
|
tTurboOutltPresActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TurboOutltPres"
|
::= { notifications 536872004 }
|
|
tAtmospherPressActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AtmospherPress"
|
::= { notifications 536872008 }
|
|
tActionAlrtLampActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ActionAlrtLamp"
|
::= { notifications 536872036 }
|
|
tEngOverspdLampActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngOverspdLamp"
|
::= { notifications 536872040 }
|
|
tEnCoolTempLampActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EnCoolTempLamp"
|
::= { notifications 536872052 }
|
|
tLubOilPresLampActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: LubOilPresLamp"
|
::= { notifications 536872056 }
|
|
tEnShutdownLampActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EnShutdownLamp"
|
::= { notifications 536872204 }
|
|
tEngWarningLampActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngWarningLamp"
|
::= { notifications 536872208 }
|
|
tEngSpeedSens2Activated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngSpeedSens2"
|
::= { notifications 536872280 }
|
|
tCrankTermRelayActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CrankTermRelay"
|
::= { notifications 536872684 }
|
|
tEngDesOpSpeedActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngDesOpSpeed"
|
::= { notifications 536872972 }
|
|
t5VSupplyFailActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: 5V SupplyFail"
|
::= { notifications 536873392 }
|
|
tPrehActuatorActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: PrehActuator"
|
::= { notifications 536873416 }
|
|
tEMSProgFailureActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EMSProgFailure"
|
::= { notifications 536873424 }
|
|
tEEPROMChecksumActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EEPROMChecksum"
|
::= { notifications 536873428 }
|
|
tCalibrMemFailActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CalibrMemFail"
|
::= { notifications 536873432 }
|
|
tCrankSensorActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Crank Sensor"
|
::= { notifications 536873456 }
|
|
tTimingSensorActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TimingSensor"
|
::= { notifications 536873460 }
|
|
tJ1939CANBusActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: J1939 CAN Bus"
|
::= { notifications 536873468 }
|
|
tInjectorCylHash1Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#1"
|
::= { notifications 536873516 }
|
|
tInjectorCylHash2Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#2"
|
::= { notifications 536873520 }
|
|
tInjectorCylHash3Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#3"
|
::= { notifications 536873524 }
|
|
tInjectorCylHash4Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#4"
|
::= { notifications 536873528 }
|
|
tInjectorCylHash5Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#5"
|
::= { notifications 536873532 }
|
|
tInjectorCylHash6Activated2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#6"
|
::= { notifications 536873536 }
|
|
tEngStartRelayActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngStartRelay"
|
::= { notifications 536873620 }
|
|
tECM8DCSupplyActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ECM 8DC supply"
|
::= { notifications 536873624 }
|
|
tOverrdCtrlModeActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: OverrdCtrlMode"
|
::= { notifications 536873692 }
|
|
tSecSpeedSensActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: SecSpeedSens"
|
::= { notifications 536873804 }
|
|
tServiceToolActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Service Tool"
|
::= { notifications 536874108 }
|
|
tRequestedSpeedActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: RequestedSpeed"
|
::= { notifications 536874504 }
|
|
tAuxEngSdSwitchActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AuxEngSdSwitch"
|
::= { notifications 536874792 }
|
|
tEngDerateSwtchActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngDerateSwtch"
|
::= { notifications 536874796 }
|
|
tCritOverrideEnActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CritOverrideEn"
|
::= { notifications 536875344 }
|
|
tEngSdApproachActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngSdApproach"
|
::= { notifications 536875348 }
|
|
tEngineSdActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Engine Sd"
|
::= { notifications 536875352 }
|
|
tCheckCfgParamsActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CheckCfgParams"
|
::= { notifications 536875356 }
|
|
tDiagnosticLampActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: DiagnosticLamp"
|
::= { notifications 536875976 }
|
|
tECUMainRelayActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ECU MainRelay"
|
::= { notifications 536876852 }
|
|
tAnlgThrottlSigActivated NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AnlgThrottlSig"
|
::= { notifications 536877672 }
|
|
tInjectorCylHash1Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#1"
|
::= { notifications 536870917 }
|
|
tInjectorCylHash2Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#2"
|
::= { notifications 536870921 }
|
|
tInjectorCylHash3Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#3"
|
::= { notifications 536870925 }
|
|
tInjectorCylHash4Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#4"
|
::= { notifications 536870929 }
|
|
tInjectorCylHash5Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#5"
|
::= { notifications 536870933 }
|
|
tInjectorCylHash6Disappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#6"
|
::= { notifications 536870937 }
|
|
t8VSensPwrSuppDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: 8VSensPwrSupp"
|
::= { notifications 536871077 }
|
|
tThrottlePosDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ThrottlePos"
|
::= { notifications 536871117 }
|
|
tAccelPedalPosDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AccelPedalPos"
|
::= { notifications 536871277 }
|
|
tPercentLoadDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: PercentLoad"
|
::= { notifications 536871281 }
|
|
tFuelDelPressDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: FuelDelPress"
|
::= { notifications 536871289 }
|
|
tWaterInFuelIndDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: WaterInFuelInd"
|
::= { notifications 536871301 }
|
|
tEngineOilLevelDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngineOilLevel"
|
::= { notifications 536871305 }
|
|
tEngOilPressDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngOil Press"
|
::= { notifications 536871313 }
|
|
tCrankcasePressDisappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CrankcasePress"
|
::= { notifications 536871317 }
|
|
tBoostPressDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Boost Press"
|
::= { notifications 536871321 }
|
|
tIntakeTempDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Intake Temp"
|
::= { notifications 536871333 }
|
|
tAirInletPressDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AirInletPress"
|
::= { notifications 536871337 }
|
|
tAirFiltDifPresDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AirFiltDifPres"
|
::= { notifications 536871341 }
|
|
tBarometricPresDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: BarometricPres"
|
::= { notifications 536871345 }
|
|
tCoolantPressDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Coolant Press"
|
::= { notifications 536871349 }
|
|
tEngCoolTempDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngCool Temp"
|
::= { notifications 536871353 }
|
|
tCoolantLevelDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Coolant Level"
|
::= { notifications 536871357 }
|
|
tCrankcasePressDisappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CrankcasePress"
|
::= { notifications 536871525 }
|
|
tFuelRailPressDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: FuelRailPress"
|
::= { notifications 536871541 }
|
|
tBattPotentialDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: BattPotential"
|
::= { notifications 536871545 }
|
|
tBatteryVoltageDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: BatteryVoltage"
|
::= { notifications 536871585 }
|
|
tAirInletTempDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AirInlet Temp"
|
::= { notifications 536871601 }
|
|
tFuelTempDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Fuel Temp"
|
::= { notifications 536871609 }
|
|
tEngOilTempDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngOil Temp"
|
::= { notifications 536871613 }
|
|
tFuelRateDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Fuel Rate"
|
::= { notifications 536871645 }
|
|
tRatedEngSpeedDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: RatedEngSpeed"
|
::= { notifications 536871669 }
|
|
tEngineSpeedDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngineSpeed"
|
::= { notifications 536871673 }
|
|
tTimingCalibrDisappeared1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TimingCalibr"
|
::= { notifications 536871825 }
|
|
tJ1939DatalinkDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: J1939 Datalink"
|
::= { notifications 536871837 }
|
|
tIncorrectFWDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Incorrect FW"
|
::= { notifications 536871849 }
|
|
tVINDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: VIN"
|
::= { notifications 536871861 }
|
|
tTotalEngHoursDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TotalEngHours"
|
::= { notifications 536871901 }
|
|
tDataLinkCommDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: DataLinkComm"
|
::= { notifications 536871905 }
|
|
tCheckSysParamsDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CheckSysParams"
|
::= { notifications 536871925 }
|
|
tECMFaultDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ECM Fault"
|
::= { notifications 536871929 }
|
|
tTimingCalibrDisappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TimingCalibr"
|
::= { notifications 536871957 }
|
|
t5VSensPwrSuppDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: 5VSensPwrSupp"
|
::= { notifications 536871961 }
|
|
tCheckPrgParamsDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CheckPrgParams"
|
::= { notifications 536871985 }
|
|
tTurboOutltPresDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TurboOutltPres"
|
::= { notifications 536872005 }
|
|
tAtmospherPressDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AtmospherPress"
|
::= { notifications 536872009 }
|
|
tActionAlrtLampDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ActionAlrtLamp"
|
::= { notifications 536872037 }
|
|
tEngOverspdLampDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngOverspdLamp"
|
::= { notifications 536872041 }
|
|
tEnCoolTempLampDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EnCoolTempLamp"
|
::= { notifications 536872053 }
|
|
tLubOilPresLampDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: LubOilPresLamp"
|
::= { notifications 536872057 }
|
|
tEnShutdownLampDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EnShutdownLamp"
|
::= { notifications 536872205 }
|
|
tEngWarningLampDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngWarningLamp"
|
::= { notifications 536872209 }
|
|
tEngSpeedSens2Disappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngSpeedSens2"
|
::= { notifications 536872281 }
|
|
tCrankTermRelayDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CrankTermRelay"
|
::= { notifications 536872685 }
|
|
tEngDesOpSpeedDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngDesOpSpeed"
|
::= { notifications 536872973 }
|
|
t5VSupplyFailDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: 5V SupplyFail"
|
::= { notifications 536873393 }
|
|
tPrehActuatorDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: PrehActuator"
|
::= { notifications 536873417 }
|
|
tEMSProgFailureDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EMSProgFailure"
|
::= { notifications 536873425 }
|
|
tEEPROMChecksumDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EEPROMChecksum"
|
::= { notifications 536873429 }
|
|
tCalibrMemFailDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CalibrMemFail"
|
::= { notifications 536873433 }
|
|
tCrankSensorDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Crank Sensor"
|
::= { notifications 536873457 }
|
|
tTimingSensorDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TimingSensor"
|
::= { notifications 536873461 }
|
|
tJ1939CANBusDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: J1939 CAN Bus"
|
::= { notifications 536873469 }
|
|
tInjectorCylHash1Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#1"
|
::= { notifications 536873517 }
|
|
tInjectorCylHash2Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#2"
|
::= { notifications 536873521 }
|
|
tInjectorCylHash3Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#3"
|
::= { notifications 536873525 }
|
|
tInjectorCylHash4Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#4"
|
::= { notifications 536873529 }
|
|
tInjectorCylHash5Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#5"
|
::= { notifications 536873533 }
|
|
tInjectorCylHash6Disappeared2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#6"
|
::= { notifications 536873537 }
|
|
tEngStartRelayDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngStartRelay"
|
::= { notifications 536873621 }
|
|
tECM8DCSupplyDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ECM 8DC supply"
|
::= { notifications 536873625 }
|
|
tOverrdCtrlModeDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: OverrdCtrlMode"
|
::= { notifications 536873693 }
|
|
tSecSpeedSensDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: SecSpeedSens"
|
::= { notifications 536873805 }
|
|
tServiceToolDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Service Tool"
|
::= { notifications 536874109 }
|
|
tRequestedSpeedDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: RequestedSpeed"
|
::= { notifications 536874505 }
|
|
tAuxEngSdSwitchDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AuxEngSdSwitch"
|
::= { notifications 536874793 }
|
|
tEngDerateSwtchDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngDerateSwtch"
|
::= { notifications 536874797 }
|
|
tCritOverrideEnDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CritOverrideEn"
|
::= { notifications 536875345 }
|
|
tEngSdApproachDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngSdApproach"
|
::= { notifications 536875349 }
|
|
tEngineSdDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Engine Sd"
|
::= { notifications 536875353 }
|
|
tCheckCfgParamsDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CheckCfgParams"
|
::= { notifications 536875357 }
|
|
tDiagnosticLampDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: DiagnosticLamp"
|
::= { notifications 536875977 }
|
|
tECUMainRelayDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ECU MainRelay"
|
::= { notifications 536876853 }
|
|
tAnlgThrottlSigDisappeared NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AnlgThrottlSig"
|
::= { notifications 536877673 }
|
|
tInjectorCylHash1AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#1"
|
::= { notifications 536870918 }
|
|
tInjectorCylHash2AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#2"
|
::= { notifications 536870922 }
|
|
tInjectorCylHash3AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#3"
|
::= { notifications 536870926 }
|
|
tInjectorCylHash4AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#4"
|
::= { notifications 536870930 }
|
|
tInjectorCylHash5AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#5"
|
::= { notifications 536870934 }
|
|
tInjectorCylHash6AlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#6"
|
::= { notifications 536870938 }
|
|
t8VSensPwrSuppAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: 8VSensPwrSupp"
|
::= { notifications 536871078 }
|
|
tThrottlePosAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ThrottlePos"
|
::= { notifications 536871118 }
|
|
tAccelPedalPosAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AccelPedalPos"
|
::= { notifications 536871278 }
|
|
tPercentLoadAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: PercentLoad"
|
::= { notifications 536871282 }
|
|
tFuelDelPressAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: FuelDelPress"
|
::= { notifications 536871290 }
|
|
tWaterInFuelIndAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: WaterInFuelInd"
|
::= { notifications 536871302 }
|
|
tEngineOilLevelAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngineOilLevel"
|
::= { notifications 536871306 }
|
|
tEngOilPressAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngOil Press"
|
::= { notifications 536871314 }
|
|
tCrankcasePressAlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CrankcasePress"
|
::= { notifications 536871318 }
|
|
tBoostPressAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Boost Press"
|
::= { notifications 536871322 }
|
|
tIntakeTempAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Intake Temp"
|
::= { notifications 536871334 }
|
|
tAirInletPressAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AirInletPress"
|
::= { notifications 536871338 }
|
|
tAirFiltDifPresAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AirFiltDifPres"
|
::= { notifications 536871342 }
|
|
tBarometricPresAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: BarometricPres"
|
::= { notifications 536871346 }
|
|
tCoolantPressAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Coolant Press"
|
::= { notifications 536871350 }
|
|
tEngCoolTempAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngCool Temp"
|
::= { notifications 536871354 }
|
|
tCoolantLevelAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Coolant Level"
|
::= { notifications 536871358 }
|
|
tCrankcasePressAlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CrankcasePress"
|
::= { notifications 536871526 }
|
|
tFuelRailPressAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: FuelRailPress"
|
::= { notifications 536871542 }
|
|
tBattPotentialAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: BattPotential"
|
::= { notifications 536871546 }
|
|
tBatteryVoltageAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: BatteryVoltage"
|
::= { notifications 536871586 }
|
|
tAirInletTempAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AirInlet Temp"
|
::= { notifications 536871602 }
|
|
tFuelTempAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Fuel Temp"
|
::= { notifications 536871610 }
|
|
tEngOilTempAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngOil Temp"
|
::= { notifications 536871614 }
|
|
tFuelRateAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Fuel Rate"
|
::= { notifications 536871646 }
|
|
tRatedEngSpeedAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: RatedEngSpeed"
|
::= { notifications 536871670 }
|
|
tEngineSpeedAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngineSpeed"
|
::= { notifications 536871674 }
|
|
tTimingCalibrAlarmReset1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TimingCalibr"
|
::= { notifications 536871826 }
|
|
tJ1939DatalinkAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: J1939 Datalink"
|
::= { notifications 536871838 }
|
|
tIncorrectFWAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Incorrect FW"
|
::= { notifications 536871850 }
|
|
tVINAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: VIN"
|
::= { notifications 536871862 }
|
|
tTotalEngHoursAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TotalEngHours"
|
::= { notifications 536871902 }
|
|
tDataLinkCommAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: DataLinkComm"
|
::= { notifications 536871906 }
|
|
tCheckSysParamsAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CheckSysParams"
|
::= { notifications 536871926 }
|
|
tECMFaultAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ECM Fault"
|
::= { notifications 536871930 }
|
|
tTimingCalibrAlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TimingCalibr"
|
::= { notifications 536871958 }
|
|
t5VSensPwrSuppAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: 5VSensPwrSupp"
|
::= { notifications 536871962 }
|
|
tCheckPrgParamsAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CheckPrgParams"
|
::= { notifications 536871986 }
|
|
tTurboOutltPresAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TurboOutltPres"
|
::= { notifications 536872006 }
|
|
tAtmospherPressAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AtmospherPress"
|
::= { notifications 536872010 }
|
|
tActionAlrtLampAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ActionAlrtLamp"
|
::= { notifications 536872038 }
|
|
tEngOverspdLampAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngOverspdLamp"
|
::= { notifications 536872042 }
|
|
tEnCoolTempLampAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EnCoolTempLamp"
|
::= { notifications 536872054 }
|
|
tLubOilPresLampAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: LubOilPresLamp"
|
::= { notifications 536872058 }
|
|
tEnShutdownLampAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EnShutdownLamp"
|
::= { notifications 536872206 }
|
|
tEngWarningLampAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngWarningLamp"
|
::= { notifications 536872210 }
|
|
tEngSpeedSens2AlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngSpeedSens2"
|
::= { notifications 536872282 }
|
|
tCrankTermRelayAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CrankTermRelay"
|
::= { notifications 536872686 }
|
|
tEngDesOpSpeedAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngDesOpSpeed"
|
::= { notifications 536872974 }
|
|
t5VSupplyFailAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: 5V SupplyFail"
|
::= { notifications 536873394 }
|
|
tPrehActuatorAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: PrehActuator"
|
::= { notifications 536873418 }
|
|
tEMSProgFailureAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EMSProgFailure"
|
::= { notifications 536873426 }
|
|
tEEPROMChecksumAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EEPROMChecksum"
|
::= { notifications 536873430 }
|
|
tCalibrMemFailAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CalibrMemFail"
|
::= { notifications 536873434 }
|
|
tCrankSensorAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Crank Sensor"
|
::= { notifications 536873458 }
|
|
tTimingSensorAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: TimingSensor"
|
::= { notifications 536873462 }
|
|
tJ1939CANBusAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: J1939 CAN Bus"
|
::= { notifications 536873470 }
|
|
tInjectorCylHash1AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#1"
|
::= { notifications 536873518 }
|
|
tInjectorCylHash2AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#2"
|
::= { notifications 536873522 }
|
|
tInjectorCylHash3AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#3"
|
::= { notifications 536873526 }
|
|
tInjectorCylHash4AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#4"
|
::= { notifications 536873530 }
|
|
tInjectorCylHash5AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#5"
|
::= { notifications 536873534 }
|
|
tInjectorCylHash6AlarmReset2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: InjectorCyl#6"
|
::= { notifications 536873538 }
|
|
tEngStartRelayAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngStartRelay"
|
::= { notifications 536873622 }
|
|
tECM8DCSupplyAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ECM 8DC supply"
|
::= { notifications 536873626 }
|
|
tOverrdCtrlModeAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: OverrdCtrlMode"
|
::= { notifications 536873694 }
|
|
tSecSpeedSensAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: SecSpeedSens"
|
::= { notifications 536873806 }
|
|
tServiceToolAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Service Tool"
|
::= { notifications 536874110 }
|
|
tRequestedSpeedAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: RequestedSpeed"
|
::= { notifications 536874506 }
|
|
tAuxEngSdSwitchAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AuxEngSdSwitch"
|
::= { notifications 536874794 }
|
|
tEngDerateSwtchAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngDerateSwtch"
|
::= { notifications 536874798 }
|
|
tCritOverrideEnAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CritOverrideEn"
|
::= { notifications 536875346 }
|
|
tEngSdApproachAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: EngSdApproach"
|
::= { notifications 536875350 }
|
|
tEngineSdAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: Engine Sd"
|
::= { notifications 536875354 }
|
|
tCheckCfgParamsAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: CheckCfgParams"
|
::= { notifications 536875358 }
|
|
tDiagnosticLampAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: DiagnosticLamp"
|
::= { notifications 536875978 }
|
|
tECUMainRelayAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: ECU MainRelay"
|
::= { notifications 536876854 }
|
|
tAnlgThrottlSigAlarmReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "ECU: AnlgThrottlSig"
|
::= { notifications 536877674 }
|
|
tECUCommunicationFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: ECU Communication Fail"
|
::= { notifications 1073741847 }
|
|
tBO1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: BO 1"
|
::= { notifications 1073742207 }
|
|
tBO2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: BO 2"
|
::= { notifications 1073742208 }
|
|
tBO3 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: BO 3"
|
::= { notifications 1073742209 }
|
|
tBO4 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: BO 4"
|
::= { notifications 1073742210 }
|
|
tModuleBroSlotABrcFalseModule NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotA) - false module"
|
::= { notifications 1073741886 }
|
|
tModuleBroSlotBBrcFalseModule NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotB) - false module"
|
::= { notifications 1073741887 }
|
|
tModuleBroSlotABrcUnknownModule NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotA) - unknown module"
|
::= { notifications 1073741888 }
|
|
tModuleBroSlotBBrcUnknownModule NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotB) - unknown module"
|
::= { notifications 1073741889 }
|
|
tModuleBroSlotABrcUnattended NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotA) - unattended"
|
::= { notifications 1073741890 }
|
|
tModuleBroSlotBBrcUnattended NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotB) - unattended"
|
::= { notifications 1073741891 }
|
|
tModuleBroSlotABrcCommCHR2EOutage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotA) - comm. outage"
|
::= { notifications 1073741892 }
|
|
tModuleBroSlotBBrcCommCHR2EOutage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotB) - comm. outage"
|
::= { notifications 1073741893 }
|
|
tModuleBroSlotABrcUnexpected NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotA) - unexpected"
|
::= { notifications 1073741894 }
|
|
tModuleBroSlotBBrcUnexpected NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Module(slotB) - unexpected"
|
::= { notifications 1073741895 }
|
|
tEMBroABrcAMessageLost NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: EM(A) - a message lost"
|
::= { notifications 1073741896 }
|
|
tEMBroBBrcAMessageLost NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: EM(B) - a message lost"
|
::= { notifications 1073741897 }
|
|
tEMBroABrcConfigurationMistake NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: EM(A) - configuration mistake"
|
::= { notifications 1073741898 }
|
|
tEMBroBBrcConfigurationMistake NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: EM(B) - configuration mistake"
|
::= { notifications 1073741899 }
|
|
tEMBroABrcInsufficient NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: EM(A) - insufficient"
|
::= { notifications 1073741900 }
|
|
tEMBroBBrcInsufficient NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: EM(B) - insufficient"
|
::= { notifications 1073741901 }
|
|
tEMBroABrcMissingOrDamaged NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: EM(A) - missing or damaged"
|
::= { notifications 1073741902 }
|
|
tEMBroBBrcMissingOrDamaged NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: EM(B) - missing or damaged"
|
::= { notifications 1073741903 }
|
|
tForceHistCHR2E1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Force Hist. 1"
|
::= { notifications 1073742115 }
|
|
tForceHistCHR2E2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Force Hist. 2"
|
::= { notifications 1073742116 }
|
|
thistPLC3 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: hist PLC 3"
|
::= { notifications 1073742117 }
|
|
thistPLC4 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: hist PLC 4"
|
::= { notifications 1073742118 }
|
|
tFaultReset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Fault reset"
|
::= { notifications 1073741848 }
|
|
tEventEMail1OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event e-mail 1 OK"
|
::= { notifications 1073741849 }
|
|
tEventEMail2OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event e-mail 2 OK"
|
::= { notifications 1073741850 }
|
|
tEventEMail3OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event e-mail 3 OK"
|
::= { notifications 1073741851 }
|
|
tEventEMail4OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event e-mail 4 OK"
|
::= { notifications 1073741852 }
|
|
tEventSMS1OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event SMS 1 OK"
|
::= { notifications 1073741853 }
|
|
tEventSMS2OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event SMS 2 OK"
|
::= { notifications 1073741854 }
|
|
tEventSMS3OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event SMS 3 OK"
|
::= { notifications 1073741855 }
|
|
tEventSMS4OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event SMS 4 OK"
|
::= { notifications 1073741856 }
|
|
tAlarmEMail1OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm e-mail 1 OK"
|
::= { notifications 1073742121 }
|
|
tAlarmEMail2OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm e-mail 2 OK"
|
::= { notifications 1073742122 }
|
|
tAlarmEMail3OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm e-mail 3 OK"
|
::= { notifications 1073742125 }
|
|
tAlarmEMail4OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm e-mail 4 OK"
|
::= { notifications 1073742126 }
|
|
tAlarmSMS1OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm SMS 1 OK"
|
::= { notifications 1073742127 }
|
|
tAlarmSMS2OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm SMS 2 OK"
|
::= { notifications 1073742128 }
|
|
tAlarmSMS3OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm SMS 3 OK"
|
::= { notifications 1073742129 }
|
|
tAlarmSMS4OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm SMS 4 OK"
|
::= { notifications 1073742130 }
|
|
tSNMPTRAP1OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: SNMP TRAP 1 OK"
|
::= { notifications 1073742131 }
|
|
tSNMPTRAP2OK NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: SNMP TRAP 2 OK"
|
::= { notifications 1073742132 }
|
|
tEventEMail1Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event e-mail 1 Fail"
|
::= { notifications 1073741857 }
|
|
tEventEMail2Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event e-mail 2 Fail"
|
::= { notifications 1073741858 }
|
|
tEventEMail3Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event e-mail 3 Fail"
|
::= { notifications 1073741859 }
|
|
tEventEMail4Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event e-mail 4 Fail"
|
::= { notifications 1073741860 }
|
|
tEventSMS1Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event SMS 1 Fail"
|
::= { notifications 1073741861 }
|
|
tEventSMS2Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event SMS 2 Fail"
|
::= { notifications 1073741862 }
|
|
tEventSMS3Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event SMS 3 Fail"
|
::= { notifications 1073741863 }
|
|
tEventSMS4Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Event SMS 4 Fail"
|
::= { notifications 1073741864 }
|
|
tAlarmEMail1Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm e-mail 1 Fail"
|
::= { notifications 1073742123 }
|
|
tAlarmEMail2Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm e-mail 2 Fail"
|
::= { notifications 1073742124 }
|
|
tAlarmEMail3Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm e-mail 3 Fail"
|
::= { notifications 1073742133 }
|
|
tAlarmEMail4Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm e-mail 4 Fail"
|
::= { notifications 1073742134 }
|
|
tAlarmSMS1Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm SMS 1 Fail"
|
::= { notifications 1073742135 }
|
|
tAlarmSMS2Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm SMS 2 Fail"
|
::= { notifications 1073742136 }
|
|
tAlarmSMS3Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm SMS 3 Fail"
|
::= { notifications 1073742137 }
|
|
tAlarmSMS4Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Alarm SMS 4 Fail"
|
::= { notifications 1073742138 }
|
|
tSNMPTRAP1Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: SNMP TRAP 1 Fail"
|
::= { notifications 1073742139 }
|
|
tSNMPTRAP2Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: SNMP TRAP 2 Fail"
|
::= { notifications 1073742140 }
|
|
tSwitchedOn NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Switched On"
|
::= { notifications 1073741825 }
|
|
tWatchdog NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Watchdog"
|
::= { notifications 1073741826 }
|
|
tSystem NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: System"
|
::= { notifications 1073741865 }
|
|
tSystemLog NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: System Log"
|
::= { notifications 1073741866 }
|
|
tWrongConfig NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrong config"
|
::= { notifications 1073741867 }
|
|
tSetpointChange NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: SetpointChange"
|
::= { notifications 1073741868 }
|
|
tPasswordSet NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Password set"
|
::= { notifications 1073741869 }
|
|
tPasswordChng NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Password chng"
|
::= { notifications 1073741870 }
|
|
tAccessCodeSet NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: AccessCodeSet"
|
::= { notifications 1073741871 }
|
|
tAccessCodeChng NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: AccessCodeChng"
|
::= { notifications 1073741872 }
|
|
tAdminAction NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Admin action"
|
::= { notifications 1073741873 }
|
|
tTerminal NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Terminal"
|
::= { notifications 1073741874 }
|
|
tExtDisplay NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Ext display"
|
::= { notifications 1073741875 }
|
|
tBinaryUnstable NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: BinaryUnstable"
|
::= { notifications 1073741876 }
|
|
tForceValue NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: ForceValue"
|
::= { notifications 1073741877 }
|
|
tTimeModeChange NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: TimeModeChange"
|
::= { notifications 1073741878 }
|
|
tGroupsLinked NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: GroupsLinked"
|
::= { notifications 1073741879 }
|
|
tGroupsUnlinked NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: GroupsUnlinked"
|
::= { notifications 1073741880 }
|
|
tPreAlarmStamp NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: PreAlarm stamp"
|
::= { notifications 1073741881 }
|
|
tProgrammingRequest NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Programming Request"
|
::= { notifications 1073741882 }
|
|
tProgrammingFinished NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Programming finished"
|
::= { notifications 1073741883 }
|
|
tProgrammingResult NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Programming result"
|
::= { notifications 1073741884 }
|
|
tUnknownECUDiag NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Unknown ECU diag"
|
::= { notifications 1073741885 }
|
|
tAlCHR2FHistCHR2Emsg1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 1"
|
::= { notifications 1073741969 }
|
|
tAlCHR2FHistCHR2Emsg2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 2"
|
::= { notifications 1073741970 }
|
|
tAlCHR2FHistCHR2Emsg3 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 3"
|
::= { notifications 1073741971 }
|
|
tAlCHR2FHistCHR2Emsg4 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 4"
|
::= { notifications 1073741972 }
|
|
tAlCHR2FHistCHR2Emsg5 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 5"
|
::= { notifications 1073741973 }
|
|
tAlCHR2FHistCHR2Emsg6 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 6"
|
::= { notifications 1073741974 }
|
|
tAlCHR2FHistCHR2Emsg7 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 7"
|
::= { notifications 1073741975 }
|
|
tAlCHR2FHistCHR2Emsg8 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 8"
|
::= { notifications 1073741976 }
|
|
tAlCHR2FHistCHR2Emsg9 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 9"
|
::= { notifications 1073741977 }
|
|
tAlCHR2FHistCHR2Emsg10 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 10"
|
::= { notifications 1073741978 }
|
|
tAlCHR2FHistCHR2Emsg11 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 11"
|
::= { notifications 1073741979 }
|
|
tAlCHR2FHistCHR2Emsg12 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 12"
|
::= { notifications 1073741980 }
|
|
tAlCHR2FHistCHR2Emsg13 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 13"
|
::= { notifications 1073741981 }
|
|
tAlCHR2FHistCHR2Emsg14 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 14"
|
::= { notifications 1073741982 }
|
|
tAlCHR2FHistCHR2Emsg15 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 15"
|
::= { notifications 1073741983 }
|
|
tAlCHR2FHistCHR2Emsg16 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Al/Hist.msg 16"
|
::= { notifications 1073741984 }
|
|
tTimeStamp NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Time Stamp"
|
::= { notifications 1073741985 }
|
|
tEmergencyStop NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Emergency Stop"
|
::= { notifications 1073741986 }
|
|
tGeneratorL1GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L1 > Voltage"
|
::= { notifications 1073741987 }
|
|
tGeneratorL2GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L2 > Voltage"
|
::= { notifications 1073741988 }
|
|
tGeneratorL3GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L3 > Voltage"
|
::= { notifications 1073741989 }
|
|
tGeneratorL1LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L1 < Voltage"
|
::= { notifications 1073741990 }
|
|
tGeneratorL2LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L2 < Voltage"
|
::= { notifications 1073741991 }
|
|
tGeneratorL3LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L3 < Voltage"
|
::= { notifications 1073741992 }
|
|
tGeneratorL1L2GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L1L2 > Voltage"
|
::= { notifications 1073741993 }
|
|
tGeneratorL2L3GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L2L3 > Voltage"
|
::= { notifications 1073741994 }
|
|
tGeneratorL3L1GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L3L1 > Voltage"
|
::= { notifications 1073741995 }
|
|
tGeneratorL1L2LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L1L2 < Voltage"
|
::= { notifications 1073741996 }
|
|
tGeneratorL2L3LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L2L3 < Voltage"
|
::= { notifications 1073741997 }
|
|
tGeneratorL3L1LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator L3L1 < Voltage"
|
::= { notifications 1073741998 }
|
|
tGeneratorVoltageUnbalance NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator Voltage Unbalance"
|
::= { notifications 1073741999 }
|
|
tCurrentUnbalance NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Current Unbalance"
|
::= { notifications 1073742000 }
|
|
tGeneratorGtFrequency NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator > Frequency"
|
::= { notifications 1073742001 }
|
|
tGeneratorLtFrequency NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator < Frequency"
|
::= { notifications 1073742002 }
|
|
tMainsL1GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L1 > Voltage"
|
::= { notifications 1073742003 }
|
|
tMainsL2GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L2 > Voltage"
|
::= { notifications 1073742004 }
|
|
tMainsL3GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L3 > Voltage"
|
::= { notifications 1073742005 }
|
|
tMainsL1LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L1 < Voltage"
|
::= { notifications 1073742006 }
|
|
tMainsL2LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L2 < Voltage"
|
::= { notifications 1073742007 }
|
|
tMainsL3LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L3 < Voltage"
|
::= { notifications 1073742008 }
|
|
tMainsL1L2GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L1L2 > Voltage"
|
::= { notifications 1073742009 }
|
|
tMainsL2L3GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L2L3 > Voltage"
|
::= { notifications 1073742010 }
|
|
tMainsL3L1GtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L3L1 > Voltage"
|
::= { notifications 1073742011 }
|
|
tMainsL1L2LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L1L2 < Voltage"
|
::= { notifications 1073742012 }
|
|
tMainsL2L3LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L2L3 < Voltage"
|
::= { notifications 1073742013 }
|
|
tMainsL3L1LtVoltage NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains L3L1 < Voltage"
|
::= { notifications 1073742014 }
|
|
tMainsVoltageUnbalance NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains Voltage Unbalance"
|
::= { notifications 1073742015 }
|
|
tMainsGtFrequency NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains > Frequency"
|
::= { notifications 1073742016 }
|
|
tMainsLtFrequency NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains < Frequency"
|
::= { notifications 1073742017 }
|
|
tOverload NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Overload"
|
::= { notifications 1073742018 }
|
|
tSdGCBFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Sd GCB Fail"
|
::= { notifications 1073742021 }
|
|
tWrnMCBFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn MCB Fail"
|
::= { notifications 1073742022 }
|
|
tSdOverspeed NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Sd Overspeed"
|
::= { notifications 1073742023 }
|
|
tSdUnderspeed NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Sd Underspeed"
|
::= { notifications 1073742024 }
|
|
tSdIOMFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Sd IOM Fail"
|
::= { notifications 1073742025 }
|
|
tSdRPMMeasurementFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Sd RPM Measurement Fail"
|
::= { notifications 1073742026 }
|
|
tSdBatteryFlat NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Sd Battery Flat"
|
::= { notifications 1073742027 }
|
|
tSdStartFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Sd Start Fail"
|
::= { notifications 1073742028 }
|
|
tWrnMaintenance1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Maintenance 1"
|
::= { notifications 1073742029 }
|
|
tWrnMaintenance2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Maintenance 2"
|
::= { notifications 1073742030 }
|
|
tWrnMaintenance3 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Maintenance 3"
|
::= { notifications 1073742031 }
|
|
tShortCircuit NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Short Circuit"
|
::= { notifications 1073742032 }
|
|
tBOCOvercurrentIDMT NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: BOC Overcurrent IDMT"
|
::= { notifications 1073742033 }
|
|
tSdEarthFaultCurrent NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Sd Earth Fault Current"
|
::= { notifications 1073742034 }
|
|
tEarthAmpsIDMT NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Earth Amps IDMT"
|
::= { notifications 1073742035 }
|
|
tWrnRA15Fail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn RA15 Fail"
|
::= { notifications 1073742036 }
|
|
tWrnCoolantTemperatureLow NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Coolant Temperature Low"
|
::= { notifications 1073742037 }
|
|
tBatteryChargeFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Battery Charge Fail"
|
::= { notifications 1073742038 }
|
|
tWrnOverrideAllSd NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Override All Sd"
|
::= { notifications 1073742039 }
|
|
tTimerON NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Timer ON"
|
::= { notifications 1073742040 }
|
|
tTimerOFF NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Timer OFF"
|
::= { notifications 1073742041 }
|
|
tres1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: res"
|
::= { notifications 1073742042 }
|
|
tres2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: res"
|
::= { notifications 1073742043 }
|
|
tECUFault NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: ECU Fault"
|
::= { notifications 1073742044 }
|
|
tWrnECUCommunicationFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn ECU Communication Fail"
|
::= { notifications 1073742045 }
|
|
tDPFRegenInhib NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: DPF RegenInhib"
|
::= { notifications 1073742047 }
|
|
tRegenerNeeded NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Regener Needed"
|
::= { notifications 1073742048 }
|
|
tRegenerNeededCHR21 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: RegenerNeeded!"
|
::= { notifications 1073742049 }
|
|
tHESTLamp NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: HEST Lamp"
|
::= { notifications 1073742050 }
|
|
tECURedLamp NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: ECU Red Lamp"
|
::= { notifications 1073742051 }
|
|
tECUYellowLamp NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: ECU Yellow Lamp"
|
::= { notifications 1073742052 }
|
|
tECUWaitToStart NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: ECU Wait To Start"
|
::= { notifications 1073742053 }
|
|
tWrnMainsVoltageDetected NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Mains Voltage Detected"
|
::= { notifications 1073742054 }
|
|
tGeneratorCCWRotation NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Generator CCW Rotation"
|
::= { notifications 1073742055 }
|
|
tMainsCCWRotation NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains CCW Rotation"
|
::= { notifications 1073742056 }
|
|
tMainsFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains Fail"
|
::= { notifications 1073742057 }
|
|
tMainsReturned NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Mains Returned"
|
::= { notifications 1073742058 }
|
|
tLoadOnMains NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Load on Mains"
|
::= { notifications 1073742059 }
|
|
tLoadOnGenset NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Load on Genset"
|
::= { notifications 1073742060 }
|
|
tAltConf1Active NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: AltConf1Active"
|
::= { notifications 1073742061 }
|
|
tAltConf2Active NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: AltConf2Active"
|
::= { notifications 1073742062 }
|
|
tWrnRentalTimer1 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Rental Timer 1"
|
::= { notifications 1073742063 }
|
|
tWrnRentalTimer2 NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Rental Timer 2"
|
::= { notifications 1073742064 }
|
|
tRentalTimer1Elapsed NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Rental Timer 1 Elapsed"
|
::= { notifications 1073742065 }
|
|
tRentalTimer2Elapsed NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Rental Timer 2 Elapsed"
|
::= { notifications 1073742066 }
|
|
tBOCRentalTimer1Exceeded NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: BOC Rental Timer 1 Exceeded"
|
::= { notifications 1073742067 }
|
|
tBOCRentalTimer2Exceeded NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: BOC Rental Timer 2 Exceeded"
|
::= { notifications 1073742068 }
|
|
tGenPeakStart NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Gen Peak start"
|
::= { notifications 1073742069 }
|
|
tPMSStart NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: PMS Start"
|
::= { notifications 1073742070 }
|
|
tRemoteStart NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Remote Start"
|
::= { notifications 1073742071 }
|
|
tAMFStart NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: AMF Start"
|
::= { notifications 1073742072 }
|
|
tManualStart NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Manual Start"
|
::= { notifications 1073742073 }
|
|
tTestStart NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Test Start"
|
::= { notifications 1073742074 }
|
|
tGenSetStop NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Gen-set Stop"
|
::= { notifications 1073742075 }
|
|
tManualStop NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Manual Stop"
|
::= { notifications 1073742076 }
|
|
tAMFStop NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: AMF Stop"
|
::= { notifications 1073742077 }
|
|
tRemoteStop NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Remote Stop"
|
::= { notifications 1073742078 }
|
|
tGenPeakStop NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Gen Peak Stop"
|
::= { notifications 1073742079 }
|
|
tPMSStop NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: PMS Stop"
|
::= { notifications 1073742080 }
|
|
tTESTModeON NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: TEST Mode ON"
|
::= { notifications 1073742081 }
|
|
tTESTModeOFF NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: TEST Mode OFF"
|
::= { notifications 1073742082 }
|
|
tGCBOpened NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: GCB Opened"
|
::= { notifications 1073742083 }
|
|
tGCBClosed NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: GCB Closed"
|
::= { notifications 1073742084 }
|
|
tMCBOpened NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: MCB Opened"
|
::= { notifications 1073742085 }
|
|
tMCBOpenExt NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: MCB Open Ext"
|
::= { notifications 1073742086 }
|
|
tMCBClosed NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: MCB Closed"
|
::= { notifications 1073742087 }
|
|
tSyncStarted NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: SyncStarted"
|
::= { notifications 1073742088 }
|
|
tRevSyncStarted NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: RevSyncStarted"
|
::= { notifications 1073742089 }
|
|
tReady NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Ready"
|
::= { notifications 1073742090 }
|
|
tIdleRun NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Idle Run"
|
::= { notifications 1073742091 }
|
|
tRunning NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Running"
|
::= { notifications 1073742092 }
|
|
tWarming NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Warming"
|
::= { notifications 1073742093 }
|
|
tSoftLoad NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Soft Load"
|
::= { notifications 1073742094 }
|
|
tLoaded NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Loaded"
|
::= { notifications 1073742095 }
|
|
tSoftUnload NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Soft Unload"
|
::= { notifications 1073742096 }
|
|
tCooling NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Cooling"
|
::= { notifications 1073742097 }
|
|
tEmergMAN NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Emerg MAN"
|
::= { notifications 1073742098 }
|
|
tNotReady NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Not Ready"
|
::= { notifications 1073742099 }
|
|
tWrnChargingAlternatorFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Charging Alternator Fail"
|
::= { notifications 1073742100 }
|
|
tWrnStopFail NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Stop fail"
|
::= { notifications 1073742101 }
|
|
tTestOnLoad NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Test On Load"
|
::= { notifications 1073742102 }
|
|
tFence1Alarm NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Fence 1 Alarm"
|
::= { notifications 1073742119 }
|
|
tFence2Alarm NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Fence 2 Alarm"
|
::= { notifications 1073742120 }
|
|
tWrnFuelTheft NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Wrn Fuel Theft"
|
::= { notifications 1073742141 }
|
|
tProtectionsDisabled NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Protections disabled"
|
::= { notifications 1073742258 }
|
|
tProtectionsEnabled NOTIFICATION-TYPE
|
OBJECTS {tControllerName, tSerNum, tTrapText}
|
STATUS current
|
DESCRIPTION "Event: Protections enabled"
|
::= { notifications 1073742259 }
|
|
|
|
|
--******************************************************************--
|
|
END
|